Finding | |
---|---|
Title | Failure to Report Unanalyzed Condition Related to External Flooding |
Description | The inspectors identified an AV of 10 CFR 50.72(b)(3)(ii)(B), Immediate Notification Requirements for Operating Nuclear Reactors, for failure to report within eight hours an unanalyzed condition that significantly degraded plant safety. Specifically, the licensee failed to notify the NRC upon discovery that a postulated PMF would result in the overtopping of earthen dams not previously assumed in the plant design. The failure to report this unanalyzed condition resulted in the NRC not being made aware of a condition which would have resulted in additional NRC review. Specifically, the failure to notify the NRC within eight hours of discovery of an unanalyzed condition that significantly degraded plant safety and resulted in an unacceptable change to the facility or procedures. The inspectors determined an evaluation for cross-cutting aspect was not applicable because this is a traditional enforcement violation. |
Site: | Watts Bar |
---|---|
Report | IR 05000390/2012009 Section 1R01 |
Date counted | Mar 31, 2013 (2013Q1) |
Type: | TEV: Severity level III |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.01 |
Inspectors (proximate) | K Miller R Monk S Shaeffer |
Violation of: | 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition 10 CFR 50.72 |
INPO aspect | |
' | |
Finding - Watts Bar - IR 05000390/2012009 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Watts Bar) @ 2013Q1
Self-Identified List (Watts Bar)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||