05000400/FIN-2015002-03
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | |
Description | An NRC-identified Green NCV of TS 6.8.1, Procedures and Programs, was identified for the licensees failure to perform adequate post modification tests (PMTs) on Motor Circuit Protectors (HMCP) breakers for dampers 1CZ-1 and 1CZ-2 as required by procedure AD EG-ALL-1155, Plant Modification Testing. The licensee entered this issue into the CAP as AR 741781. The licensee took immediate corrective action to manually close 1CZ-1 and 1CZ-2 to isolate the MCR boundary. The licensee also changed the setpoint, and revised the PMT to include the direction reversal. The licensees failure to perform adequate PMTs on HMCP breakers for 1CZ-1 and 1CZ-2 as required by procedure AD-EG-ALL-1155 was a performance deficiency. The performance deficiency was more than minor because it was associated with the Procedure Quality Attribute of the Barrier Integrity Cornerstone and adversely affected the cornerstone objective to provide reasonable assurance that physical design barriers protect the public from radionuclide releases caused by accidents or events. Specifically, the licensee failed to test the highest instantaneous current the HMCP breakers would be expected to experience. This would be during the dampers direction reversal, during the PMT. Therefore, the HMCP breakers for 1CZ-1 and 1CZ-2 had the potential to trip open during a control room isolation signal (CRIS), causing unfiltered inleakage into the MCR envelope in the event of a radiological emergency. Using IMC 0609.04, Initial Characterization of Findings, issued on June 19, 2012, and IMC 0609, Appendix A, The Significance Determination Process (SDP) for Findings At- Power, issued on June 19, 2012; the inspectors concluded that a detailed risk evaluation was required since the finding represented a degradation of the barrier function of the control room against smoke and the radiological barrier function provided for the control room. This conclusion was based upon the potential of the HMCP breakers tripping due to a high instantaneous current, during an event that would cause a CRIS such as a high radiation signal at the normal intake or emergency intakes, or smoke detection at the normal intake. A detailed risk evaluation was performed in accordance with the guidance of NRC IMC 0609 Appendix A. A bounding analysis was performed considering potential demands on MCR habitability due to radiation and smoke effects. The major analysis assumptions included: a 94-day exposure period, recovery credit for manual closure of either 1CZ-1 or 1CZ-2, at power core damage probability radiation impact determined from the NRC SPAR model, fuel pool radiation impact from NUREG-1738, and fire risk from IMC 0609 Appendix F. The dominant sequence was a fire impacting the MCR with smoke, failure of operators to isolate the MCR dampers resulting in loss of the operators leading to loss of core heat removal. The risk of the performance deficiency was mitigated by the low initiating event probabilities and the recovery likelihood of MCR damper closure. The result of the analysis was an increase in core damage frequency of < 1.0E-6/year a GREEN finding of very low safety significance. The finding was assigned to the cross-cutting aspect of Work Management in the Human Performance cross-cutting area because the licensees work management processes failed to develop and implement a PMT that adequately tested the breakers to their designed performance. |
Site: | Harris |
---|---|
Report | IR 05000400/2015002 Section 1R18 |
Date counted | Jun 30, 2015 (2015Q2) |
Type: | NCV: Green |
cornerstone | Barrier Integrity |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.18 |
Inspectors (proximate) | R Kellner R Williams W Loo W Pursley A Butcavage A Sengupta G Hopper J Austin J Parent M Riches P Lessard R Hamilton |
Violation of: | Technical Specification - Procedures Technical Specification |
CCA | H.5, Work Management |
INPO aspect | WP.1 |
' | |
Finding - Harris - IR 05000400/2015002 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Harris) @ 2015Q2
Self-Identified List (Harris)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||