05000335/FIN-2016010-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Implement Qualification Procedures and Methods in Accordance with IEEE 323-1974 |
Description | The inspectors identified three examples of a green non-cited violation of Title 10 Code of Federal Regulations (CFR) Part 50.49.e.(5) aging for the licensees failure to assure conformance with the qualification procedures and methods specified in IEEE 323-1974 IEEE Standard for Qualifying Class 1E Equipment for Nuclear Power Generating Stations as amended by RG 1.89 Environmental Qualification of Certain Electric Equipment Important to Safety for Nuclear Power Plants. In response to this issue, the licensees immediate corrective actions included an immediate determination of operability, in which the licensee concluded that that for the specific examples documented in this violation, the affected components were operable. The licensee entered these issues in the corrective action program for resolution as AR2128753, AR02128366, AR2128755, and AR2135777. The three performance deficiencies were determined to be more than minor because they were associated with the Mitigating Systems cornerstone attribute of Design Control and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, with time in service, significant aging degradation of SSCs increases the likelihood these SSCs could unpredictably fail when called upon to perform their designed safety function. The team used IMC 0609 Attachment 4, Initial Characterization of Findings, issued June 19, 2012, and IMC 0609 Appendix A, The Significance Determination Process (SDP) for Findings At-Power, issued June 19, 2012, and determined the finding to be of very low safety significance (Green) because the findings were a deficiency affecting the design of a mitigating structure, system, or component (SSC), and the SSC maintained their operability or functionality. This finding was assigned a cross-cutting aspect of H.6 Design Margins in the Human Performance Area because the finding was indicative of current licensee performance and the licensee did not operate and maintain equipment within design margins and margins were not carefully guarded and were changed without a systematic and rigorous process (WP.2). |
Site: | Saint Lucie |
---|---|
Report | IR 05000335/2016010 Section 1R21 |
Date counted | Jun 30, 2016 (2016Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21N |
Inspectors (proximate) | J Bartley S Herrick T Fanelli |
Violation of: | 10 CFR 50.49 |
CCA | H.6, Design Margins |
INPO aspect | WP.2 |
' | |
Finding - Saint Lucie - IR 05000335/2016010 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Saint Lucie) @ 2016Q2
Self-Identified List (Saint Lucie)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||