05000458/FIN-2013007-06
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Implement the Engineering Change Process for Appendix R Lighting |
Description | The team identified a Green finding for the failure to properly implement the engineering change process. Specifically, the licensee failed to update the Maintenance Rule program and perform the required preventive maintenance tasks after the addition of three 8-hour Appendix R emergency lights. During subsequent discharge testing, two of the three lights failed. The licensee entered this issue into their corrective action program as Condition Reports CR-RBS-2013-03118 and CR-RBS-2013-03273. The failure to properly implement the engineering change process was a performance deficiency. The performance deficiency was more than minor because it was associated with the protection against external events (fire) attribute of the Mitigating Systems Cornerstone and it adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The team evaluated this finding using Inspection Manual Chapter 0609, Appendix F, Fire Protection Significance Determination Process, dated September 20, 2013, because it affected the ability to reach and maintain safe shutdown conditions in case of a fire. The team assigned the finding a low degradation rating since the ability to reach and maintain safe shutdown conditions in the event of a control room fire would be minimally impacted by the failure of the three emergency lights to function for 8-hours. Specifically, the team determined that the alternative shutdown procedure provided operators with an alternate method of verifying that the emergency diesel generator breaker was closed. Because this finding had a low degradation rating, it screened as having very low safety significance (Green). The finding did not have a cross-cutting aspect since it was not indicative of present performance in that the performance deficiency occurred more than three years ago. |
Site: | River Bend |
---|---|
Report | IR 05000458/2013007 Section 1R05 |
Date counted | Dec 31, 2013 (2013Q4) |
Type: | Finding: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | A Barrett G Miller J Mateychick S Achen S Alferink |
INPO aspect | |
' | |
Finding - River Bend - IR 05000458/2013007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (River Bend) @ 2013Q4
Self-Identified List (River Bend)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||