05000313/FIN-2014009-01
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Inadequate Flood Protection for Auxiliary and Emergency Diesel Fuel Storage Buildings |
Description | Apparent Violation. The inspectors identified a finding of preliminary substantial safety significance (Yellow) for the failure to design, construct, and maintain the Units 1 and 2 auxiliary and emergency diesel fuel storage buildings in accordance with the safety analysis reports' description of internal and external flood barriers so that they could protect safety-related equipment from flooding. Two apparent violations were associated with this finding: Contrary to 10 CFR Part 50, Appendix B, Criterion Ill, "Design Control," the licensee failed to assure that regulatory requirements and the design basis were correctly translated into specifications, drawings, procedures, and instructions, and that design changes were subjected to design control measures commensurate with those applied to the original design. Contrary to 10 CFR Part 50, Appendix B, Criterion V, "Instructions, Procedures, and Drawings," the licensee failed to prescribe documented instructions for activities affecting quality and accomplish activities affecting quality in accordance with drawings. The licensee entered these issues into the corrective action program as Condition Reports CR-ANO-C-2013-01304 and CR-ANO-C-2014-00259. The licensee resolved the safety concern by replacing the degraded seals or parts, installing penetration seals, implementing compensatory measures, and/or incorporating instructions into procedures. The inspectors determined that the finding was more than minor because it was associated with the protection against external factors attribute of the mitigating systems cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the performance deficiency resulted in the vulnerability to flooding of safety-related equipment necessary to maintain core cooling in the auxiliary and emergency diesel fuel storage buildings. The inspectors used Inspection Manual Chapter 0609, Attachment 0609.04, "Initial Characterization of Findings," dated June 19, 2012, and Appendix A, "The Significance Determination Process (SOP) for Findings At-Power," dated June 19, 2012, to evaluate the significance of the finding. In accordance with Appendix A, Exhibit 4, the inspectors determined that a detailed risk evaluation was necessary because, if the flood barriers were assumed to be completely failed, two or more trains of a multi-train system would be degraded during an external flood. The NRC risk analysts determined that the finding should be evaluated in accordance with NRC Inspection Manual Chapter 0609, Appendix M, "Significance Determination Process Using Qualitative Criteria," April 12, 2012. Appropriate quantitative significance determination process tools did not exist to provide a reasonable estimate of the significance because a plant-specific flood hazard analysis did not exist and was not expected to be available until sometime in 2015. The risk analysts used NRC Inspection Manual Chapter 0609, Appendix M, Table 4.1, "Qualitative Decision-Making Attributes for NRC Management Review," to determine the preliminary safety significance of the finding. The following were the dominant considerations in reaching a preliminary risk determination conclusion: With respect to the auxiliary and emergency diesel fuel storage buildings, there were more than 100 unknown ingress pathways for a flooding event, therefore if an external flood above grade level were to occur, the buildings would flood. The unexpected rate of flooding would likely be beyond the licensee's capability to prevent or mitigate as equipment and connections associated with alternative mitigating strategies, could be submerged. All reactor core cooling and makeup could fail due to significant flooding of the auxiliary and emergency diesel fuel storage buildings. The change in core damage frequency was quantitatively bounded below 2 x 1 o-3 and qualitatively determined to likely be less than 1 x 1 o-4. The bounding and qualitative results are based on the frequency of the probable maximum flood event and a loss of all equipment needed for core cooling and makeup. This finding was preliminarily determined to be of substantial safety significance (Yellow) for Unit 1 and Unit 2, as determined by a Significance and Enforcement Review Panel. This finding had a cross-cutting aspect in the area of human performance related to maintaining design margins. Specifically, the licensee did not design, construct, and/or maintain over 100 flood barriers to ensure design margins were sustained [H.6]. |
Site: | Arkansas Nuclear |
---|---|
Report | IR 05000313/2014009 Section 1R01 |
Date counted | Sep 30, 2014 (2014Q3) |
Type: | Violation: Yellow |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.01 |
Inspectors (proximate) | B Tindell D Loveless G Werner J Melfi |
Violation of: | 10 CFR 50 Appendix B Criterion V |
CCA | H.6, Design Margins |
INPO aspect | WP.2 |
' | |
Finding - Arkansas Nuclear - IR 05000313/2014009 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Arkansas Nuclear) @ 2014Q3
Self-Identified List (Arkansas Nuclear)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||