ENS 44263
ENS Event | |
---|---|
06:57 Jun 4, 2008 | |
Title | High Pressure Coolant Injection System Declared Inoperable |
Event Description | On 6/04/08 at 0257, the High Pressure Coolant Injection (HPCI) system was declared inoperable. The HPCI pump was placed in service to evaluate HPCI pump start performance. The HPCI pump tripped on low suction pressure when started. An Event Response Team is assembled to investigate the cause of the low suction trip of HPCI.
Loss of the HPCI system is reportable under 10 CFR 50.72(b)(3)(v) as loss of a single train safety system required to mitigate the consequences of an accident. No additional Emergency Core Cooling Systems or Safety Related equipment was inoperable during this time period. The licensee is in a 14 day LCO due to TS 3.5.1. The licensee notified the NRC Resident Inspector.
The purpose of this notification is to retract a previous report made on 6/04/08 at 0758 (EN 44263). The High Pressure Coolant Injection (HPCI) system was declared inoperable. The HPCI pump was placed in service to evaluate HPCI pump start performance. The HPCI pump received a momentary low suction pressure trip signal in the test configuration alignment. Since the initial report, failure mode cause technical evaluation has determined that the HPCI was always able to satisfy its design safety function. Additional instrumentation was added and data collected from seven HPCI test runs was analyzed. As evidenced by the successful completion of its IST test and the detailed review of multiple HPCI runs, the HPCI system was always able to perform its design function because: --- HPCI restarted on its own with no operator action. --- HPCI would meet its injection time requirements. --- Required flows and required pressures were reached on all HPCI runs . Therefore HPCI was never inoperable. The NRC resident has been informed of the retraction. R1DO (Henderson) notified. |
Where | |
---|---|
Hope Creek New Jersey (NRC Region 1) | |
Reporting | |
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
Time - Person (Reporting Time:+1.02 h0.0425 days <br />0.00607 weeks <br />0.0014 months <br />) | |
Opened: | Bernard Litkett 07:58 Jun 4, 2008 |
NRC Officer: | John Knoke |
Last Updated: | Jun 6, 2008 |
44263 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 44263\u003C/a\u003E - \u003Ca href=\"/Hope_Creek\" title=\"Hope Creek\"\u003EHope Creek\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EHigh Pressure Coolant Injection System Declared Inoperable\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 44263 - Hope Creek\n","link":"","lat":39.46618888888889,"lon":-75.53605833333333,"icon":"/w/images/c/cc/PSEG_icon.png"}],"imageoverlays":null} | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (95 %) |
After | Power Operation (95 %) |
Hope Creek with 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
WEEKMONTHYEARENS 564942023-04-30T05:00:00030 April 2023 05:00:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded Primary Containment Integrity Degraded ENS 536252018-09-26T04:00:00026 September 2018 04:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Core Injection (Hpci) System Inoperable ENS 521592016-08-07T05:01:0007 August 2016 05:01:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Declared Inoperable ENS 499092014-03-13T10:31:00013 March 2014 10:31:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Standby Liquid Control System Sample Concentration Outside Technical Specification Limits ENS 496712013-12-20T18:03:00020 December 2013 18:03:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Both Control Room Air Conditioning Subsystems Inoperable ENS 488972013-04-08T15:15:0008 April 2013 15:15:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Declared Inoperable During Surveillance Testing ENS 482742012-09-04T04:00:0004 September 2012 04:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection Declared Inoperable ENS 477452012-03-15T00:34:00015 March 2012 00:34:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Inoperable Due to Failure of Turbine Governor Valve ENS 475852012-01-12T03:15:00012 January 2012 03:15:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Declared Inoperable ENS 445412008-10-05T08:31:0005 October 2008 08:31:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection (Hpci) System Inoperable ENS 442632008-06-04T06:57:0004 June 2008 06:57:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Declared Inoperable ENS 441542008-04-22T12:41:00022 April 2008 12:41:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Loss of Safety Function Due to Blown Fuse ENS 439202008-01-19T16:52:00019 January 2008 16:52:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident 'A' and 'B' Recirculation Pump Motor Generator Overspeed Stops Found Set High (Non-Conservative) During Surveillance Testing ENS 437792007-11-11T21:39:00011 November 2007 21:39:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Hpci Inoperable Due to Valve Failure During Quarterly Surveillance ENS 435372007-07-31T04:51:00031 July 2007 04:51:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Declared Inoperable ENS 424222006-03-14T21:59:00014 March 2006 21:59:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Loss of Control Room Emergency Filtration ENS 419952005-09-15T01:38:00015 September 2005 01:38:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Failed Surveillance Testing ENS 418522005-07-19T07:45:00019 July 2005 07:45:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident High Pressure Coolant Injection System Inoperable ENS 408762004-07-16T14:00:00016 July 2004 14:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Shutdown/Loss of Single Safety Function ENS 406482004-04-06T00:30:0006 April 2004 00:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Offsite Electrical Power Sources and 1E 4Kv Distribution Buses Inoperable ENS 405392004-02-23T06:52:00023 February 2004 06:52:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Started Due to Grass Intrusion ENS 402252003-10-05T07:00:0005 October 2003 07:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Inoperable Trains of Control Room Emergency Filtration at Hope Creek ENS 401072003-08-27T13:24:00027 August 2003 13:24:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Control Room Access Door Latch Was Determiend to Be Not Fully Engaging. 2023-04-30T05:00:00 | |