05000272/LER-1980-002, Forwards LER 80-002/03L-0.Previous Transmittal Included Incorrect LER Attachments

From kanterella
(Redirected from 05000272/LER-1980-002)
Jump to navigation Jump to search
Forwards LER 80-002/03L-0.Previous Transmittal Included Incorrect LER Attachments
ML18081B083
Person / Time
Site: Salem 
Issue date: 02/05/1980
From: Librizzi D
Public Service Enterprise Group
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
NUDOCS 8002210479
Download: ML18081B083 (3)


LER-1980-002, Forwards LER 80-002/03L-0.Previous Transmittal Included Incorrect LER Attachments
Event date:
Report date:
2721980002R00 - NRC Website

text

\\.

PS~G February 5, 1980 Mr. Boyce H. Grier Director of USNRC Off ice of Inspection ~nd Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

LICENSE NO. DPR-70 DOCKET NO. 50-272 REPORTABLE OCCURRENCE 80-02/03L Pursuant to the requirements of Salem Generating Station Unit No. 1 Technical Specifications, Section 6.9.1, we are submitting Licensee Event Report for Reportable Occurrence 80-02/03L.

This repoit is required within thirty (30) days of the occurrence.

CC:

Sincerely yours,

.. *j

" t...

) )

F. P. Librizzi General Manager -

Electric Production Director, Office of Inspection and Enforcement (30 copies)

Director, Office of Management Information and Program Control (3 copies) ll \\IC..,111

~11111* I

Report Number:

Report Date:

80-02/03L 2/05/80 Occurrence Date:

1/04/80 Facility:

Salem Generating Station Public Service Electric & Gas Company Hanco~k's Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

.Failure to Perform a Functional Test of the Power Range Neutron Flux Low Trip Setpoint when Greater than 25% Reactor Power CONDITIONS PRIOR TO OCCURRENCE:

Load Changes due to Routine Power Operations DESCRIPTION OF OCCURRENCE:

A supervisor in the Instruments and Controls Group identified the failure of our procedure to comply with the Technical Specifications

(

{3.3.1.1) by not testing the low trip setpoint when performed

\\

greater than 25% reactor power.

(

Th~ design of the circuit for the power range neutron flux detector did not allow testing of setpoints lower than the power level being generated.

A test signal was inserted, adding to the power level indicated, to reach the desired level in order to perform the monthly functional test.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:.

The manufacturer's, Westinghouse, generic procedure to perform a functional test of the trip setpoints on the power range neutron flux recommends the method used by the Instruments and Controls Group to perform this test.

ANALYSIS OF OCCURRENCE:

The procedure used at our station was essentially a duplicate of the generic procedure provided by the manufacturer and the conditions overlooked by the manufacturer were also overlooked by our personnel.

This problem has* existed since initial licensing in 1976 until the start of our 1979 Refueling Outage.

During the outage, the procedure was* evaluated and corrected.

Since the outage, the monthly functional tests have been completed in accordance with Technical Specification 3.3.1.1.

LER ~80-02/03L CORRECTIVE ACTION:

An on-the-spot change was written to the functional test procedure which allow the detector to be removed from the circuit and a test signal is inserted to simulate all power levels.

FAILURE DATA:

Not Applicable Prepared By M.. J. Murphy Manager -

Salem Generating Station SORC Meeting No.