05000454/FIN-2015008-03
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Evaluate the Adverse Effects of Sharing the RWSTs of Both Reactor Units |
| Description | The team identified a Severity Level IV NCV of 10 CFR 50.59(d)(1), Changes, Tests, and Experiments, and an associated finding of very-low safety significance (Green) for the licensees failure to perform a written safety evaluation that provided the bases for the determination that a change which resulted in the sharing of the refueling water storage tanks (RWSTs) of both reactor units did not require a license amendment. Specifically, the licensee did not evaluate the adverse effect of reducing reactor unit independence. The licensee captured this issue into their CAP with a proposed action to revise the associated calculation to remove the dependence on the opposite unit, and/or review the implications of crediting the opposite unit RWST under their 10 CFR 50.59 process. The performance deficiency was more than minor because it was associated with the Mitigating Systems cornerstone attribute of design control, and affected the cornerstone objective of ensuring the availability, reliability, and capability of mitigating systems to respond to initiating events to prevent undesirable consequences. In addition, it was associated with the Barrier Integrity cornerstone attribute of design control, and affected the cornerstone objective of providing reasonable assurance that physical design barriers protect the public from radionuclide releases caused by accidents or events. In addition, the associated traditional enforcement violation was more than minor because the team could not reasonably determine that the changes would not have ultimately required NRC prior approval. The finding screened as very-low safety significance (Green) because it did not result in the loss of operability or functionality, and it did not represent an actual open pathway in the physical integrity of the reactor containment. Specifically, the licensee reviewed the affected calculation and reasonably determined that enough conservatism existed such that adequate net positive suction head (NPSH) could be maintained without sharing the RWSTs of both reactor units. The team did not identify a cross-cutting aspect associated with this finding because it was confirmed not to be reflective of current performance due to the age of the performance deficiency. |
| Site: | Byron |
|---|---|
| Report | IR 05000454/2015008 Section 1R21 |
| Date counted | Sep 30, 2015 (2015Q3) |
| Type: | TEV: Severity level IV |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | A Della Grecab Palagi C Lipa D Betancourt J Leivo M Jones N Feliz-Adorno |
| Violation of: | 10 CFR 50.59 |
| INPO aspect | |
| ' | |
Finding - Byron - IR 05000454/2015008 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Byron) @ 2015Q3
Self-Identified List (Byron)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||