05000395/FIN-2011006-02
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Correctly Translate the Design Basis into Procedures for Low EDG Air Pressure and Low Thermal Barrier Heat Exchanger Flow |
| Description | The team identified a non-cited violation (NCV) of 10 CFR 50, Appendix B, Criterion III, Design Control involving two examples. In one example, the licensee did not properly translate the instrument uncertainties associated with the EDG low pressure alarm and pressure indicator into operating procedures (OP) and alarm response procedures (ARP). In the second example, the licensee failed to translate the minimum thermal barrier flow requirements into applicable abnormal operating procedures (AOP) and ARPs. The licensee entered these issues into their corrective action program as CR 11-00744 and CR-11-00955. The licensees failure to correctly translate the applicable design bases information for the EDG air start system and the thermal barrier heat exchangers setpoints into procedures was a performance deficiency. The finding was determined to be more than minor because it was associated with the Procedure Quality attribute of the Mitigating System Cornerstone and affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the failure to translate the appropriate values into the procedures described above adversely affected the quality of procedures for abnormal and alarm conditions that are required by Regulatory Guide 1.33, Quality Assurance Program Requirements. The inadequate procedures adversely affected operator action to assess operability and to combat deficiencies associated with risk significant equipment. The team assessed the finding using the SDP and determined that the finding was of very low safety significance (Green) because it was a design deficiency confirmed not to result in the loss of operability or functionality, did not represent the loss of a system safety function and did not screen as potentially risk significant due to a seismic, flooding, or severe weather initiating event. A cross-cutting aspect was not identified because the finding does not represent current performance. |
| Site: | Summer |
|---|---|
| Report | IR 05000395/2011006 Section 1R21 |
| Date counted | Jun 30, 2011 (2011Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | D Jones D Mas-Penaranda M Yeminy S Sandal B Desai J Eargle |
| INPO aspect | |
| ' | |
Finding - Summer - IR 05000395/2011006 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Summer) @ 2011Q2
Self-Identified List (Summer)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||