Finding | |
|---|---|
| Title | Failure to Correct Degraded Electrical Insulation on the Component Cooling Water System Motors |
| Description | The NRC identified a non-cited violation of 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Action, for the licensees failure to promptly correct conditions adverse to quality. Specifically, the licensee failed to correct degraded conditions associated with the electrical supply cable insulation for the component cooling water motors originally identified in 2003. In addition, the licensee did not have justification for the temporary repairs made to the cables nor for continued operability. The failure of the licensee to promptly correct conditions adverse to quality associated with the loss of full qualification of plant components due to degraded electrical supply cable insulation was a performance deficiency. This performance deficiency was more than minor because it was associated with the equipment performance attribute of the mitigating systems cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The finding has very low safety significance because it did not represent a loss of system safety function, did not represent the actual loss of safety function of a single train for greater than its technical specification allowed outage time, and did not screen as potentially risk significant due to a seismic, flooding, or severe weather initiating event. This finding has a crosscutting aspect in the resources component of the human performance area because the licensee failed to minimize long-standing equipment issues by correcting these deficiencies. |
| Site: | Fort Calhoun |
|---|---|
| Report | IR 05000285/2011006 Section 4OA2 |
| Date counted | Dec 31, 2011 (2011Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71152 |
| Inspectors (proximate) | C Osterholtz H Freeman J Wingebach R Alexander R Cohen R Latta |
| CCA | H.6, Design Margins |
| INPO aspect | WP.2 |
| ' | |
Finding - Fort Calhoun - IR 05000285/2011006 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Fort Calhoun) @ 2011Q4
Self-Identified List (Fort Calhoun)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||