05000263/FIN-2014008-03
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Repairs Credited for Hot Shutdown Conditions |
| Description | The inspectors identified a finding of very-low-safety significance and associated NCV of 10 CFR Part 50, Appendix R,Section III.G.1 for the licensees failure to provide one train of systems necessary to achieve and maintain hot shutdown conditions. Specifically, the licensee failed to ensure that a sufficient quantity of nitrogen existed from the alternate nitrogen system to supply credited SRVs for the duration that the plant is expected to be in hot shutdown following a fire. Instead, the licensee relied on replacing the nitrogen bottles using a repair procedure. Similarly, the licensee failed to ensure one train of diesel fuel oil transfer system for the emergency diesel generator (EDG) was free of fire damage in the event of a fire. Instead the licensee relied upon repair activities for fuel transfer. The licensee entered the issue into their Corrective Action Program and established hourly fire tours in the affected fire areas. The performance deficiency was determined to be more than minor because the licensee failed to ensure that safe shutdown equipment and circuits (i.e., alternate nitrogen system and EDG fuel oil) were free of fire damage for the duration that could be expected to maintain hot shutdown conditions following a fire. These repair activities could have potentially affected the plant and operators activities during a challenging fire event. The finding affected the Mitigating Systems cornerstone. The finding represented a low degradation and therefore the inspectors determined that the finding screened as having very-low-safety significance (Green) in Task 1.3.1 of IMC 0609, Appendix F. The inspectors determined that the finding has a cross-cutting aspect in the area of Human Performance because the licensee did not recognize and plan for the possibility of mistakes, latent issues, and inherent risk, even while expecting successful outcomes. Individuals did not implement appropriate error reduction tools. |
| Site: | Monticello |
|---|---|
| Report | IR 05000263/2014008 Section 1R05 |
| Date counted | Mar 31, 2014 (2014Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | A Dahbur D Oliver R Daley R Winter |
| Violation of: | 10 CFR 50 Appendix R |
| CCA | H.12, Avoid Complacency |
| INPO aspect | QA.4 |
| ' | |
Finding - Monticello - IR 05000263/2014008 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Monticello) @ 2014Q1
Self-Identified List (Monticello)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||