| Title | Lightning Induced Trips of Safety-Related Chillers |
| Description | A URI was identified by the inspectors for safety-related chiller trips due to lightning. On October 13, 2011, following a lightning strike at the station the A train safety-related chiller tripped on overcurrent when the 250 amp limit for circuit 1 of the two circuit chiller was exceeded. The B train of chilled water system was also inoperable which required the licensee to enter TS 3.0.3. The B train chiller was returned to an operable status to allow exiting TS 3.0.3. The licensee entered the problem into their CAP as CR-11-05225 and performed an operability evaluation. The evaluation also referenced CR-11-03187 that documented a similar, previous trip of the C chiller while aligned to A train power on June 5, 2011, during a lightning storm. The inspectors continue to evaluate the regulatory aspects of these events. This issue is identified as URI 05000395/2011005-02, Lightning Induced Trips of Safety-Related Chillers. |
| Site: | Summer |
|---|---|
| Report | IR 05000395/2011005 Section 4OA2 |
| Date counted | Dec 31, 2011 (2011Q4) |
| Type: | URI: |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |