05000458/FIN-2013007-05
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Maintain Communication Systems Required for Alternative Shutdown Scenarios |
Description | The team identified a Green non-cited violation of License Condition 2.C.(10) for the failure to implement and maintain in effect all provisions of the approved fire protection program. Specifically, the licensee failed to ensure that the communications systems would work under all postulated control room fire scenarios. The licensee entered this issue into their corrective action program as Condition Reports CR-RBS-2013-03243 and CR-RBS-2013-03397. The failure to ensure that the communications systems would work under all postulated control room fire scenarios was a performance deficiency. The performance deficiency was more than minor because it was associated with the protection against external events (fire) attribute of the Mitigating Systems Cornerstone and it adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The team evaluated this finding using Inspection Manual Chapter 0609, Appendix F, Fire Protection Significance Determination Process, dated September 20, 2013, because it affected the ability to reach and maintain safe shutdown conditions in case of a fire. A senior reactor analyst performed a Phase 3 evaluation to determine the risk significance of this finding since it involved a postulated control room fire that led to control room evacuation. The senior reactor analyst determined this finding was of very low safety significance (Green). The finding had a cross-cutting aspect in the Work Practices component of the Human Performance area because the licensee failed to ensure supervisory and management oversight of work activities, including contractors, such that nuclear safety was supported. |
Site: | River Bend |
---|---|
Report | IR 05000458/2013007 Section 1R05 |
Date counted | Dec 31, 2013 (2013Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | A Barrett G Miller J Mateychick S Achen S Alferink |
Violation of: | License Condition - Fire Protection License Condition |
CCA | H.2, Field Presence |
INPO aspect | LA.2 |
' | |
Finding - River Bend - IR 05000458/2013007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (River Bend) @ 2013Q4
Self-Identified List (River Bend)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||