ML17108A476

From kanterella
Revision as of 15:22, 19 June 2019 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Jump to navigation Jump to search
Relief Request NDE-SIF-U2 - Questions from San Luis Obispo Mothers for Peace
ML17108A476
Person / Time
Site: Diablo Canyon  Pacific Gas & Electric icon.png
Issue date: 04/10/2017
From: Swanson L
Pacific Gas & Electric Co
To: Christopher Newport, John Reynoso, Balwant Singal
Division of Operating Reactor Licensing
Singal B, 301-415-3016
References
NDE-SIF-U2
Download: ML17108A476 (2)


Text

From: Lucy J Swanson To: Singal, Balwant

Newport, Christopher
Reynoso, John Cc
Swanson Jane

Subject:

[External_Sender] DIABLO CANYON POWER PLANT, UNIT 2 - RELIEF REQUEST NDE-SIF-U2, Date: Saturday, April 15, 2017 6:41:46 PM Attachments:

ML17086A013.pdf ATT00001.htm April 10, 2017

TO:

Balwant K. Singal, Senior Project Manager

Balwant.Singal@nrc.gov

Christopher Newport, Senior resident Inspector, Diablo

Christopher.Newport@nrc.gov

John P. Reynoso, Resident Inspector, Diablo

John.Reynoso@nrc.gov

FROM: Jane Swanson, Spokesperson

San Luis Obispo Mothers for Peace

janeslo@icloud.com Upon reading ML17086A013 (see attached) San Luis Obispo Mothers for Peace (MFP) has a number of questions. Given that Balwant Singal's name is given as the person to whom PG&E's Chief Nuclear Officer is invited to address questions, I also address MFP questions to him, as well as to the Resident Inspectors. I will appreciate responses from one or more of you in order to help MFP better understand the meaning of this document.

On page 2 of the attachment under 3.1 it is stated that both welds were examined in the 19th refueling outage.

That outage concluded in June of 2016. Do I understand correctly that the welds in question were thoroughly examined at that time?

In section 3.3 are statements about ultrasonic examinations covering 63% and 52% of welds.

Is the impracticality referred to in this document defined by the fact that, when in operating mode, it is impossible to access the welds in the way they can be accessed during an outage?

Will the welds be inspected during future outages? If so, during what month/s would such inspections take place?

Section 3.5 seems to be an admission that the design of the seal injection filter vessel is faulty.

The NRC staff concludes that therefore it is an unreasonable burden on the licensee to make them examine those welds.

Mothers for Peace suggests that rather than offering bad design as an excuse, the fundamental problem should be addressed.

Redesign and replace in the interest of public safety.

The risks to workers at Diablo and the general public must outweigh the "burden upon the licensee." I look forward to your responses.