Public Version of Revision 6 to Emergency Plan Implementing Procedure 3100025E, Fire Emergencies.
ML17212A594
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 05/01/1981
From:
FLORIDA POWER & LIGHT CO.
To:
Shared Package
ML17212A592 List:
References
3100025E, NUDOCS 8109020026
Download: ML17212A594 (8)


Text

3etp~t't'LORIDAPOWER&LIGHTCOMPANYST.LUCIEUNITi'llE-PLANIMPLEMENTINGPROCEDURE3100025EREVISION61.0Title:FIREEMERGENCIES2.0~Atoval:ReviewedbyFacilityReviewGroupApprovedbyK.N.HarrisPlantManagerJuly25,1975Jul29,1975Revision6ReviewedbyFRGApprovedby3.0~3coe:PlantManager/is,19K/Z,19~3.1PurposeThisprocedureprovidesinstructionstocontrolandextinguishfires,minimizedamageandpreventpersonalinjuries.3.2Discussion3.2.1AnyuncontrolledfireisconsideredaFireEmergency.Inordertocontrolandextinguishafire,afirefightingorganizationhasbeenestablished.3.2.2TheFireTeamiscomposedofmembersoftheOperatinggroupassignedtotheSt.LuciePlant.ThemembersoftheFireTeamsarequalifiedinfirefighting.3.2.3Foralistofthelocationsoffirefightingequipment,refertotheMechanicalMaintenancepreventivemaintenanceprogramasdelineatedinAdmin.ProcedureNo.,0010431"PreventiveMaintenanceProgram".3.2.4Theemergencyclassificationsystemincludescertainfirerelatedevents.Thus,firesmaybeclassifiedasUnusualEvents,Alerts,orSiteAreaEmergencies.3.3~AuttotltThisprocedureimplementstheSt.LuciePlantEmergencyPlanandFireProtectionPlan.4.0Precautions:4.1Class"C"fireextinguishers(C02orDryChemical)orfogtypefirehosenozzlesshallbeusedoncombustibleliquidfires,electricalfiresoronfireswhichmightinvolveenergizedconductorsand/orequipment.8l09020026810827,'DRADOCK05000335'P.DR, 110 tPage2of4E-PLANIMPLEMENTINGPROCEDURE3100025EFIREEMERGENCIESREVISION64.0Precautions(continued)4.2Foamtypefireextinguishingmaterialsshallnotbeusedonelectricalfires.4.3WhenfightingfiresintheRadiationControlledAreathatmayinvolveradioactivematerials,themembersoftheFireTeamshalluseadditionalprotectiveequipmentspecifiedbytheRadiationTeamLeaderandshallfollowanyinstructionsheissuesregardingprecautionstoobservewhilefightingthefire.5.0Responsibilities:5.1TheNuclearWatchEngineeristheFireTeamLeader.Ifheisnotavailable,theNuclearTurbineOperatoractsashisalternate..ItshallbetheresponsibilityoftheFireTeamLeaderto:5.1.1Directallphasesofthefirefightingactivities.5.1.2Coordinatetheactivitiesofanyoutsidefirefightingorganizationcalledintoassistwiththeemergency.5.2ItshallbetheresponsibilityofeachFireTeammembertobethoroughlyfamiliarwiththecontentsofthisprocedureandthelocationoffirefightingequipmentintheplant.5.3Allpersonnelshallbefamiliarwiththelocationof,andbefamiliarwithoperationoffireequipmentintheirdesignatedworkstations.5.4Onthebasisofobservations,theNuclear,PlantSupervisorisresponsibleforclassificationoftheemergency.Heisalsoresponsibleformakingnotificationsandtakingotheractionsappropriatetotheemergencyclass.6.0

References:

6.1St.LuciePlantEmergencyPlan.6.2E-PlanImplementingProcedureEP3100023E,On-SiteEmergencyOrganization/andRoster.6.3St.LuciePlantAdministrativeProcedureNo.1800022FireProtectionPlan".6.4St.LuciePlantAdministrativeProcedureNo.0010431"PreventiveMaintenanceProgram".7.0Records:AnyactionstakenshallberecordedintheNuclearPlantSupervisor'sLogBook.

l~

0E-PLANIMPLEMENTINGPROCEDURE3100025EFIREEMERGENCIESREVISION6Page3of48.0Instructions:8.1Whenanindividualdiscoversafirewhichcanbesafelyextinguishedusingfirefightingequipmentathand,heshalldosoandthenpromptlynotifytheNuclearPlantSupervisor.8.2Whenanindividualdiscoversafireor.explosionresultinginafirewhichcannotbeextinguishedusingfirefightingequipmentathand,heshallnotifytheNuclearPlantSupervisoroverthePAsystemorthecontrolroombydialing333onanyPAXtelephone.Thefollowinginformationshallbegiven:8.2.1Locationofthefire.8.2.2Typeoffire,ifknown.8.2.3Whetherornotthereareanyinjuredpersonnel.8.2.4Extentofdamagetoplantcomponents.NOTE:Speedinnotificationismuchmoreimportantthanthecompletenessoftheinitialreport.8.3TheNuclearPlantSupervisorshallinstructtheindividualtotakeanyimmediateactionheisqualifiedtoperformtoextinguishthefire.8.4TheNuclearPlantSupervisorshallcross-connectthePAsystem,declareaFireEmergency,announcethelocationofthefire,andsoundthefirealarm..Ifsufficientinformationisavailable,heshallclassifythe-emergencyandimplementtheEmergencyPlan.(1)TheNuclearWatchEngineerwilldirect,byuseofthepage.system,whichmemberswillmeethimatthefiresite,andwhichmemberswillgotothefirehouse.(2)IfthefireisfoundtobeintheRadiationControlledArea,theRadiationTeamshallbeactivatedbytheEmergencyCoordinator(NuclearPlantSupervisor).(3)IfthefireorexplosionisintheRadiationControlledArea,theyshallwearappropriateprotectiveclothingandrespiratoryequipmentandpersonnelmonitoringdevices,attempttostayupwindofthefire,andcoordinatetheiractionswiththeRadiationTeam.(4)Other'lantpersonnelexcepttheoperatorsonwatchshallreporttothemaintenanceshopandbereadytoassistinthe.fireorexplosionfightingoperationswhencalledupon.

0E-PLANIMPLEMENTINGPROCEDURE3100025EFIREEMERGENCIESREVISION6Page4of48.4(continued)(5)Duringnormalworkinghoursadditionalpersonnelareavailablefromthemaintenancedepartmenttosupportfirefightingeffortsuntiloutsideassistanceisobtained.(6)TheEmergencyCoordinator(NuclearPlantSupervisor)shalldesignateadditionalavailableon-sitepersonneltoassistinextinguishingthefire,asrequiredbythesituation.8.4.1RequestingOutsideFireAssistance:(1)Ifthefireistoolargetobecontrolledbyavailableplantforces,theSt.LucieCounty-Ft.PierceFireDistrictshallbecalledbytheEmergencyCoordinator.(2)Themainguardstationshallbenotifiedofthelocationof-thefireandtheexpectedarrivaloftheoff-sitefirefightingequipment.(3)WorkingcommuinicationsshallbeestablishedbetweentheEmergencyCoordinator,thepersoninchargeoftheoff-sitefirefightingorganization,theRadiationTeamLeader,ifthefireisintheRadiationControlledArea,andtheFireTeamLeader.St.LucieCounty-Ft.PierceORSt.LucieCountyEmergencyCenter461-1547464-1122911(4)Inthecaseofanuncontrolledfire,notinvolvingasafetysystem,butrequiringoff-sitesupport,theNuclearPlantSupervisorshalldeclareanUNUSUALEVENT.(5)Inthecaseofanuncontrolledfire,potentiallyaffectingsafetysystemsandrequiringoff-sitesupport,theNuclearPlant.SupervisorshalldeclareanALERT.(6)Inthecaseofafireresultingindegradationofsafetysystems,theNuclearPlantSupervisorshalldeclareaSITEAREAEMERGENCY.NOTE:SeeE-PlanImplementingProcedure3100023E,EmergencyRoster,forspecificinformationregardingmeansofcommunicationandtelephonenumbers.