Finding | |
---|---|
Title | Failure to Monitor Performance of a Maintenance Rule Scoped System |
Description | The inspectors identified a Green noncited violation of10 CFR Part 50.65(a)(2) involving the failure to adequately monitor the performance of a maintenance rule scoped system. The licensees maintenance rule program required evaluation of the area radiation monitoring system for classification as a maintenance rule (a)(1) system after three failures within eighteen months. The licensee had identified two functional failures of the residual heat removal heat exchanger A hatch radiation monitor in June and July2008. The inspectors identified three other instances of functional failures on components that were used in plant emergency operating procedures and emergency preparedness procedures. These failures were not included in the licensees maintenance rule database. A total of five functional failures occurred in system components before the licensee considered evaluation of area radiation monitoring as a maintenance rule (a)(1) system in September 2009. The licensee entered this condition in the corrective action program as condition reports CR-GGN-2009-04853 and CR-GGN-2009-04857.The finding was more than minor because it was similar to Inspection Manual Chapter 0612, Appendix E, Example 7.d, in that equipment performance problems were such that effective control of performance or condition through appropriate preventive Maintenance Under (a)(2) could not be demonstrated. In addition, it affected the equipment performance attribute of the Mitigating Systems Cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. This finding was characterized under the significance determination process as having very low safety significance because the maintenance rule aspect of the finding did not cause an actual loss of safety function of the system nor did it cause a component to be inoperable. There is no crosscutting aspect associated with this performance deficiency since the cause of this issue does not reflect current licensee performance. |
Site: | Grand Gulf |
---|---|
Report | IR 05000416/2009004 Section 1R12 |
Date counted | Sep 30, 2009 (2009Q3) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.12 |
Inspectors (proximate) | J Kirkland P Elkmann C Graves R Smith A Barrett G Miller C Osterholtz D Proulx M Chambers R Kellar A Fairbanks D Bollock B Rice T Pate D Reinert D Strickland R Kumana K Clayton G Guerra |
INPO aspect | |
' | |
Finding - Grand Gulf - IR 05000416/2009004 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Grand Gulf) @ 2009Q3
Self-Identified List (Grand Gulf)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||