05000285/FIN-2012007-03
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Alternate Shutdown Procedure Does Not Account for Single Worst Case Spurious Actuations |
| Description | The inspectors identified a non-cited violation with two examples related to the failure to establish an alternate shutdown capability that met the requirements of License Condition 3.D and the performance criteria in 10 CFR Part 50, Appendix R,Section III.L. Specifically, the licensee failed to establish an alternate shutdown capability that accounted for the effects of an inadvertent safety injection actuation signal and failed to ensure the plant parameters remained similar to those experienced during a loss of normal a.c. power following single spurious component actuations. The failure to meet the performance goals prescribed by the alternate shutdown capability was a performance deficiency. The performance deficiency was more than minor because it was associated with the protection against external events (fire) attribute of the Mitigating Systems Cornerstone and it adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The inspectors evaluated this deficiency using Inspection Manual Chapter 0609, Appendix F, Fire Protection Significance Determination Process. The performance deficiency affected the fire protection defense-in depth strategies involving post-fire safe shutdown systems. Because Appendix F does not address control room fire scenarios, a senior reactor analyst evaluated the significance of this performance deficiency. This finding was evaluated using the process in Inspection Manual Chapter 0609, Attachment 4, Phase 1 Initial Screening and Characterization of Findings, and was determined to be of very low safety significance because the finding was not a design deficiency, confirmed not to result in loss of functionality, did not result in loss of a system safety function, did not result in loss of the safety function for a single train, did not result in loss of safety function for maintenance rule equipment, and did not potentially affect risk significant external initiating events. Because the original failure to comply with the regulations had occurred longer than three years prior to this inspection, this finding did not reflect current licensee performance. |
| Site: | Fort Calhoun |
|---|---|
| Report | IR 05000285/2012007 Section 1R05 |
| Date counted | Jun 30, 2012 (2012Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | G Miller G Pick J Mateychick J Watkins S Makor |
| INPO aspect | |
| ' | |
Finding - Fort Calhoun - IR 05000285/2012007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Fort Calhoun) @ 2012Q2
Self-Identified List (Fort Calhoun)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||