Title | EDG Fuel Oil Supply System Design does Not Meet the Single Failure Criteria |
Description | The inspectors identified a finding of very low safety significance and associated NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for the failure to ensure the emergency diesel generator (EDG) fuel oil system original design met the single failure criteria with respect to having two safety-related pumps that were physically separated and provided with independent piping and safety-related power source. The licensee entered this finding into their Corrective Action Program and implemented actions that included separating the fuel oil system into individual trains for each EDG, providing each pump with safety-related power, and tracking the final resolution of this issue to completion. The performance deficiency was determined to be more than minor because the finding was associated with the Mitigating Systems cornerstone attribute of design control and affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The finding screened as very low safety significance (Green) based on a Detailed Risk-Evaluation performed by the Senior Reactor Analysts. The inspectors did not identify a cross-cutting aspect associated with this finding because the finding was not representative of current performance. |
Site: | Monticello |
---|---|
Report | IR 05000263/2013007 Section 1R21 |
Date counted | Dec 31, 2013 (2013Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | A Dunlop G Hausman I Hafeez R Daley |
Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
INPO aspect | |
' | |
Finding - Monticello - IR 05000263/2013007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Monticello) @ 2013Q4
Self-Identified List (Monticello)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||