ML20132E302

From kanterella
Revision as of 06:00, 10 August 2022 by StriderTol (talk | contribs) (StriderTol Bot change)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Proposed Tech Specs Re Waiver of 18-month Interval Surveillance Requirement for ECCS
ML20132E302
Person / Time
Site: LaSalle  Constellation icon.png
Issue date: 09/23/1985
From:
COMMONWEALTH EDISON CO.
To:
Shared Package
ML20132E291 List:
References
0672K, 672K, NUDOCS 8510010055
Download: ML20132E302 (4)


Text

.

ATTACHMENT 1 PRCPOSED CHANGE TO APPENDIX A TECHNICAL S)ECIFICATION TO OPERATING LICENSES tFF-ll and NPF-18 Revised Paces:

~

l FPF-ll NPF-18 3/4 5-4 3/4 8-4 l

l O

0672K

EMERGENCY CORE COOLING SYSTEMS SURVEILLANCE REQUIRCHENTS .

4.5.1 ECCS divisions 1, 2 and 3 shall be demonstrated OPERABLE by: .

a. At least once per 31 days for the LPCS, LPCI and HPCS systems:
1. Verifying by venting at the high point vents that the system piping from tre pump discharge valve to the system isolation valve is filled with water.
2. Performance of a CHANNEL FLNCTIONAL TEST of the:

a) Discharge line " keep filled" pressure alarm instrumentation, and b) Header delta P instrumentation.

3. Verifying t nt each valve, manual, power operated or automatic, in the flow path that is not locked, sealed, or otherwise secured in position, is in its correct position.
4. Verifying that each ECCS corner room watertight door is closed, except during normal entry and exit from the room.
b. Verifying that, when tested pursuant to Specification 4.0.5, each:
1. LPCS pump develops a flow of at least 6350 gpm against a
  • test line pressure greater than or equal to 290 psig.
2. LPCI pump develops a flow of at least 7200 gpm against a test line pressure greater than or equal to 130 psig.
3. HPCS pump develops a flow of at least 6250 gpm against a test line pressure greater than or equal to 370 psig.

a.

c. For the LPCS, LPCI and HPCS systems, at least once per 18 months:
1. Performing a system functional test which includes simulated automatic actuation of the system throughout its emergency operating sequence and verifying that each automatic valve in the flow path actuates to its correct position. Actual injection of coolant into the reactor vessel may be excluded from this test.
2. Performing a CHANNEL CALIBRATION of the:

a) Discharge line " keep filled" pressure alarm instrumentation and verifying the:

, 1) High pressure setpoint and the low pressure setpoint of the:

+ %a 4 ale- M ' N goc h p gle.I %A. ~ tao Aww* ' 0% l s. (2 Q3/4W5-4 (Laputt.l.

LA SALLE - UNIT 1 Amendment No.18

ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)

d. At least once per 18 months d ring shutdown by:
1. Subjecting the diesel to an inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for this class of standby service.
2. Verify'ing the diesel generator capability to reject a load of greater than or equal to 1190 kW for diesel generator 0, greater than or equal to 638 kW for diesel generators 1A and 2A, and greater than or equal to 2381 kW for diesel generator 2B while maintaining engine speed less than or equal to 75% of the difference between nominal speed and the overspeed trip setpoint or 15% above nominal, whichever is less.
3. Verifying the diesel generator capability to reject a load of 2600 kW without tripping. The generator voltage shall not exceed 5000 volts during and following the load rejection.

4 Simulating a loss-of-offsite power by itself, and:

a) For Divisions 1 and 2 and for Unit 1 Division 2:

1) Verifying deenergization of the emergency busses and load shedding from the emergency busses.
2) Verifying the diesel generator starts on the auto-start signal, energizes the emergency busses with permanently connected loads within 13 seconds, energizes the auto-connected loads and operates for greater than or equal to 5 minutes while its generator is so loaded. After '

energization, the steady-state voltage and frequency of the emergency busses shall be maintained at 4160 1 150 volts and 60 1 1.2 Hz during th6s test, b) For Division 3:

1) Verifying deenergization of the emergency bus.
2) Verifying the diesel generator starts on the auto-start signal, erergizes the emergency bus with its loads with-in 13 seconds and operates for greater than or equal to 5 minutes while its generator is so loaded. After energization, the steady-state voltage and frequency of the emergency bus shall be maintained at 4160 i 150 volts and 60 2 1.2 Hz during this test.
5. Verifying that on an ECCS actuation test signal, without loss-of-offsite pcwer, diesel generators 0, 2A, and 28 start on the auto-start signal and operate on standby for greater than or equal to 5 minutes. The generator voltage and frequency shall be 4160 + 416, -150 volts and 60 + 3.0, -1.2 Hz within 13 seconds after the auto-start signal; the steady-state generator voltage and frequency shall be maintained within these limits during this test.

I'

+4 -fk_ nu/% IF-M ldlw=JL & OA

% i l M M 'M N LA SALLE 3/4 8-4

= _ _ _ . _ - - -_. __ . -_ _ __ _ _ _--. _ _ _ _ .._. _ _ _ _ _ _ _

d l

j //

! ATTACHMENT 2 i

} SIGNIFICANT HAZARDS CONSIDERATION I

I Comonwealth Edison has evaluated the proposed Technical Specifica-

, tion Amendment and determined that it does not represent a significant hazards

! consideration. Based on the criteria for defining a significant hazards l

consideration established in 10 CFR 50.92, operation of LaSalle County Station 4 Units 1 and 2 in accordance with the proposed amendment will not:

!a 1) Involve a significe.nt increase in the probability or consequences of an j accident previously evaluated because the operability of the equipment is i still maintained and based on the type of surveillances extended, no i significant increase in the probability of equipment failure is

! postulated.

r

2) Create the possibility of a new or different kind of accident from any accident previously evaluated because this amendment does not remove or i

add any equipment.

3) Involve a significant reduction in the margin of safety because the
increased surveillance interval does not significantly increase in any
possibility that an undetected failure will occur in any of the related l equipment covered by these Technical Specifications.

a l The surveillance requirement of Technical Specification 4.5.1.c involves logic / functional testing and ensures that all portions of the system I work together. The portions of the LPCI System which are note likely to fail I (valves, instruments, etc) are verified operable by current surveillances j during the extension period.

The surveillance requirement of Technical Specification 4.8.1.1.2.d j for the Unit 1 Division 2 diesel generator (1A) includes logic testing and preventative maintenance, etc. The diesel generators are verified operable while in operation by performing several other surveillences required by specifications 4.8.1.1.2.a,b and c. This ensures the diesel will start, will i accept load and has available such auxiliaries as necessary.

) Based on the preceding discussion, it is concluded that the proposed l system change clearly falls within all acceptable criteria with respect to j the system or conponent, the consequences of previously evaluated accidents l will not be increased and the margin of safety will not be decreased.

Therefore, based on the guidance provided in the Federal Register and the l criteria established in 10CFR50.92(e), the proposed change does not constitute j a significant hazards consideration.

5 0672K 1

u.___.- _ . - ~ - - _ - _ _ _ _ , . _ _ _ _ _ _ _ _ - , . _ - - __ . . _ _ _ _ _ _ _ , _ - _ _ _ _ _ . _ _ _ _