Proposed Tech Specs Re Controlled Area,Effluent Release Boundary,Exclusion Area,Frequency Notation,Fuel Handling & Process Control Program
ML20247G000
Person / Time
Site: La Crosse File:Dairyland Power Cooperative icon.png
Issue date: 03/28/1989
From:
DAIRYLAND POWER COOPERATIVE
To:
Shared Package
ML20247F995 List:
References
NUDOCS 8904040092
Download: ML20247G000 (3)


Text

m . - .- - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

DEFINITIONS - (Cant'd)

===========._==============================================-2=================:.-

b. The freight door is closed,
c. Each air lock is OPERABLE, 1

1 d. The containment leakage rates are within the limit, and

e. The sealing mechanism associated with each penetration (e.g.,

welds, bellows, o-rings) is OPERABLE.

CONTROLLED AREA A Controlled Area is an area for which access shall be controlled because of actual presence of uncontained radioactive material. Controlled areas shall be designated by radiation control signs and markers in accordance with 10CFR20.203. These controlled areas shall include the Turbine Building i beyond the change room door, the containment Building, the Waste Treatment l Building, and any other areas so marked by radiation signs and markers.

1 EFFLUENT RELEASE BOUNDARY The Dairyland power Cooperative property line within the 1109 ft. (338m) radius EXCLUSION AREA is the EFFLUENT RELEASE BOUNDARY. See Figure 1, Section 4.

EXCLUSION AREA The EXCLUSION AREA is defined as the area within an 1109 ft. (338m) radius from the centerline of the Containmer t Building. This was the area established per 10 CFR 100 as the EXCLUSION AREA for plant siting and operation.

FREQUENCY NOTATION The FREQUENCY NOTATION specified for the performance of Surveillance Requirements shall correspond to the intervals defined in Table of Surveillance Frequency Notation.

FUEL HANDLING FUEL HANDLING shall be the movement of any irradiated fuel within the Containment Building. Suspension of FUEL HANDLING shall not preclude completion of movement of the fuel to a safe conservative position.

MEMBEi[(S_) 0F THE PUBLIC MEMBER (S) 0F THE PUBLIC shall include any person who is not occupationally associated with the utility. This category does not include employees of the utility, its contractors or vendors. Also excluded from this category are persons who enter the site to service equipment or make deliveries. This category does include persons who use portions of the site for recreational or other purposes not associated with the utility.

8904040092 890328 22 PDR ADOCK 05000409 ,

P PDC

u

( -

l-t DEFINITIONS -'(Cont'd)

===========,=======:e===============================================u

OFFSITE DOSE CALCULATION MANUAL- (ODCM) l An OFFSITE DOSE CALCULATION MANUAL (ODCM) shall be a manual containing the methodology and parameters to be used for the calcule. tion of offsite doses due to radioactive gaseous and . liquid effluents and for the calculation of l

geseous and liquid effluent monitoring instrumentation alarm / trip setpoints.

' It shall describe the radiological environmental monitoring program.

1 OPERABLE-OPERABILITY l

A system, subsystem, train, component or device shell be OPERABLE or have OPERABILITY when it is capable of. performing its specified function (s) and .

when all necessary attendant instrumentation, controls, a normal or an emergency electrical power so"rce, cooling-or seal water, lubrication or other auxiliary equipment that are required for the' system, subsysten, train, component or device to perf orm its function (s) are also capable of performing their related support function (s).

I PROCESS CONTROL PROGRAM (PCP) f The PROCESS CONTROL PROGRAM shall contain the current formula, sampling, analyses, tests, and determinations to be made to ensure that the processing and packaging of solid radioactive wastes based on demonstrated processing o#

actual or simulated solid wastes will be accomplished in such a way as to .

assure compliance with 10 CFR Part 20, 10 CFR Part 61 and Federal and State regulations and other requirements governing the transportation and disposal

.of the radioactive waste.

REPORTABLE EVENT l A REPORTABLE EVENT shall be any of those conditions specified in Section-6.8.3. A Licensee-Event Report shall be submitted for REPORTABLE b/ENTS..

RESTRICTED AREA A RESTRICTED AREA shall be any area within the EXCLUSION' AREA, access to which is controlled by the licensee for purposes of protection of individuals from exposure to ionizing radiation and radioactive materials.

l SOLIDIFICATION SOLIDIFICATION shall be the conversion'of wet wastes into a form that meets shipping and burial ground requirements.

SOURCE CRECK A SOURCE CHECK shall be the qualitative assessment of channel response when the channel sensor is exposed to a radioactive source.

1 2-3 i >

l w________________-__ _ __ _--__ _____ ___-________ _ ___ - _ ____ _ - - - -_-__- ___ -__ _- __ _ ___ _ - _ . _ _ _-_ -

t l

  • ^

c .. . .

l DEFINITIONS - (Cont'd)

=================================================================

STAGGERED TEST BASIS A STAGGERED TEST BASIS shall consist of:

1

n. A test schedule.for n systems, subsystems, trains or other designated components obtained by dividing the specified test interval into n equal subintervals. ]
b. The testing of one system, subsystem, train or other designated component at the beginning of each subinterval.

1 UNRESTRICTED AREA An UNRESTRICTED AREA shall be any area not controlled by'the licensee for purposes of protection of MEMBERS OF THE PUBLIC from exposure to ionizing radiation and radioactive materials.

l l

SURVEILLANCE FICQUENCY NOTATION NOTATION FREQUENCY S At least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

D At le'ast once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

W At least once per 7 days.

M At least once per 31 days.

Q At least once per 92 days.

SA At least once per 6 months.

A At least once per 12 months.

R At least once per 18 months.

P Completed prior to each use or release.

N.A. Not applicable.

l l

1 l

l 2-4 1 - _ _ _ .--__ _ _ _ _ - -