Finding | |
---|---|
Title | Failure to Establish As-found Testing on 6.9kV Vacuum Breakers |
Description | The team identified a non-cited violation of 10 CFR Part 50, Appendix B, Criterion XI, Test Control, for the licensees failure to establish a periodic as-found testing program of safety-related 6.9kV vacuum breakers in accordance with applicable design document IEEE 308-1971. The licensee entered this issue into their corrective action program as action request 01983086 and initiated a procedure change request to have the procedure changed to verify the as-found capability of the breakers before performing the first scheduled preventative maintenance on the breakers in April 2016. The performance deficiency was determined to be more than minor because, if left uncorrected, it had the potential to lead to a more significant safety concern. Specifically, the failure to establish as-found testing could mask degradation of the circuit breakers and decrease the reliability of the breakers to perform their safety-related function when called upon. The finding was determined to be of very low safety significance (Green), because it was a deficiency affecting the design or qualification of a structure, system, or component, which maintained its operability. The team determined that no finding cross-cutting aspect was applicable because the finding did not reflect current licensee performance. |
Site: | Harris |
---|---|
Report | IR 05000400/2015007 Section 1R17 |
Date counted | Dec 31, 2015 (2015Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.17 |
Inspectors (proximate) | E Stamm J Bartley M Riley S Herrick |
Violation of: | 10 CFR 50 Appendix B Criterion XI |
INPO aspect | |
' | |
Finding - Harris - IR 05000400/2015007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Harris) @ 2015Q4
Self-Identified List (Harris)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||