05000390/FIN-2013010-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Implement Corrective Actions to Identify and Evaluate Effects of Harmonics on Degraded Voltage Relay Function |
| Description | The NRC identified a non-cited violation of 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Action, for the licensees failure to implement corrective actions to identify and evaluate the effects of electrical system harmonics on safety-related under-voltage relays. This was a performance deficiency. The licensee entered this issue into their corrective action program as Problem Evaluation Reports 515413 and 703444. The licensee also established a preventative maintenance program to monitor motors powered from the 6.9 kilovolt shutdown boards for harmonic distortion until further monitoring and evaluation of harmonic distortion on the 6.9 kilovolt shutdown board degraded voltage relays can be completed. The performance deficiency was more than minor because it affected the design control attribute of the Mitigating Systems cornerstone and adversely impacted the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, at the time of identification, there was reasonable doubt as to whether the degraded voltage scheme would perform as required by the Watts Bar 1 Technical Specifications during design basis conditions. The inspector determined the finding to be of very low safety significance (Green) because the finding was a deficiency affecting the design or qualification of a mitigating structure, system, or component, and the structure, system, or component maintained its operability and functionality. Because the opportunity to identify the impact of harmonics on degraded voltage relay performance occurred in 1993, the inspector determined that no cross-cutting aspect was applicable because the finding was not indicative of current licensee performance. |
| Site: | Watts Bar |
|---|---|
| Report | IR 05000390/2013010 Section 1R21 |
| Date counted | Sep 30, 2013 (2013Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | R Nease M Riley |
| Violation of: | 10 CFR 50 Appendix B Criterion XVI Technical Specification |
| INPO aspect | |
| ' | |
Finding - Watts Bar - IR 05000390/2013010 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Watts Bar) @ 2013Q3
Self-Identified List (Watts Bar)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||