05000285/FIN-2011006-05
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Establish Adequate Measures to Maintain Vendor Manual Design Control Information |
| Description | The NRC identified a non-cited violation of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for the failure to establish adequate measures for the selection and review for suitability of application of parts equipment, and processes that are essential to the safety-related function of structures, systems, and components. Specifically, the team identified numerous condition reports involving inadequate implementation of vendor manual information that affected the suitability of application of parts equipment, and processes that are essential to the safety-related function of structures, systems, and component repair and refurbishment activities over an extended period. The failure to properly maintain design information associated with vendor manuals to ensure information, which affected the suitability of application of parts equipment, and processes, essential to the safety-related function of structures, systems, and component repair and refurbishment activities, was a performance deficiency. The performance deficiency was determined to be more than minor because it was associated with the design control attribute of the Mitigating Systems Cornerstone, and affected the associated cornerstone objective to ensure availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences, and was therefore a finding. The finding has very low safety significance because it did not represent a loss of system safety function, did not represent the actual loss of safety function of a single train for greater than its technical specification allowed outage time, and did not screen as potentially risk significant due to a seismic, flooding, or severe weather initiating event. This finding has a crosscutting aspect in the decision making component of the human performance area because the licensee failed to make safety-significant decision using a systemic process which included formally defining the authority and roles for decisions in that the licensee chose not to fill key positions responsible for the program for several years |
| Site: | Fort Calhoun |
|---|---|
| Report | IR 05000285/2011006 Section 4OA2 |
| Date counted | Dec 31, 2011 (2011Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71152 |
| Inspectors (proximate) | C Osterholtz H Freeman J Wingebach R Alexander R Cohen R Latta |
| CCA | H.13, Consistent Process |
| INPO aspect | DM.1 |
| ' | |
Finding - Fort Calhoun - IR 05000285/2011006 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Fort Calhoun) @ 2011Q4
Self-Identified List (Fort Calhoun)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||