Finding | |
---|---|
Title | Failure to Develop a Procedure to Ensure an Emergency Diesel Generator Alarm Device was Calibrated or Tested |
Description | The team identified a NCV of Technical Specification 6.8, Procedures and Programs , for the licensees failure to develop a procedure to ensure an EDG alarm device was properly calibrated or tested. Specifically, the component validating the full status of the EDG fuel header lines had never been calibrated, nor tested. The licensee entered these issues into their corrective action program as CR-11-00984 The team determined that the licensees failure to develop and implement a procedure that ensured the EDG ultrasonic alarm device was properly calibrated or tested was a performance deficiency. This performance deficiency is more than minor because it affected the mitigating systems cornerstone attribute of ensuring the availability, reliability, and capability of safety systems that respondto initiating events. Specifically, the lack of calibration and testing of a non safety-related device could adversely affect the capability of the EDG to start and load within 10 seconds as required by TS. In accordance with NRC IMC 0609.04, Initial Screening and Characterization of Findings , the inspectors conducted a Phase 1 SDP screening and determined the finding to be of very low safety significance (Green) because it was not a design issue resulting in loss of function, it did not represent an actual loss of a system safety function, it did not result in exceeding a TS allowed outage time, and it did not affect external event mitigation. A review of the most recent EDG tests demonstrated that the EDGs started within the required 10 seconds thereby indicating that the fuel line header was not empty at the time of the test. A cross-cutting aspect was not identified because the finding does not represent current performance. |
Site: | Summer ![]() |
---|---|
Report | IR 05000395/2011006 Section 1R21 |
Date counted | Jun 30, 2011 (2011Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | D Jones D Mas-Penaranda M Yeminy S Sandal B Desai J Eargle |
INPO aspect | |
' | |
Finding - Summer - IR 05000395/2011006 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Summer) @ 2011Q2
Self-Identified List (Summer)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||