Page 1 of 134 II CH-ODCM-0001 II Off-Site Dose Calculation Manual {ODCM) Revision 27 Safety Classification:

I Non-Safety Change No.: Reason for Change: Reauestor:

Preparer:

Issued: If sage Leve~eference EC 69113 Revised ODCM to remove reference to Technical Specification 5.18 and add additional special interest TLD locations.

NA Marcellus, M. 05-25-17 3:00 pm Fort Calhoun Station II CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Table of Contents PARTI Page 2 of 134 Revision 27 1.0 PUR-POSE AND SCOPE .....* _ ..... _ ................................. , .........

.-.... , .............

_ ........................

6 1.1 Purpose ......................................................................................................................

6 1.2 Scope ....... _ ................. , ................................................................................................

6 2.0 DEFINITIONS-

...................................................................................................................

6 3-.0 INSTRUMENTATION

....................................................................................................

10 3.1 Radioactive Liquid Effluent Instrumentation

.. , ..........................................................

10 3.2 Radioactive Gaseous Effk1ent Instrumentation

...............................

.; .....................

14 4.0 RADIOACTIVE EFFLUENTS

......................................

-._ ... _ ..................

-...........................

_. 20 4.1 Radioactive Liquid Effluents

..........

-........ , .................................................................

20 4.2 Radioactive Gaseous Effluents

...............................................................................

26 4.3 Uranium Fuel Cycle, ..........................................

_ ...... _ ............

-........ ; .. , .........................

3_5 5.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (REMP) ..................

36 5.1 Mo*nitoring Program ................................. , .................................................................

36 5.2 Land Use Survey ..........

-... -.................................. , .............

-............

....... , ............

-.. , .. _ .. .-51 5.3 lnterlaboratory Comparison Program ......................................................................

52

  • 6.0 ADMINISTRATIVE CONTROL$ ................... , .............. , ................. , ................................

53 6.1 Responsibilities

........................................................................................................

53 6.2 Radioactive Effluent Reporting Requirements

.........................................................

53 6.3 Change Mechanism

.....................

-..............

.-.................

., ..........................................

57 6.4 Meteorological Data ................................ " ........................

_ .......................................

58_ 6.5 References

..................

.............
............ , ...........

_ ........................

-...... * ..... _., ......... , ...... 58 7 .0 BASIS ............................................

_ ...............................................

_ ........ _ ....................

-.. ; .. 59 7.1 Instrumentation

....................... , ...............................

-..............................

_ ...................

59 7.2* Radioactive Effluents

.... _., ................................................. , ............ , .............

-...............

60 7.3 Radiological Environmental Monitoring

...................................................................

67 7.4 Abnormal Release or Atmormal Discharge Reporting

... , ......... .. , .......................... , ... 68 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) List of Tables PARTI Page 3 of 134 Revision 27 Table 1.2 -Frequency Notation ...............................................................................................

8 Table 1.3-Radiological Effluent Controls Program Technical Specification Implementation

.. 9 Table 3.1.1 -Radioactive Liquid Effluent Monitoring Instrumentation

....................................

11 Table 3.1.2 -Radioactive Liquid Effluent Monitoring Instrumentation Surveillance Requirements

.......................................................................................................

13 Table 3.2.1 -Radioactive Gaseous Effluent Monitoring Instrumentation

...............................

15 Table 3.2.2 -Radioactive Gaseous Effluent Monitoring Instrumentation Surveillance Requirements

...................................................................................

19 Table 4.1 -Radioactive Liquid Effluent Sampling and Analysis .............................................

22 Table 4.2 -Radioactive Airborne Effluent Sampling and Analysis .........................................

27 Table 4.3 -Sampler Depositionffransportation Correction Factors .......................................

29 Table 5.1 -Radiological Environmental Monitoring Program .................................................

38 Table 5.2 -Radiological Environmental Sampling Locations And Media ...............................

41 Table 5.3 -Detection Capabilities for Environmental Sample Analysis Lower Limit of Detection (LLD) ...................................................................................................

49 Table 5.4-Reporting Levels for Radioactivity Concentrations in Environmental Samples ......................................................................................

50 List of Figures PARTI Figure 1 -Environmental Radiological Sampling Points .......................................................

47 Figure 2-40CFR190 Sampling Points .................................................................................

48 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Table of Contents PART II Page 4 of 134 Revision 27 1.0 EFFLUENT MONITOR SETPOINTS

.............................................................................

71 1.1 Liq_uid Effluents

........................................... , .......................

,. ..............................

,. ....... 71 1.2 Airborne Effluents

............................... , ..........................................................

..........

76 2.0 EFFLUENT CONCENTRATIONS

.................................................................................

88 2.1 Liquid Effluent Concentrations

......*................... , .....................................................

89 2.2 Airborne Effluent Concentrations

............................................................................

89 3.0 RADIOACTIVE EFFLUENT DOSE CALCULATIONS

...................................................

90 3.1 Liquid Effluent Dose Calculations

........................................................................... , 90 3.2 Airborne Effluent Dose Calculations

........................................................................

95 4.0 LOWER LIMIT OF DETECTION (LLD) .......................... , ...........................................

,, 108 CH-ODCM-0001 Reference Use Off:-Site Dose Calculation Manual (ODCM) List of Tabh~s PART II Page 5 of 134 Revision 27 Table 1 -AIIQcation Factors for Simultaneous Releases ............

_.,, .. , .. ;.,; ... , ..... , ......................

83 Table 2 -Dose Factors for Exposure to a -Semi-Infinite Cloud of Noble Gases ...*..* , ..*. .-.*. -, .. 109 Table 3 -Bioaccumulatioil Factors ...............................................................................

.. , ..... 110 Table 4 -Highest Potential Exposure Pathways for Estimating Dose .......... , ......... , ......... , .. ; 111 Table 5-Stable Element Transfer Data .................................................................

-.............

112 Table 6 -Recommended Values for Uap to Be Used *for the Maximum Exposed Individual in Lieu of Site Specific Data ...............

,. ... , ... , .... , ....... , ....................

,, ...... ,.113 Table 7 ., Animal Consumption Rates ..... , .............................................. , ...............................

113 Table 8 -External Dose Factors forst~nding .on Contaminated Ground .............................

114 Table 9 -Inhalation Dose Factors for Adult .. -........ ,. , ...*.....

_ ........................ , ...........................

116 Table 10 -Inhalation Dose Factors for Teenager ................................ , ................................

118 Table 11 -Inhalation Dose Factors fot Child ....... , ...............................................................

120 Table t2 -Inhalation Dose Factors for Infant .....................................................................

122 Table 13 -Ingestion*

Dose Factors for Adult.. ........................................................................

124 Table 14 -Ingestion Dose Factors for Teenager'

................. , ................. , ....... , ..... ,., ......... , ... 126 Table 15 -Ingestion Dose Factors for .Child .................... , ............................... , ...................

128 Table 16 -Ingestion Dose Factors for Infant .......................................................................

130 Table 17 -Recommended Values for Other Patametets

......... , .... , ........ , .... , .... , ...................

1.32 Table. 18 -Estimated Doses Received by the General Public from On-Site Exposure ........ 134 List of Figures PART 11 Figure 1 -Exclusion and S.ite Boundary Map .................................... , .. , ............

-.......................

84 Figure 2 -Liquid Radioactive Discharge Pathways ...............................................................

85 Figure 3* -Liquid RadioijCtive Waste Disposal System ....................................................... , .. 86 Figure 4 -Airborne Effluent Discharge Pathways ............ , .....................................

-... -..............

86 Figure 5 -Airborne Radioactive Waste Disposal System ......................................................

88 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 1.0 PURPOSE AND SCOPE 1.1 Purpose Page 6 of 134 Revision 27 1.1.1 Contains methodologies for and parameters necessary for calculating offsite doses, determination of gaseous and liquid radiation monitor set points, and administrative controls for effluent instrumentation, Radiological Effluent Tech Specs (RETS), and the Radiological Environmental Monitoring Program (REMP}. 1.2 Scope 1.2.1 Radioactive effluents are generated from station operations.

These controls provide methodologies ensuring these effluents are properly monitored and quantified to promote accurate dose reporting.

Additional controls ensure station equipment and processes are used to minimize release to the environment.

The combination of minimizing release, accurately reporting dose, and monitoring the plant environs provides the basis for ensuring that station operation is not negatively impacting public health and the environment.

2.0 DEFINITIONS

2.1 Abnormal

Discharge

-The unplanned or uncontrolled emission of an effluent (i.e., containing plant-related, licensed radioactive material) into the unrestricted area. 2.2 Abnormal Release -The unplanned or uncontrolled emission of an effluent (i.e., containing plant-related, licensed radioactive material).

2.3 Channel

Check -A CHANNEL CHECK shall be the qualitative assessment of channel behavior during operation by observation.

This determination shall include, where possible, comparison of the channel indication and/or status with other indications and/or status derived from independent instrument channels measuring the same parameter.

2.4 Channel

Function Test -Injection of a simulated signal into the channel to verify that it is operable, including any alarm and/or trip initiating action. 2.5 Effluent Concentration Limit (ECL) -Radionuclide limits listed in 1 O CFR Part 20, Appendix B, Table 2, Column 1. 2.6 Member(s) of the Public -Member(s) of the Public means any individual except when that individual is receiving occupational dose.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 7 of 134 Revision 27 2.7 Operable-Operability-A system, subsystem, train, component or device shall be OPERABLE or have OPERABILITY when it is capable of performing its specified safety function(s) and when all necessary attendant instrumentation, controls, nonnal or emergency electrical power sources, cooling and seal water, lubrication, and other auxiliary equipment that are required for the system, subsystem, train, component, or device to perform its specified safety function(s) are also capable of perfonning their related support function(s).

2.8 Purge-Purging

-PURGE or PURGING shall be any controlled process of discharging air or gas from a confinement to maintain temperature, pressure, humidity, concentration or other operating condition, in such a manner that replacement air or gas is required to purify the confinement.

2.9 Residual

Radioactivity

-Residual radioactivity means radioactivity in structures, materials, soils, ground water, and other media at a site resulting from activities under the licensee's control. This includes radioactivity from all licensed and unlicensed sources used by the licensee, but it excludes background radiation.

It also includes radioactive materials remaining at the site as a result of routine or accidental releases of radioactive material at the site and previous burials at the site, even if those burials were made in accordance with the provisions of 10 CFR Part 20. 2.10 Site Boundary -The Site Boundary is the line beyond which the land is neither owned, or leased, nor controlled by the licensee.

2.11 Source Check -A SOURCE CHECK shall be the qualitative assessment of channel response when the channel sensor is exposed to a source of increased radioactivity.

2.12 Special Liquid -Non-routine release pathway in which normally non-radioactive liquid streams (such as Raw Water) found to contain radioactive material, are non-routine, and will be treated on a case specific basis if and when this occurs. 2.13 Unrestricted Area -An UNRESTRICTED AREA shall be any area at or beyond the SITE BOUNDARY access to which is not controlled by the licensee for purposes of protection of individuals from exposure to radiation and radioactive materials, or any area within the SITE BOUNDARY used for residential quarters or for industrial, commercial, institutional, and/or recreationa.1 purposes.

2.14 Venting -VENTING shall be the controlled process of discharging air or gas from a confinement to maintain temperature, pressure, humidity, concentration, or other operating condition, in such a manner that replacement air or gas is not provided or required during VENTING. Vent, used in system names, does not imply a VENTING process. 2.15 Water Effluent Concentration (WEC) -Radionuclide limits listed in 10 CFR Part 20, Appendix B, Table 2, Column 2.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 8 of 134 Revision 27 Table 1.2 -Frequency Notation The surveillance intervals are defined as follows: Notation Title FrequencyA s Shift At least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> D Daily At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> -W Weekly At least once per 7 days BW Biweekly At least once per 14 days M Monthly At least once per 31 days Q Quarterly At least once per 92 days SA Semiannual At least once per 184 days A Annually At least once per 366 days R Refueling At least once per 18 months p Prior to Prior to each release (Performance within 24 hrs.) A. Each surveillance requirement shall be perfonned within the specified surveillance interval with a maximum allowable extension not to exceed 25 percent of the specified surveillance interval.

y I CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 9 of 1.34 Revision 27 Table 1.3 -Radiological Effluent Control$ Program Techni~I Specification Implementation Technical Speciffoation ODCM Implementing

_Step 5.16.1.a 3.1.1, 3.2.1 5.16.1.b 4.1.1 5.16.1.c Table 4.1, Table 4.2 5.16.1.d 4.1.2 5.16.1.e 4.1.2B.1, 4.2.2B.1 .. 5.16.1.f 4.1 :3A, 4.2.4A 5.16 .. 1.g 4.2.1 5.16.1.h 4.2.2 5.16.1.i 4.2.3 5.16.1 ii 4.3.1 5.16.2.a 5.1.1 5.16.2.b 5.2 .. 1 5.16.2.c 5,.3.1 5.17 6.3, 6.2.1D -1

( CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 3.0 INSTRUMENTATION

3.1 Radioactive

Liquid Effluent Instrumentation

3.1.1 Limiting

Condition for Operation Page 10 of 134 Revision 27 A. The radioactive liquid effluent monitoring instrumentation channels shown in Table 3.1.1 shall be OPERABLE with their alarm/trip setpoints set to ensure that the limits of Specification 3.1.1 are not exceeded.

The alarm/trip setpoints of these channels shall be determined in accordance with Part II of the Off-Site Dose Calculation Manual. APPLICABILITY:

At all times ACTION: 1. With a iadioactive liquid effluent monitoiing instr..imentation channel alarm/trip setpoint less conservative than required by the above specification, immediately suspend the releases of radioactive liquid effluents monitored by the affected channel or declare the channel inoperable.

2. With less than the minimum number of radioactive liquid effluent monitoring instrumentation channels operable, take the action shown in Table 3.1.1. Restore inoperable effluent monitoring instrumentation to OPERABLE status within 30 days and, if unsuccessful, explain in the next Annual Radiological Effluent Release Report why this inoperabllity was not corrected in a timely manner. The reporting requirement is limited to the following instrumentation that monitors effluent streams: RM-055, RM-054A, and RM-054B. 3.1.2 Surveillance Requirements A. Each radioactive liquid effluent monitoring instrumentation channel shall be demonstrated OPERABLE by performance of the CHANNEL CHECK, SOURCE CHECK, CALIBRATION, and CHANNEL FUNCTIONAL TEST at the frequencies shown in Table 3.1.2.

CH-ODCM-0001 Reference Use Page 11 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) Table 3.1.1 -Radioactive Liquid Effluent Monitoring Instrumentation Minimum Channels Instrument Operable Action 1. Radioactivity Monitors Providing Alarm and Automatic Termination of Release. 1.1 Liquid Radwaste Effluent Line (RM-055) 1 1, 5 1.2 Steam Generator Slowdown Effluent Line (RM-054A and S) 1 A 2, 5 2. Flow Rate Measurement Devices 2.1 Liquid Radwaste Effluent Line 1 3 2.2 Steam Generator Slowdown Effluent Line 1 3 3. Radioactivity Recorders

3.1 Liquid

Radwaste Effluent Line 1 4 3.2 Steam Generator Slowdown Effluent Line 1 4 A. If one of the two radiation monitors is inoperable, the activity of both blowdown lines shall be monitored by the operable monitor within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of the declaration of inoperability by the Shift Manager, or the action steps of ACTION 2, Table 3.1.1 should be performed on the Steam Generator that is not being monitored.

CH-ODCM-0001 Referenc.e Use Off-Site Dose Calculation Manual (ODCM) Table 3.1.1 (continued)

Table Notation Page 12 of 134 Revision 27 ACTION 1 With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may cor:itinue provided that prior to initiating a release: 1. At least two independent samples are analyzed in accorc;tance with applicable chemistry procedures.

2. At least two qualified individuals independently verify the release rate calculations.

ACTION 2 With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided that grab samples are analyzed for principal gamma emitters at a sensitivity of 5.0E-07 µCi/gram:

  • 1. At least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> when the specific activity of the secondary coolant is greater than 0.01 µCi/gram do.se equivalent 1-131. 2. At least daily when the specific activity of the secondary coolant is less than or eqt1al to 0.01 µCi/gram equivalent 1-131. Otherwise, suspend release of radioactive effluents via this* pathway. ACTION 3 With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided the flow rate is determined at least once per four hours during the actual release. ACTION 4 With the number of .channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided the radioactivity is recorded.

manually at least once per four hours during the actual release. ACTION 5 During the performance of source checks the effluent radiation monitor is unable to respond, hence is considered inoperable.

Effluent releases may continue uninterrupted during the performance of source checks provided the operator is stationed at the monitor during the check. If the effluent radiation monitor fails the source check; carryout the action(s) of the Off.,Site Dose Calculation Manual for the inoperable monitor or terminate the effluent re.lease.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM); Page 13 of 134 Revision 27 Table 3.1.2 -Radioactive Liquid Effluent Monitoring Instrumentation Surveillance Requirements Channel Channel Source Instrument Check Calibration Function Check Test 1. Radioactivity Monitors Providing Alarm and Automatic Isolation 1.1 RM-054A/0548 QA R Q M 1.2 RM-055 --R Q p 2. Flowrate Monitors 2.1 Steam Generator Slowdown D R Q --A. Visual Flowcheck Daily CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 3.2 Radioactive Gaseous Effluent Instrumentation

3.2.1 Limiting

Condition for Operation Page 14 of 134 Revision 27 A. The radioactive gaseous effluent monitoring instrumentation channels shown in Table 3.2.1 shall be OPERABLE with their alarm/trip setpoints set to ensure that the limits of Specification 3.2.1 are not exceeded.

The alarm/trip setpoints of these channels shall be determined in accordance with Part II of the Off-Site Dose Calculation Manual. -APPLICABILITY:

At all times ACTION: 1. With a radioactive gaseous effluent monitoring instrumentation channel alarm/trip setpoint less conservative than required by the above specification, immediately suspend the releases of radioactive gaseous effluents monitored by the affected channel or declare the channel inoperable.

2. With less than the minimum number of radioactive gaseous effluent monitoring instrumentation channels operable, take the action shown in Table 3.2.1. Restore inoperable effluent monitoring instrumentation to OPERABLE status within 30 days and, if unsuccessful, explain in the next Annual Radiological Effluent Release Report why this inoperability was not corrected in a timely manner. The reporting requirement is limited to the following instrumentation that monitors effluent streams: RM-057, RM-043, RM-062, RM-063, and RM-052. 3.2.2 Surveillance Requirements A. Each radioactive gaseous effluent monitoring instrumentation channel shall be demonstrated OPERABLE by performance of the CHANNEL CHECK, SOURCE CHECK, CALIBRATION, and CHANNEL FUNCTIONAL TEST at the frequencies shown in Table 3.2.2.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 15 of 134 Revision 27 Table 3.2.1 -Radioactive Gaseous Effluent Monitoring Instrumentation Minimum Instrument Channels Action Operable 1. Auxiliary Bldg. Exhaust Stack (RM-052, RM-062) 1.1 Noble Gas 1 1, 9, 11 1.2 Iodine and Particulate 1 2, 9, 11 2. Laboratory and Radwaste Processing Building Stack (RM-043) 2.1 Noble Gas 1 3, 9 2.2 Iodine and Particulate 1 4,9 3. Condenser Off Gas (RM-057) 3.1 Noble Gas 1 5,9 4. Containment Purge Line (RM-051, RM-052) 4.1 Noble Gas 1 1, 6, 9, 11, 12 4.2 Iodine and Particulate 1 2, 9, 11, 12 5. Containment Pressure Relief Line (RM-051, RM-052) 5.1 Noble Gas 1 1, 9, 11 5.2 Iodine and Particulate 1 2,9, 11 6. Containment Penetrations M72 and M74 (Integrated Leak Rate Test Depressurization Vent Path) N/A 10 7. Flow Rate Measurement Devices 7.1 Waste Gas Discharge Header 1 7 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 16 of 134 Revision 27 Table 3.2.1 -Radioactive Gase.ous Effluent Monitoring Instrumentation Minimum Instrument Channels Action Operable 7.2 Auxiliary Building Stack 1 7 7.3 Laboratory and Radwaste Processing Building Stack t 7 7.4 Containment Purge Line 1 7 7.5 Containment Pressure Relief Line Annubar D/P 1 7 I 8. Radioactivity Chart Recorders

8.1 Auxiliary

Building Exhaust Stack 1. 8 ---1 CH-ODCM-0001 Reference Use Page 17 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) Table 3.2.1 Radioactive Gaseous Effluent Monitoring Instrumentation TABLE NOTATION ACTION 1 If the Auxiliary Building Exhaust Stack Noble Gas Monitor is inoperable, releases from the containment pressure relief line and the containment purge line are to be secured in the most expeditious manner. Ventilation of the auxiliary building via the Auxiliary Building Exhaust Stack may continue provided grab samples are taken once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. (See Table 4.2) ACTION2 If the Auxiliary Building Exhaust Stack Iodine and Particulate Sampler is inoperable, ventilation of the Auxiliary Building and releases from the gaseous waste discharge header, containment pressure relief line or the containment purge line may continue through the Auxiliary Building Exhaust Stack provided sample collection in accordance with Table 4.2 using auxiliary sample collection equipment is initiated within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of the declaration of inoperability by the Shift Manager. ACTION 3 If the Noble Gas Monitor is inoperable, ventilation of the LRWPB may continue via the LRWPB stack provided grab samples are taken at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. (See Table 4.2) ACTION4 If the Iodine and Particulate Sampler is inoperable, ventilation of the LRWPB may continue via the LRWPB Stack provided sample collection using auxiliary sample collection equipment is initiated within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of the declaration of inoperability, by the Shift Manager, in accordance with Table 4.2. ACTIONS During power operation, when the condenser air ejector is in service, the condenser off gas discharge shall be monitored for gross radioactivity.

If this monitor is inoperable, grab samples are taken at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. (See Table4.2)

ACTIONS The release of airborne effluents from the Containment purge line will be secured if a noble gas monitor is unavailable to monitor the containment building atmosphere.

ACTION 7 With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided the flowrate is estimated or recorded manually at least once per four hours during the actual release. ACTIONS With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided the radioactivity level is recorded manually at least once per four hours during the actual release. ACTION 9 During the performance of source checks the effluent radiation monitor is unable to respond, hence is considered inoperable.

Effluent releases may continue uninterrupted during the performance of source checks provided the operator is stationed at the monitor during the check. If the effluent radiation monitor fails the source check, carryout the Action(s) of the Off-Site Dose Calculation Manual for the inoperable monitor or terminate the effluent release.

CH-ODCM-0001 Reference Use Page 18 of 134 Revision 27 Off-Site Dose. Calculation Manual (ODCM) Table 3.2.1 Radioactive Gc1seous Effluent Monitoring Instrumentation TABLE NOTATION ACTION 10 Automatic release termination capability is not required provided manual isolation can be accomplished in accordance with the requirements of SE-ST-ILRT-0001, Containment-Integrated Leakage Rate Test (CILRT). ACTION 11 During the ventilation of airborne effluents from the Auxiliary Building Stac.k at least one Auxiliary Building Exhaust fan shall be in operation.

ACTION 12 IF containment purges are made without processing through at least one of the Containment Air Cooling and Filtering Units, and it is confirmed that one half of the annual dose objective listed in Section 4.2.2 will be exceeded during the calendar quarter, a special report shall be submitted to the NRC as defined in Section 4.2.4.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 19 of 134 Revision 27 Table 3.2.2 -Radioactive Gaseous Effluent Monitoring Instrumentation Surveillance Requirements Channel Channel Source Instrument Check Calibration Function Check Test 1. Radioactivity Monitors Providing Alarm and Automatic Isolation 1.1 RM-043 D R Q M 1.2 RM-057 D R Q M 1.3 RM-062 D R Q M,P 1.4 RM-052 A D R Q M, pA 2. Flowrate Monitors 2.1 RM-043 Sampler D R Q ----2.2 RM-062 Sampler D R Q ---2.3 RM-052 Sampler D R Q ----2.4 Auxiliary Bldg Exhaust Stack D R Q --2.5 Laboratory and Radwaste Process Bldg Exhaust Stack D R Q ----Operations Check Air Flow Calibration

3. Environmental Monitors 3.1 RM-023 -Sample Station #40 M A 3.2 RM-024 -Sample Station #41 M A 3.3 RM-025 -Sample Station #28 ------3.4 RM-026 -Sample Station #36 ------3.5 RM-027 -Sample Station #37 M A 3.6 RM-028 -Sample Station #38 -----3.7 RM-029 -Sample Station #39 ---/ --3.8 RM-035 -Sample Station #1 -----3.9 RM-036 -Sample Station #2 M A 3.10 RM-037 -Sample Station #3 -----3.11 RM-038 -Sample Station #4 M A 3.12 RM-039 -Sample Station #5 ----3.13 RM-040 -Sample Station #32 M A A. Required when RM-052 is sampling the Auxiliary Building Exhaust Stack.

CH-ODCM-0001 Reference Use Page 20 of 134 Revision 27 Off-Site' Dose Calculation Manual (ODCM) 4.0 RADIOACTIVE EFFLUENTS 4.1 Ri:ic;lioactive Liquid Effluents

  • I 4.1.1 Concentration A. Limiting Condition for Operation
1. The release rate of radioactive material in liquid effluents shall be controlled such that the instantaneous concentrations for radionuclides, other than dissolved or entrained noble gases, do not exceed the values specified in 10 CFR Part 20 for liquid effluents, at site discharge.

To support plant operations; Supervisor-System Chemistry may increase this limit up to the limit spe~ified in Technical Specifications 5.16.1.b.

For dissolved or entrained noble gases, the concentration shall be limited to 2.0E-04 µCi/ml, total activity.

2. Technical Specification 5.16.1.b establishes the administrative controi limit on concentration of radioactive material,, other than dh;solved or entrained noble gases, releas_ed in liquid effluents to unrestricted areas conforming to ten times 10 CFR Part 20.1001-20.2401, Appendix B, Table 2, Column 2, For dissolved or entrained noble gases, the concentration shall be limited to 2.0E-04 µCi/ml total activity.

APPLICABILITY:

At all times ACTION: a. When the concentration of radioactive materia_l released ,at site discharge exceeds the above Omits, appropriate corrective actions shall be taken immediately to restore concentrations within the above limits, B. Surveillance Requirements NOTE

  • Radioactive liquid waste include~ water used for fire suppression in areas of I the plantthat may contain radioactivity.

These liquids are required to be , monitored prior to release in accordance with S'O-G-28.

1. Radioactive liquid waste shall be sampled and analyzed according to the sampling and analysis program in Table 4.1.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page.21 of 134 Revision 27 2. The results of the radioactivity analysis shall be used with the calculational methods in Part II of the Off-Site Dose Calculation ManuaL 3. To assure th~t the eoncentration at the point of release is maintained within the limits. of Technical

~pacification 5.16.1.b.

4.1.1 B ( continued)

4. Records shall be maintained of the radioactive concentrations and volume before dilution of each batch of liquid effluent released and of the average dilution flow and length of time over which each disch~rge occurred.

Ana_lytical results shall be submitted to the Commission in accordance with Part I, Section 6.0 of th~ Off-Site pose Calculation Manual.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 22 of 134 Revision 27 Table 4.1 -Radioactive Liquid Effluent Sampling and Analysis A. M *t H t I W t T k & S . I L" "d R I om or, oe as e ans iP8Cl8 1au1 , e eases Sampling Frequency Type of Activity Analysis Lower Limit of Detection (LLD) (µCi/ml) A Each Batch Principal Gamma Emitters 8 5.0E-07 Each Batch 1-131 1.0E-06 Dissolved Noble Gases Each Batch {Gamma Emitters) 8 1.0E-05 Monthly Composite 0 H-3 1.0E-05 Monthly Composite 0 Gross Alpha 1.0E-07 Quarterly Composite o Sr-89, Sr-90 5.0E-08 Quarterly Composite 0 Fe-55 1.0E-06 B. Steam Generator Blowdown Sampling Frequency Type of Activity Analysis Lower Limit of Detection (LLD) (pCi/ml) A Weekly Composite o Principal Gamma Emitters 8 5.0E-07 Weekly Composite o 1-131 C 1.0E-06 Dissolved Noble Gases (Gamma Weekly Composite 0 Emitters) 8 1.0E-05 Monthly Composite 0 H-3 1.0E-05 Monthly Composite 0 Gross Alpha 1.0E-07 Quarterly Composite 0 Sr-89, Sr-90 5.0E-08 Quarterly Composite 0 Fe-55 1.0E-06 NOTES: A. LLD is defined in Part II of the Off-Site Dose Calculation Manual. B. The principal gamma emitters for which the LLD specification applies exclusively are the following radionuclides:

Kr-87, Kr-88, Xe-133, Xe-133m, Xe-135, and Xe-138 for dissolved or entrained gases and Mn-54, Fe-59, Co-58, Co-60, Zn-65, Mo-99, Cs-134, Cs-137, and Ce-141 for fission and corrosion products.

Ce-144 shall also be measured, but with a LLD of 5.0E-06. C. A weekly grab sample and analyses program including gamma isotopic identification will be initiated for the turbine building sump effluent when the steam generator blowdown water composite analysis indicates the 1-131 concentration is greater than 1.0E-06 µCi/ml. D. To be representative of the average quantities and concentrations of radioactive materials in liquid effluents, samples should be collected in proportion to the rate of flow of the effluent stream. Prior to analyses, all samples taken for the composite should be mixed in order for the composite sample to be representative of the average effluent release.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 4.1.2 Dose from Radioactive Liquid Effluents A. Limiting Condition for Operation Page 23 of 134 Revision 27 1. The dose or dose commitment to an individual in unrestricted areas from radioactive materials in liquid ,affluents shall be limited to the following:

a. During any calendar quarter: Less than or equal to 1.5 mrem to the total body and 5 mrem to any organ; and. b. During any calendar year: Less than or equal to 3 mrem to the total body and 10 mrem to any organ. APPLICABILITY:

At all times ACTION: a. If the dose contribution, due to the cumulative release of radioactive materials in liquid effluents, exceeds the annual or quarterly dose objectives, submit a Special Report to the NRC, per Section 6.2.3, within 30 days. B. Surveillance Requirements

1. Cumulative dose contributions from liquid effluents for the cµrrent calendar quartet and the current calendar year shall be determined iii accordance with the methodology and parameters in Part II of the Off-Site Dose Calculation Manual at least once per quarter.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 4.1.3 Liquid Radwaste Treatment A. Limiti~g Condition for Operation Page 24 of 134 Revision 27 1. The Liquid Radwaste Treatment System shall be OPERABLE, and appropriate portions of these systems shall be used to reduce releases of radioactivity when the projected doses due to the liquid effluent, from each unit, to UNRESTRICTED AREAS would exceed 0.06 mrem to the whole body or 0.2 mrem to any organ in a 31-day period. APPLICABILITY:

At all times ACTION: a. With radioactive liquid waste being discharged without treatment and in excess of the above limits and any portion of the Liquid Radwaste Treatment System not in operation, prepare and submit to the Nuclear Regulatory Commission within 30 days, pursuant to 10 CFR 50, Appendix I, a Special Report that includes the following information:

1) Explanation of why liquid radwaste was being discharged without treatment, identification of equipment or subsystem(s) not operable and reasons for inoperability.
2) Action(s) taken to restore the inoperable equipment to operable status. 3) Summary description of action(s) taken to prevent a recurrence.

B. Surveillance Requirements 1 . Dose due to liquid releases shall be projected frequently and at least once per quarter, in accordance with the methodology and parameters in Part II of the Off-Site Dose Calculation Manual, when Liquid Radwaste Treatment Systems are not fully OPERABLE.

2. OPERABLE is defined as follows: a. A filtration/ion exchange (FIX) system will be utilized for processing liquid radwaste.

The system consists of a booster pump, charcoal pretreatment filter, and pressure vessels containing organic/inorganic resins, which can be configured for optimum performance.

The effluent from the FIX system is directed to the monitor tanks for release.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 4.1.3B.2 (continued)

Page 25 of 134 Revision 27 b. Waste filters (WD-17A and WD-17B) are used only on those occasions when considered necessary, otherwise the flows from the low activity fluids may bypass the filters. No credit for decontamination factors (iodines, Cs, Rb, others) was taken for these filters during the 10 CFR Part 50 Appendix I dose design objective evaluation; therefore, the inoperability of these filters does not affect the dose contributions to any individual in the unrestricted areas via liquid pathways.

The inoperability of waste filters will not be considered a reportable event in accordance with the Action listed above. 4.1.4 Liquid Holdup Tanks Tanks included in this Specification are those outdoor tanks that are not surrounded by liners, dikes, or walls capable of holding the tanks contents and that do not have tank overflows and surrounding area drains connected to the liquid radwaste treatment system. A. Limiting Condition for Operation

1. The quantity of radioactive material contained in each unprotected outdoor liquid holdup tank shall not exceed 1 O curies, excluding tritium and dissolved or entrained noble gases. APPLICABILITY:

At all times ACTION: a. When the quantity of radioactive material in any unprotected outdoor liquid holdup tank exceeds 10 curies, excluding tritium and dissolved or entrained noble gasses, immediately suspend all additions of radioactive material to the tank and within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> reduce the tank contents to within the limit. B. Surveillance Requirements

1. The quantity of radioactive material contained in each outdoor liquid holdup tank shall be determined to be within the above limit by analyzing a representative sample of the tank's contents at least once per 7 days when radioactive material is being added to the tank.

CH-ODCM-0001 Reference Use Page 26 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 4.2 Radioactive Gaseous Effluents

  • I 4.2.1 Concentration A. Limiting Condition for Operation

-1. The release rate of radioactive material in airborne effluents shall be controlled such that the instantaneous concentrations of radionuclides does not exceed the values specified in 10 CFR Part 20 for airborne effluents at the unrestricted area boundary.

To support plant operations, Supervisor-System Chemistry may increase this limit up to the limits specified in Technical Specification 5.16.1.g.

2. Technical Specification 5.16.1.g establishes the administrative control limit on the concentration resulting from radioactive material, other than noble gases, released in gaseous effluents to unrestricted areas conforming to ten times 10 CFR Part 20.1001-20.2401, Appendix 8, Table 2, Column 1. For noble gases, the concentration shall be limited to five times 10 CFR Part 20.1001-20.2401, Appendix B, Table 2, Column 1. APPLICABILITY:

At all times ACTION: a. When the concentration of radioactive material released to unrestricted areas exceeds the above limits, appropriate corrective actions shall be taken immediately to restore concentrations within the above limits. 8. Surveillance Requirements NOTE Radioactive gaseous wastes include atmospheres in areas where gaseous

  • fire suppression systems are utilized or where smoke is produced as a result I of fire in areas of the plant that may contain radioactivity.

These atmospheres are required to be monitored prior to gaseous release to unrestricted areas in accordance with SO-G-28. 1. Radioactive gaseous wastes shall be sampled and analyzed according to the sampling and analysis program of Table 4.2. The results of the radioactivity analysis shall be used to assure the limits in Step 4.2.1A are not exceeded.

' CH-ODCM-0001 Referen Off'-Site Dose Calculation Manual (ODCM) ce Use Page 27 of 134 Revision 27 Table 4.2 -Radioactive Airborne Effluent Sampling and Analysis A. Gas Decay Tank Releases Sampling Frequency ctivity Analysis Type of A Prior to each release Principal Ga mma .Emitters B Lower Lim it of Detection (LLD) (JJCi/1111)

A 1,0.E-04 B. Containment Purge Releases or Con tainment Pressure Relief Line Releases E Sampling Frequency Type of Act ivity Analysis Prior to eact, rElleEJs~

Priopipal Garn ma Emiti~rs 8 Prior to each release H-3 C. Condenser Off Gas Releases E Sampling Frequency Type of Act ivity Analysis Monthly c *rritium.(H;,3)

Monthly

  • Principal Gc:1m ma Emitters 8 D. Auxili~ry Buil~ing Exhaust $ta~k E Sampling Frequency Type of Aet ivity Analysis Weekly (Charcoal Sample) 1-131 Weekly (Particulate Sample) Principal Garn ma Emitters 8 Weekly (Noble Gases) ma Emitter~ 8 Principal Gc:1.m . Weekly Tritium (H-;3} Monthly Composite 0 Gross Alpha Quarterly Composite (Particulate Samples) Sr-89, Sr.;9Q Lower .Limit of Detection (LLD) (pCi/ml) A 1.0E-04 1:0E-06 Lower Limit of Detection (LLO) (µCi/ml) A 1.0E-06. 1 .. oE.:04 Lower* Limit of Detectfon (LLO) (pCi/1111)

A 1.0E-11 1.0E-4 1..0E-06 1.0E-11 1.0E-11 L_ ----------------------------------------, CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 28 of 134 Revision 27 Table 4.2 -Radioactive Airborne Effluent Sampling and Analysis E. Laboratory and Radwaste Building Exhaust Stack E Sampling Frequency Type of Activity Analysis Lower l-imit of Detection (LLD) (1,1Ci/ml)

A Weekly (Charcoal Sijmple) 1-131 1.0E-12 Weekly (Particulate Sample) Principal Gamma Emitters 8 1.0E-11 Weekly (Noble Gases) Principal Gamma Emitters 8 1.0E-4 Monthly Composite 0 Gross Alpha 1.0E-11 Quarterly Composite (Particulate Sample) Sr-89, Sr-90 1.0E-11 NOTES: A. LLD is defined in Part II of the Off-Site O_ose Calculati.on Manual. B. The principal gamma emitters for which the LLD specification applies exclusively are the following radionuclides:

Kr-87, Kr-8l3, Xe-133, Xe-1~3m, Xe-135, and Xe-138 for noble gas releases and Mn-54, fe,..59, Co-58, Co-60, Zn-65, Mo-99, Cs-134, Cs-137, Ce-141, and Ce-"144 for Iodine arid particulate releases.

C. Required only when steam generator blowdown radioactivity for tritium .(Table 4.1, Item B) exceeds 3.0E-03 µCi/milliliter.

D. Frequency requirement may be satisfied using weekly gross alpha results from particulate sampling media. E. Particulate and Iodine samples shall be corrected for sampler deposition/transportation efficiency by using the approved software programs or by multiplying the activity obtained by the associated sampler multiplication factor (See Table 4.3).

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 29 of 134 Revision 27 Table 4.3 -Sampler Deposition/Transportation Correction Factors \ Sampler Sample RM-062 AB RM-052 AB RM-052 CONT RM-051 CONT RM-043 LRWPB PORTABLE CONT ACRONYM DEFINITIONS:

AB -Auxiliary Building Exhaust Stack. CONT -Containment Building Particulate DF ACTMULT 0.411 2:433 0.638 1.567 0.525 1;905 0.624 1.603 0.809 1.236 1.000 1.000 LRWPB -Laboratory and Rad Waste Processing Building DF -Deposition Factor ACTMUL T -Activity multiplication factor to correct for sample loss. Iodine DF ACTMULT 0.669 1.495 0.653 1.531 0.688 1.453 0.714 1.401 0.873 1.236 0.950 t.053 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM} 4.2.2 Dose -Noble Gases A. Limiting Condition for Operation Page 30 of 134 Revision 27 1. The dose or dose commitment to an individual at the site boundary from release of noble gases in airborne effluents shall be limited to the following:

a. During any calendar quarter: Less than or equal to 5 mrads for gamma radiation and less than or equal to 10 mrads for beta radiation; and b. During any calendar year: Less than or eq1,Jal to 1 O mrads for gamma radiation and less than or equal to 20 mrads for beta radiation.

APPLICABILITY:

At all times ACTION: a. If the dose contribution, due to the cumulative release of noble gases in airborne effluents, exceeds the annual or quarterly dose objectives, submit a Special Report to the NRC, per Section 6.2.3, within 30 days. B. Surveillance Requirements

1. The radiation dose contributions from radioactive noble gases In airborne effluents shall be determined, in accordance with the methodologies and parameters of Part II of the Off-Site Dose Calculation Manual, on a quarterly basis. 4.2.3 Dose 131, 1-133, H-3, C-14, and Radioactive Material in Particulate Form with Half-Lives Greater than 8 Days (Other than Noble Gases} A. Limiting Condition for Operation
1. The dose to an individual or dose commitment to any organ of an individual in unrestricted areas due to the release of 1-131, 1-133, H-3, C-14, and radioactive materials in particulate form with half-lives greater than eight days (excluding noble gases) in airborne effluents shall be limited to the following:
a. During any calendar quarter: Less than or equal to 7.5 mrem to any organ; and CH-ODCM-0001 Reference Use Off-Site oo-se Calculation Manual (ODCM) 4.2.3A.1 (continued)

Page 31 of 134 Revision 27 b. During any calendar year: Leiss than or equal to 15 mrem to any organ. APPLICABILITY:

At all times ACTION: a. If the dose contribution, due to the cumulative release of 1-131, 1-133, H-3, C-14, and radioactive materials in particulate form with half-lives greater than eight days, exceeds the annual or quarterly dose objectives, submit a Special Report to the NRC per Section 6,2,3., within 30 days; B. Surveillance Requirements, 1. The radiation dose contributions from 1-131, 1-133, H-3, C-14 and radioactive materials in particulate form with half-live_s greater than eight days (excluding noble gases) in airborne effluents shall be determined, in accordance with the methodologies and parameters of Part II of the Off..,Site Dose Calculation Manual, on a quarterly basis. 4.2.4 Gaseous Radwaste Treatment A. Limiting Condition for Operation

1. In accordance with Technical Specification 5.1'6.1.f, the Waste Gas System and the Ventilation Exhaust Systems shall be OPERABLE, and appropriate portions of these systems shall be used to reduce the releases of radioactivity when the projected doses in 31 days due to gaseous effluent releases to areas at and beyond the SIT.E BOUNDARY would exceed: a. 0.2 nirad to air from gamma radiation, or b. 0.4 mrad to air from beta radiation; or c. 0.3 mrem to any organ of a MEMBER OF THE PUB_LIC CH-ODCM-0001 Reference Use Page 32 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 4.2.4A.1 (continued)

APPLICABILITY:

At all times ACTION: a. With radioactive gaseous waste being discharged without treatment and in excess of the above limits, prepare and submit a report 'to the Nuclear Regulatory Commission within 30 days, pursuant to 10 CFR 50, Appendix I, a special report that includes the following information:

  • 1) Identification Qf equipment or subsystern(s) not operable and reasons for inoperability.
2) Action(s) taken to restore the inoperable equipment to operable status. 3) Summary description of action(s) taken to prevent a recurrence.

B. Surveillance Requirements

1. Dose due to gaseous releases shall be projected frequently and at least once per quarter, in accord~nce with the methodology and parameters in Part II of the Off-Site Dose Calculation Manual, whem Waste Gas Systems and Ventilation Exhaust Systems are not fully OPERABLE. .

CH-ODCM-0001 Reference Use Page 33 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 4.2.48 (ponJinued)

2. OPERABLE is defined as follows: a. Waste *Gas System 1) The waste airborne radioactive material at Fort Calhoun Station is collected ir:i. the vent header where the gas compressors take suction, compress the gas a.nd deliver it to one of the four gas deef;ly tanks. The waste airborne radioactive material is treated in these gas decay tanks by holding for radioactive decay prior to final controlled release to the environs.

In order to provide conformance with the dose design objectives, gas decay tanks are normally stored for approximately 30 days and thus achieve decay of short half-life radioactive materials, e.g.; 1-.131, Xe-133. Earlienelease i$ allowen:j when a plant need exists and analytical results are .in accordance with AL.,ARA re.lease objectives.

If the radioactive air,borne wastes from the gas decay tanks are discharged without processing in accordance With the above conditions, and it is confirmed that one half of the annual dose objective will be exceeded during the calendar quarter, a special report shall be .submitted to the Commission pursuant to Section 4;2AA. .b. Ventilation Exhaust Systems 1) The radioactjve effluents from the c;:qntrolled access area of th~ aµxiliary building are filtered by the HEPA filters in the auxiliary building ventilation system. If the radioactive effluents are discharged without the HEPA filters, a special report shall be submitted to the NRC as defined in Action 4.2.48.2.a above. 2) The discharge from the gas decay tanks is routed through charcoal and HEPA filter unit VA-82. No credit was taken for the operation

<>f hydrogen purge filters during the 1 O CFR P~rt 50, Appendix.

I dq$e desig.n eva!uatioo and doses through the r;1irborne effluent pathways Were well below the design ,objectives.

The unavailability of hydrogen purge filters will not be considered a reportable event.

  • CH-ODCM-0001 Reference Use Page 34 of 134 Revision 27 , Off-Site Dose Calculation Manual (ODCM) 4.2.48.2.b (continued)
3) The containment air is processed through at least one of the redundant containment HEPA and charcoal filters in the Containment Air Cooling and Filtering Units prior to purging. If the containment purges are made without processing through one of the Containment Air Cooling and Filtering Units, and it is confirmed that one half of the annual dose objective will be exceeded during the calendar quarter, a special report shall be submitted to the NRC as defined in Action 4.2.48.2.a above.

l_ -CH-ODCM-0001 Reference Use Page 35 of 134 Revision 27 Off-Site Dose Calculation Manual (OOCM) 4.3 Uranium Fuel Cycle 4.3.1 Total Dose-Uranium Fuel Cycle A. Limiting Condition for Operation

1. The dose to any real individual from uranium fuel cycle sources shall be limited to s 25 mrem to the total body or any organ ( except the thyroid, which shall be limited to s 75 mrem) during each calendar year. APPLICABILITY:

At all times ACTION: a. With the calculated dose from the release of radioactive materials in liquid or gaseous effluents exceeding twice the limits of specifications 4.1.2A, 4.2.2A, or 4.2.3A, calculations shall be made including direct radiation contribution from the plant and outside storage tanks to determine whether the above limits have been exceeded.

If such is the case, in lieu of any other report required by Section 6.2, prepare and submit a Special Report to the Commission pursuant to Technical Specification 5.16 that defines the corrective action to be taken to reduce subsequent releases to prevent recurrence of exceeding the above limits and includes the schedule for achieving conformance with the above limits. This Special Report, as defined in 10 CFR Part 20.2203(a)(4) and 20.2203(b

), shall include an analysis that estimates the radiation exposure (dose) to a MEMBER OF THE PUBLIC from uranium fuel cycle sources, including all effluent pathways and direct radiation, for the calendar year that includes the release(s) covered by this report. It shall also describe levels of radiation and concentration of radioactive material involved, and the cause of exposure levels or concentrations.

If the estimated dose(s) exceeds the above limits, and if the release condition resulting in the violation of 40 CFR Part 190 or 1 0 CFR Part 72.104 has not already been corrected, the Special Report shall include a request for a variance in accordance with the provisions of 40 CFR Part 190 or 10 CFR Part 72.104. Submittal of the report is considered a timely request, and a variance is granted until staff action on the request is complete.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 4.3.1 (continued)

B. Surveillance Requirements Page 36 of 134 Revision 27 1. Cumulative dose contributions from liquid and gaseous effluents shall be determined in accordance with surveillance requirements 4.1.28, 4.2.2B and 4.2.38 and in accordance with the methodology and parameters in Part 11 of the Off-Site Dose Calculation Manual. 5.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (REMP) 5.1 Monitoring Program 5.1.1 Limiting Condition for Operation A. The Radiological Environmental Monitoring Program shall be conducted as specified in Table 5.1. APPLICABILITY:

At all times ACTION: 1. Analytical results of this program and deviations from the sampling schedule shall be reported to the Nuclear Regulatory Commission in the Annual Radiological Environmental Operating Report (Section 6.2). 2. If the level of radioactivity from calculated doses leads to a higher exposure pathway to individuals, this pathway shall be added to the Radiological Environmental Monitoring Program. Modifications to the program shall be reported in the Annual Radiological Environmental Operating Report to the Nuclear Regulatory Commission.

3. If the level of radioactivity in an environmental sampling medium exceeds the reporting level specified in Table 5.4, and the activity is attributable to plant operation, a Special Report shall be prepared and submitted to the Nuclear Regulatory Commission within 30 days (Section 6.2.3). The detection capabilities of the equipment used for the analysis of environmental samples must meet the requirements of Table 5.3 for Lower Level of Detection (LLD).

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 5.1.1A (continued)

Page 37 of 134 Revision 27 4. If the level of radioactivity in a sample from either an onsite or offsite well, performed per the Site Groundwater Protection Program, exceeds the reporting level specified in Table 5.4, and the activity is attributable to plant operation, a Special Report shall be prepared and submitted to the Nuclear Regulatory Commission within 30 days (Section 6.2.3). The detection capabilities of the equipment used for the analysis of environmental samples must meet the requirements of Table 5.3 for Lower Level of Detection (LLD). Copies of the Special Report will be forwarded to State/Local authorities.

[AR 39127] 5. If the level of radioactivity from either an onsite or offsite well, performed per the Site Groundwater Protection Program exceeds the reporting level specified in Table 5.4, and the activity is attributable to plant operations, state and local authorities shall be notified by the end of the next business day. NRC shall be notified per SO-R-1, Reportability Determinations.

[AR 39127] 6. Radiological environmental sampling loc.ations and the media that is utilized for analysis are presented in Table 5.2. Sampling locations are also illustrated on the map, Figure 1. Details of the quarterly emergency TLD locations are contained in surveillance test CH-ST-RV-0003, Environmental Sample Collection

-Quarterly/Environmental Dosimeters (TLDs). Each TLD sample location contains one dosimeter that is exchanged quarterly for REMP sampling and as needed for Emergency Planning Zone monitoring.

7. Deviations from the monitoring program, presented in this section and detailed in Table 5.2, are permitted if specimens are unobtainable due to mitigating circumstances such as hazardous conditions, seasonal unavailability, malfunction of equipment, or if a person discontinues participation in the program, etc. If the equipment malfunctions, corrective actions will be completed as soon as practicable.

If a person no longer supplies samples, a replacement will be made if possible.

All deviations from the sampling schedule will be described in the Annual Radiological Environmental Operating Report, pursuant to Section 6.2. 5.1.2 Surveillance Requirements A. The Radiological Environmental Monitoring Program (REMP) samples shall be collected and analyzed in accordance with Tables 5.1, 5.2, and 5.3.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Table 5.1 -Radiological Environmental Monitoring Program Exposure Pathway Collection Site A _Type of Analysis 8 and/or Sample 1. Direct Radiation A. 14 TLD indicator stations, one Gamma dose background stationF, total of 15. B. An inner-ring of 16 stations, one in each cardinal sector in the Gamma dose general area of the unrestricted area boundary and within 2.5miles.

C. An outer-ring of 16 stations, one in each cardinal sector located Gamma dose outside of the inner-ring, but no more distant than approximately Smiles. D. Other TLDs may be placed at Gamma dose special interest locations beyond the Restricted Area where either a MEMBER OF THE PUBLIC or Omaha Public Power District employees have routine access. 2. Air Monitoring A. Indicator Stations Filter for Gross Beta c 1. Three stations in the general Charcoal for 1-131 area of the unrestricted area boundary Filter for Gamma Isotopic 2. City of Blair 3. Desoto Township B. One background station F 3. Water A. Missouri River at nearest Gamma isotopic, H-3 downstream drinking water intake. p31 analysis on each composite when the dose B. Missouri River downstream near calculated for the the mixing zone. consumption of water is > 1 mrem/yearG C. Missouri River upstream of Plant intake (background)F.

Page 38 of 134 Revision 27 Frequency Quarterly Quarterly Quarterly Quarterly Weekly Weekly Quarterly composite of weekly filters Composite sample over 2 week period when 11 31 analysis is performed, monthly otherwise for Gamma isotopic analysis.

Quarterly composite for H-3 Analysis CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Table 5.1 -Radiological Environmental Monitoring Program Exposure Pathway Collection Site A Type of Analysis e and/or Sample 4. Milk 0 A. Nearest milk animal (cow or Gamma Isotopic and 1-131 goat) within 5 miles 8. Milk animal (cow or goat) between 5 miles and 18.75 miles (background)F.

5. Fish A. Four fish samples within vicinity Gamma Isotopic of Plant discharge.

B. One background sample upstream of Plant discharge.

6. Sediment A. One sample from downstream Gamma Isotopic area on the station side of the Missouri River. B. One sample from upstream of Plant Intake (background)F.
7. Vegetables or A. One sample In the highest Gamr:na Isotopic Food Products E exposure pathway. B. One sample from onsite crop field C. One sample outside of 5 miles (background)F.
8. Groundwater A. Three samples from sources H3, Gross Beta, Gamma potentially affected by plant Isotopic, Sr-90 operations.

B. One sample outside of 5 miles (background)F.

9. Vegetation in lieu A. One sample at the highest Gamma Isotopic of milk annual average D/Q offsite location.

B. One sample at the second highest annual average D/Q offsite location.

C. One sample outside of 5 miles (background)

F_ Page 39 of 134 Revision 27 Frequency Biweekly grazing season {May to October), monthly at other times Once per season (May to October) Semiannually Once per season (May to October) Quarterly Monthly (when available)

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) NOTES: A. See Table 5.3 for required detection limits. Page 40 of 134 Revision 27 B. The Lower Limit of Detection (LLD) for analysis is defined in the Off-Site Dose Calculation Manual in accordance with the wording of NUREG-1301.

C. When a gross beta count indicates radioactivity greater than 2.SE-13 µCi/ml or 0.25 pCi/m3, (ten times the yearly mean), a gamma spectral analysis will be performed.

D. If milk samples are temporarily not available at a sampling site due to mitigating circumstances, then vegetation (broadleaf, pasture grass, etc.) shall be collected as an alternate sample at the site. If there are no milk producers within the entire 5-mile radius of the plant, then vegetation shall be collected monthly, when available, at two offsite locations having the highest calculated annual average ground level D/Q and a background locale. (Reference Off-Site Dose Calculation Manual, Part II, Table 4 "Highest Potential Exposure Pathways for Estimating Dose") E. Samples should be collected from garden plots of 500 ft2 or more. (Reference Reg. Guide 4.8 "Environmental Technical Specifications for Nuclear Power Plants," Dec. 1975). F. This sample may not be located in the least prevalent wind direction.

The Branch Technical Position paper, Table 1, subnote "d" says this regarding background information, or control locations. "The purpose of this sample Is to obtain background information.

If it is not practical to establish control locatlons In accordance with the distance and wind direction criteria, other sites which provide valid background data may be substituted".

G. The dose shall be calculated for the maximum organ and age group, using methodology and parameters In the Off-Site Dose Calculation Manual.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 41 of 134 Revision 27 Table 5.2 -Radiological Environmental Sampling Locations And Media Approximate Approximate Air Monitoring Distance Sample Approximate from Center Direction Sedi-Station Collection Sites of (degrees Sector TLD Water Milk ment No. Containment from true Airborne Airborne (miles) north) Particulate Iodine Onsite Station, 11 0-meter weather 1 tower 0.53 293°,WNW p X Onsite Station, adjacent 2C,E to old plant access road 0.59 207°/SSW K X X X Offsite Station, Intersection of Hwy. 75 3 and farm access road 0.94 145°/SE G X 4 Blair OPPD office 2.86 305°/NW Q X X X 5" Fort Calhoun, NE City 6 Hall 5.18 150°/SSE H X Fence around intake gate, Desoto Wildlife 7 Refuge 2.07 102°/ESE F X Onsite Station, entrance to Plant Site 8 from Hwy. 75 0.55 191°/S J X Onsite Station, NW of 9 Plant 0.68 305°/NW Q X Onsite Station, WSW of 10 Plant 0.61 242*,wsw M X Offsite Station, SE of 11 Plant 1.07 39°/SE G X Vegetables Ground* Fish and Food water Products CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 42 of 134 Revision 27 Table 5.2 -Radiological Environmental Sampling Locations And Media Approximate Approximate Air Monitoring Distance Sample Approximate from Center Direction Sedi-Station Collection Sites of (degrees Sector TLD Water Milk ment No. Containment from true Airborne Airborne (miles) north) Particulate Iodine Metropolitan Utilities Dist., Florence Treatment Plant 12 North Omaha, NE 14.3 154°/SSE H X West bank Missouri River, downstream from 13 Plant discharge 0.45 108°/ESE F X X Upstream from Intake 14° Bldg, west bank of river 0.09 4°/N A X X 15 Smith Farm 1.99 134°/SE G 16A 17A 18A 19A 20° Mohr Dairy 9.86 186°/S J B 21A Fish Sampling Area, 0.08 22 Missouri River (R.M. 645.0) 60/N A Fish Sampling Area, 17.9 23° Missouri River (R.M. 666.0) 358°/N A 24A 25A 26A 27A Vegetables Ground-Fish and Food water Products X X X X X CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 43 of 134 Revision 27 Table 5.2 -Radiological Environmental Sampling Locations And Media Approximate Approximate Air Monitoring Distance Sample Approximate from Center Direction Sedi,-Station (degrees Sector TLD Water Milk No. Collection Sites of from true ment Contaioment north) Airborne Airborne (miles) Particulate Iodine 28A 29A 30A 31A 32° Valley Substation

  1. 902 19.6 221°,sw L X X X 33A 34A 35 Onsite Farm Field 0.52 118°/ESE F Offsite Station Intersection Hwy 75/Co. 36 Rd.P37 0.75 227°/SW L X Offsite Station Desoto 37 Township 1.57 144°/SE G X X X 38A 39A 4QA 41c Dowler Acreage 0.73 175°/S J X X X B,C 42 Sector A-1 1.94 0°/NORTH A X 43 Sector B-1 1.97 16°/NNE B X 44 Sector C-1 1.56 41°/NE C X 45 SectorD-1 1.34 71°/ENE D X 46 Sector E-1 1.54 90°/EAST E X 47 Sector F-1 0.45 108°/ESE F X Vegetables Ground-Fish and Food Products water X CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 44 of 134 Revision 27 Table 5.2 -Radiological Environmental Sampling Locations And Media Approximate Approximate Air Monitoring Distance Sample Approximate from Center Direction Sedi* Station Collection Sites of (degrees Sector TLD Water MIik ment No. Containment from true Airborne Airborne (miles) north) Particulate Iodine 48 Sector G-1 1.99 134°/SE G X 49 Sector H-1 1.04 159°/SSE H X 50 Sector J-1 0.71 179"fS0UTH J X 51 Sector K-1 0.61 205°/SSW K X 52 Sector L-1 0.74 229°/SW L X
  • 53 Sector M-1 0.93 248°N/SW M X 54 Sector N-1 1.31 266°/WEST N X 55 Sector P-1 0.60 291°N/NW p X 56 Sector Q-1 0.67 307°/NW Q X 57 Sector R-1 2.32 328°/NNW R X 58 Sector A-2 4.54 350°fNORTH A X 59 Sector B-2 2.95 26°/NNE B X 60 SectorC-2 3.32 50°/NE C X 61 Sector D-2 3.11 75°/ENE D X 62 Sector E-2 2.51 90°/EAST E X 63 Sector F-2 2.91 110°/ESE F X 64 SectorG-2 3.00 140°/SE G X 65 Sector H-2 2.58 154°/SSE H X 66 SectorJ-2 3.53 181°/SOUTH J X 67 Sector K-2 2.52 205°1ssw K X 68 Sector L-2 2.77 214*1sw L X 69 Sector M-2 2.86 243°/WSW M X Vegetables Ground-Fish and Food water Products CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 45 of 134 Revision 27 Table 5.2 -Radiological Environmental Sampling Locations And Media Approximate Approximate Air Monitoring Distance Sample Approximate from Center Direction Sedi-Station Collection Sites of (degrees Sector TLD Water Milk ment No. Containment from true Airborne Airborne, (miles) north) Particulate Iodine 70 SectorN-2 2.54 263°/WEST N X 71 Sector P-2 2.99 299°NVNW p X 72 Sector Q-2 3.37 311°/NW Q X 73 Sector R-2 3.81 328°/NNW R X 74 D. Miller Farm 0.65 203°/SSW K 75c Lamp Acreage 0.65 163°/SSE H X X X B,C 76 Stangl Farm 3.40 169°/S J X 77G River N-1 R X 78G River S-1 E X 79G Lagoon S-1 G X BOG Parking S-1 H X 81G Training W-1 K X 82G Switchyard S-1 L X 83G Switchyard SE-1 L X 84G Switchyard NE-1 M X 85G Switchyard W-1 L X 86G Switchyard N-1 N X 87G Range S-1 p X BBG Mausoleum E-1 L X Vegetables Ground-Fish and Food water Products X X X CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) NOTES: Page 46 of 134 Revision 27 A. Location is either not in use or currently discontinued and is documented in the table for reference only. B. If milk samples are temporarily not available at a sampling site due to mitigating circumstances, then vegetation (broadleaf,.

pasture grass, etc.) shall be collected as an alternate sample at the site; If there are no milk producers*

within the entire 5-mile radius of the plant, then vegetation shall be collected monthly, when available, at two offsite locations having the highest calculated annual average ground level D/Q and a. background locale. (Reference Site Dose Calculation Manual, Part II, Table 4 "Highest Potential Exposure Pathways for Estimating Dose") C. Locations represent highest potential exposure pathways as determined by the biennial Land Use Survey, performed in accordance with Part I, Section 7.3.2, of the Off-Site Dose Calculation Manual and are monitored as such. D. Background location (control).

All other locations are indicators.

E. Location for monitoring Sector K High Exposure Pathway Resident Receptor for inhalation.

F. When broad leaf (pasture grasses) are being collected in lieu of milk, background broad leaf samples will be collected at a background locale. G. Location for special interest monitoring general dose to the public per 40CFR190 (Figure 2)

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Figure 1 -Environmental Radiological Sampling Points (*) Locations currently discontinued are not illustrated.

Page 47 of 134 Revision 27 N 1 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Figure 2 -40CFR 190 Sampling Points ----------------*:-~

IOWA , --' ' I .. ,. UNRESTidTED~

AREA BOUNDARY ', domowm AREA I I I I ' I I I I \ CD I.JQUID EFFLUENTS D1SdHAR<1E

@ AIRBORNE EFFLUENTS DISCHARGE 0 r ~CALE IN MILES ... ... ... ", ", ... ... . , ' ' " 1 I ' ' EXCLUSION AND SITE BOUNDARY MAP Page 48 of 134 Revision 27 N \ TO OMAHA CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Pa,1e 49 of 134 Revision 27 Table 5.3 -Detection Capabilities for Environmental Sample Analysis Lower Limit of Detection (LLD) A, B, c Gross Co-58, Sample Units Beta H-3 Mn-54 Fe-59 Co-60 Zn-65 Zr-95 Nb-95 1-131 Cs-134 Cs-137 Water pCI/L 4 2.0E+03 1.5E+01 3.0E+01 1.5E+01 3.0E+01 1.5E+01 1.5E+01 1.0E+00° 1.5E+01 1.8E+01 pCi/kg Fish (wet) ---1.3E+02 2.6E+02 1.3E+02 2.6E+02 ---1.3E+02 1.5E+02 Milk pCI/L ---------1.0E+OO 1.5E+01 1.8E+01 Airborne Particulates or Gases pClfm 3 1.0E-02 --------7.0E-02 1.0E-02 1.0E-02 pCi/kg Sediment (dry) ---------1.5E+02 1.8E+02 Grass or Broad Leaf E E E Vegetation/

Vegetables or pCi/kg Food Products (wet) --------------6.0E+01 6.0E+01 8.0E+01 Ba-140 La-140 1.5E+01 -1.5E+01 ----A. This list does not mean that only these nuclides are to be considered.

Other peaks that are identifiable as Plant effluents, together with those of the above nuclides, shall also be analyzed and reported In the Annual Radiological Environmental Operating Report pursuant to Part I, Section 6.2, of the Off-Site Dose Calculation Manual. B. Required detection capabilities for thermoluminescent dosimeters used for environmental measurements shall be in accordance with the recommendations of Regulatory Guide 4.13 . .C. The LLD is defined in Part II of the Off-Site Dose Calculation Manual. D. LLD for drinking water samples. If no drinking water pathway exists, the LLD of gamma isotopic analysis may be used. E. 1-131 analysis performed on broadleaf/pasture grass samples when milk is unavailable.

Gamma isotopic analysis performed on food products/vegetables.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 50 of 134 Revision 27 Table 5.4 -Reporting Levels for Radioactivity Concentrations in Environmental Samples A Sample Units H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-95 Nb-95 1-131 Cs-134 Water pCi/L 2.0E+04 1.0E+03 4.0E+02 1.0E+03 3.0E+02 3.0E+02 4.CIE+02 4.0E+02 2.0E+00 8 3.0E+01 Fish pCi/kg (wet) --3.0E+04 1.0E+04 3.0E+04 1.0E+04 2.0E+04 ----1.0E+03 Milk pCi/L ----------3.0E+OO 6.0E+01 Airborne Particulates or pCi/m 3 Gases --------9.0E-01 1.0E+01 Grass or Broad Leaf Vegetation/

Vegetables or pCi/kg Food Products (wet) ----------1.0E+02 1.0E+03 A. A Non-routine report shall be submitted when more than one of the radionuclides listed above are detected in the sampling medium and: Concentration 1 Concentration 2 Concentration 3 R . L l 1 + R . . L l 2 + R

  • l 3 + " ... l.O eporting eve eporting eve eporting Leve Cs-137 Ba-140 La-140 5.0E+01 2.0E+02 2.0E+03 -7.0E+01 3.0E+02 2.0E+01 -2.0E+03 --When radionuclides other than those listed above are detected and are the result of Plant efflu,:lnts, this report shall be submitted if the potential annual dose to a member of the general public is equal to or greater than the dose objectives of Part I, Section 4.1 and 4.2, of the Off-Site Dose Calculation Manual. This report is not required if the measured level of radioactivity was not the result of Plant effluents; however, in such an event, the condition shall be reported and described in the Annual Radiological Environmental Operating Report.
  • B. If no drinking water pathway exists, the LLD of gamma isotopic analysis may be used.

CH-ODCM-0001 Reference Use Page 51 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 5.2 Land Use Survey 5.2.1 Limiting Condition for Operation A. A Land Use Survey shall identify the location of the nearest milk animal, neare~t meat animal, nearest vegetable garden, nearest groundwater source and the nearest residence in each of the 16 cardinal sectors within a distance of five miles. The survey shall be conducted under the following conditions:

1. Within a one-mile radius from the Plant site, enumeration by door-to-do.or or equivalent counting techniques.
2. Within a Five-mile radius, enumeration may be conducted door-to-door or by using referenced information from county agricultural agents or other reliable sources. APPLICABILITY:

At all times ACTION: a. If it is learned from this survey that milk animals, vegetable gardens and resident receptors are present at a location which yields a calculated dose greater than 20% from previously sampled location{~).

the new location(s) shall be added to the monitoring program. Milk and vegetable garden ~mpling location(s) havfr1g the lowest calculated dose may then be dropped from the monitoring program at the end ofthe grazing and/or growing season during which the survey was conducted and the new location added to the monitoring program, Groundwater monitoring is based on a determination if source(s) are potentially affected by plant operations.

Modifications to the air monitoring locations, vegetable garden sampling locations, and milk ,sampling locations will be made as soon as practicable.

The Nuclear Regulatory Commission shall be notified of modifications to the program in the Annual Radiological E:nvironmental Operating Report. (Section 6.2).

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 5.2.1A.2 (continued)

Page 52 of 134 Revision 27 b. If it is learned from this survey that a pathway for dose to a MEMBER OF THE GENERAL PUBLIC no longer exists, an additional pathway has been identified or site specific factors affecting the dose calculations for a pathway have changed, then this information should be documented in the Land Use Survey, the Annual Radiological Environmental Operating Report and the Annual Radioactive Effluent Release Report. This information can be used to increase the accuracy of the dose models for the Annual Radioactive Effluent Release Report as well as dose estimates performed during the reporting period (i.e., quarterly dose estimates).

5.2.2 Surveillance

Requirements A. A land use survey shall be conducted once per 24 months between the dates of June 1 and October 1. The results of the land use survey shall be submitted to the Nuclear Regulatory Commission in the Annual Radiological Environmental Operating Report (Section 6.2) for the year it was performed.

5.3 lnterlaboratory

Comparison Program 5.3.1 Limiting Condition for Operation A. Analyses shall be performed on radioactive materials as part of an lnterlaboratory Comparison Program that has been approved by the Nuclear Regulatory Commission.

APPLICABILITY:

At all times ACTION: 1. With analysis not being performed as required above, report the corrective actions taken to prevent a recurrence to the Commission in the Annual Radiological Environmental Operating Report (Section 6.2). 5.3.2 Surveillance Requirements A. The results of these analyses shall be included in the Annual Radiological Environmental Operating Report (Section 6.2).

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 6.0 ADMINISTRATIVE CONTROLS 6.1 Responsibilities Page 53 of 134 Revision 27 6.1.1 FCS Chemistry Department is responsible for the implementation and maintenance of the Off-Site Dose Calculation Manual. 6.1.2 FCS Operations Department is responsible for the compliance with the Off-Site Dose Calculation Manual in the operation of Fort Calhoun Station. 6.2 Radioactive Effluent Reporting Requir~ments The reporting requirements for radioactive effluents stated in this Section are to provide assurance that the limits set forth in Part I of the Off-Site Dose Calculation Manual are complied with. These reports will meet the requirements for documentation of radioactive effluents contained in 10 CFR Part 50.36a; Reg. Guide 1.21, Rev. 2; Reg. Guide4.8, Table 1; and Reg. Guide 1.109, Rev. 1. 6.2.1 Annual Radioactive Effluent Release Report A report covering the operation of the Fort Calhoun Station during the previous calendar year shall be submitted prior to May 1 of each year per the requirements of Technical Specifications 5.9.4.a. and 10 CFR Part 50. The Radioactive Effluent Release Report shall include: A. A summary of the quantities of radioactive liquid and airborne effluents and solid waste released from the plant as outlined in Regulatory Guide 1.21, Revision 2. B. A summary of the annual meteorological data that provides joint frequency distributions of wind direction and wind speed by atmospheric stability class will be Included in the annual report. In addition, hourly meteorological data is recorded and retained on site as outlined in Regulatory Guide 1.21, Revision 2. C. An assessment of radiation doses from the radioactive liquid and airborne effluents released from the unit during each calendar quarter as outlined in Regulatory Guide 1.21, Revision 2. The assessment of radiation doses shall be performed in accordance with calculational methodology of the Regulatory Guide 1.109, Revision 1. D. Changes to the Process Control Program (PCP) or to the Offsite Dose Calculation Manual (ODCM) made during the reporting period. Each change shall be identified by markings in the margin of the affected pages clearly indicating the area of the page that was changed and shall indicate the date the change was implemented.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 6.2.1 (continued)

Page 54 of 134 Revision 27 E. A list and description of abnormal releases or abnormal discharges from the site to unrestricted areas of radioactive materials in gaseous and liquid effluents made during the reporting period. F. An explanation of why instrumentation designated in Part I, Sections 3.1.1 and 3.2, of the Off-Site Dose Calculation Manual, was not restored to OPERABLE status within 30 days. G. A description of any major design changes or modifications made to the Liquid and/or Gaseous Radwaste Treatment Systems or Ventilation Exhaust Systems during the reporting period. H. An explanation of why the liquid and/or gaseous radwaste treatment systems were not OPERABLE, causing the limits of specifications 4, 1.3A and 4.2.4A to be exceeded.

I. The results of sampling from offsite and onsite groundwater wells per the Site Groundwater Protection Plan. [AR 39127] J. Non-routine planned *discharges (e.g., discharges from remediation efforts like pumping contaminated groundwater from a leak). 6.2.2 Annual Rac:tiological gnvironmental Operating Report The Annual Radiological Environmental Operating Report for the previous one year of operation shall be submitted prior to May 1 of each year. This report contains the data gathered from the Radiological Environmental Monitoring Program. The content of the report shall include: A. Summarized and tabulated results of the radiological environmental sampling/analysis activities following the format of Regulatory Guide 4.8, Table 1. In the event that some results are not available, the report shall !:>e submitted noting and explaining the reasons for the missing results. The mis~ing data shall !:>e submitted as soon as possible in a supplementary report. B. Interpretations and statistical evaluation ofthe results, including an assessment of the observed impacts of the plant operation and environment.

C. The results of participation in a NRC approved lnterlaboratory Comparison Program. D. The results of land use survey required by Section 5.2.

CH-ODCM-0001 Reference Use Page 55 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 6.2.2 6.2.3 (continued)

E. The results of specific activity analysis in which the primary coolant exceeded the limits of Technical Specification 2.1.3. The following information shall be included:

1. Reactor power history starting 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> prior to the first sample in which the limit was exceeded.
2. Results of the last isotopic analysis for radioiodine performed prior to exceeding the limit, results of analysis while limit was exceeded and results of one analysis after the radioiodine activity was reduced to less than the limit. Each result should include date and time of sampling and the radioiodine concentrations.
3. Purification system flow history starting 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> prior to the first sample in which the limit was exceeded.
4. Graph of the 1-131 concentration and one other radioiodine isotope concentration in micro-curies per gram as a function of time for the duration of the specific activity above the steadystate level, AND 5. The time duration when the specific activity of the _primary coolant exceeded the radioiodine limit. F. A map of the current environmental monitoring sample locations.

Special Report If the limits or requirements of Sections 4.1.2A, 4.1.3A, 4.2,2A, 4.2.3A, 4.2.4A, 4.3.1 A, and/or 5.1.1 A.3 and/or 5.1.1 A.4 are exceeded, a Special Report shall be issued to the Commission, pursuant to Technical Specification 5.16. This report shall include: [AR 39127] A. . The results of an investigation to identify the causes for exceeding the specification.

B. Define and initiate a program of action to reduce levels to within the specification limits. C. The report shall also include an evaluation of any release conditions, environmental factors, or other aspects necessary to explain the condition.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 6.2.4 EPA 40 CFR Part 190 Reporting Requirements Page 56 of 134 Revision 27 With the calculated dose from the release of radioactive materials in liquid or gaseous effluents exceeding twice the limits of dose from specifications 4.1.2A, 4.2.2A, or 4.2.3A, calculations shall be made including direct radiation calculations, to prepare and submit a special report to the Commission within 30 days and limit the subsequent releases such that the dose to any real individual from uranium fuel cycle sources is limited to s 25 mrem to the total body or any organ (except thyroid, which is limited to s 75 mrem) over the calendar year. This special report shall include an analysis which demonstrates that radiation exposures to any member of the public from uranium fuel cycle sources (including all effluent pathways and direct radiation) are less than the 40 CFR Part 190 standard.

Otherwise, obtain a variance from the Commission to permit releases which exceed the 40 CFR Part 190 standard.

The submittal of the report is to be considered a timely request and a variance is granted pending the final action on the variance request from the Commission.

6.2.5 ISFSI

10 CFR Part 72.104 Reporting Requirements The regulatory requirements of 10CFR20, 10CFR72 and 40CFR190 each limit total dose to individual members of the public without regard to specific pathways.

The only significant exposure pathways for light water reactors included in 10CFR20, 10CFR72 and 40CFR190 not addressed by 10CFR50 Appendix I are the direct radiation pathway and exposure from on-site activity by members of the public. The 10CFR72.104 dose limits are the same as those specified in 40CFR190.

ISFSI dose contribution is in the form of direct radiation as no liquid or gas releases are expected to occur. If the dose limits of 40CFR190 or 1OCFR72.104 are exceeded, a special report to the NRC, as well as an appropriate request for exemption/variance, is required to be submitted to the NRC. The requirement that the dose limits of 1OCFR72.104 apply to any 'real individual' is controlled for ISFSI activities in the ISFSI 72.212 report. Therefore, for the purposes of analyzing dose from the ISFSI, the member of the public as defined in 40CFR190 is the same as for the 'real individual'.

The report of the annual direct radiation required by 1 OCFR72 shall be submitted prior to 60 days from January 1 of each year. The external Total Body Dose is comprised of: 1) Total Body Dose due to noble gas radionuclides in gaseous effluents

2) Dose due to radioactive waste and the ISFSI CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 57 of 134 Revision 27 3) Total Body Dose due to radioactivity deposited on the ground (this dose is accouhted for in the determination of the non-noble gas dose and is not considered here) The Total Body Dose, external is given by: D,ext = O,tb + D,osf WhereD,ext is the external dose D,tb is the total body dose D,osf is the .dose from on-site storage The Total Dose is then given .by: D,tot = D,ext + D,liq + D,nng Dose Limits Where D,tot is the total dose D,ext is the external dose P,liq is the dose from liquid effluents D,nng is the dose from non-noble gases Total Body, annual Thyroid, annual Other Qrgans, annual 25 mrem 75 mrem 25 mrem 6.3 Change Mechanism The Off-Site Dose Calcu.lation Manual is the controlling document for all radioactive effluent releases.

It Js defined as a procedure under the guidance of Technical Specification 5.8. It will be revised and reviewed by the Plant Operations Review Committee and approved by the Plant Manager in accordance with Technical Specification 5, 17. All changes to the Off-Site Dose Calculation Manual will be forwarded to the. Nuclear Regulatory Commission during the next reporting period for the Annual Radioactive Effluent Release Report in accordance with the requirements ofTechnical Specification 5.17.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 6.4 Meteorological Data Page 58 of 134 Revision 27 The Annual Average x/Q is utilized to determine the concentrations of radionuclides at the unrestricted area boundary.

It is also the factor used in conjunction with the parameters and methodologies in Part II, of the Off-Site Dose Calculation Manual to determine unrestricted area dose on a quarterly bases or as needed. It is based on an average of the highest calculated sector xta values, using all 16 sectors for each of the three previous year Annual Radioactive Effluent Release Reports, and the XOQDOQ plume trajectory model. An additional 1 O percent will be added to the average for unrestricted area dose estimates performed quarterly or as needed for conservatism.

When calculating xta data for the Annual Radiological Effluent Release Report, if the highest calculated x/O for the reporting period is observed to be greater than +/- 10% of the Annual Average x/Q previously calculated, contact the -Supervisor-System Chemistry for further instructions.

This model conforms with the Nuclear Regulatory Commissions Regulatory Guide 1.111. Current year meteorological data will be utilized in the preparation of the Annual Radioactive Effluent Release Report. This data is used to calculate the joint frequency table, the dispersion coefficients and deposition factors in all 16 sectors. These are used in the calculation of doses to individuals in unrestricted areas as a result of the operation of Fort Calhoun Station. The models used, GASPAR 2 and LADTAP 2, meet the intent of Nuclear Regulatory Commissions Reg. Guide 1.109 and 1.21 for the reporting of doses due to routine radioactive effluent releases.

6.5 References

6.5.1 Regulatory

Guide 1.109, Rev. 1 -Calculation of Annual Dose to man from Routine Releases of Reactor Effluents for the purpose of evaluation compliance with 10 CFR Part 50, Appendix I 6.5.2 Regulatory Guide 1.111, Rev. 1 -Methods for Estimating Atmospheric Transport and Dispersion of Gaseous Effluents in Routine Releases from Light-Water-Cooled Reactors.

6.5.3 Regulatory

Guide 1.113, Rev. 1 -Estimating Aquatic Dispersion of Effluents from Accidental and Routine Releases for the purpose of Implementing Appendix I. 6.5.4 Regulatory Guide 4.8, Environmental Technical Specification for Nuclear Power Plants. 6.5.5 NRC Branch Technical Position, March 1978 6.5.6 NUREG-0133

-Preparation of Radiological Effluent Technical Specifications for Nuclear Power Plants. 6.5.7 NUREG-1301

-Offsite Dose Calculation Manual Guidance.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 59 of 134 Revision 27 6.5.8 Regulatory Guide 1.21, Rev. 2 -Measuring, Evaluating, and Reporting Radioactivity in solid wastes and Releases of Radioactivity Materials in Liquid and Gaseous Effluents from Light-Water-Cooled Nuclear Power Plants. 6.5.9 Code of Federal Regulations, Title 1 o, Part 20 6.5.10 Code of Federal Regulations, Title 10, Part 50 6.5.11 Code of Federal Regulations, Title 40, Part 190 6.5.12 Fort Calhoun Revised Environmental Report (Unit No. 1 )-1972 6.5.13 Fort Calhoun Technical Specifications (Unit No. 1) 6.5.14 Updated Safety Analysis Report 6.5.15 AR 12357, Implement Recommendations of Memo FC-0133-92, Part I, Table 3.2.1 Action 4, of the Off-Site Calculation Manual 6.5.16 .AR 39127, NEI Industry Initiative on Groundwater, Protection 6.5.17 Regulatory Guide 4.1, Rev. 2 -Radiological Environmental Monito_rlng for Nuclear Power Plants 6.5.18 SO-G-28 -Station Fire Plan 7.0 BASIS 7 .1 Instrumentation 7 .1.1 Radioactive Liquid Effluent Instrumentation The Radioactive liquid effluent instrumentation is provideq to monJtoralid control, as applicable, the releases of radioactive material in liquid effluents during actual or potential releases of liquid effluents.

The Alarmff rip setpoints for these instruments shall be calculated in accordance with Part II of the Offsite Dose Calculation Manual to ensure that the alarm/trip will occur prior to exceeding the limits of 10 CFR Part 20. The OPERABILITY and use of this instrumentation is consistent with the requirements of General Design Criteria 60, 63 and 64 of Appendix A to 10 CFR Part 50.

i -----CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 7.1.2 Radioactive Gaseous Effluent Instrumentation Page 60 of 134 Revision 27 The Radioactive gaseous effluent instrumentation is provided to monitor and control, as applicable, the releases of radioactive material in gaseous effluents during actual or potential releases of gaseous effluents.

The Alarmn-rip setpoints for these instruments shall be calculated in accordance with Part II of the Offsite Dose Calculation Manual to ensure that the alarm/trip will occur prior to exceeding the limits of 10 CFR Part 20. The OPERABILITY and use of this instrumentation is consistent with the requirements of General Design Criteria 60, 63 and 64 of Appendix A to 10 CFR Part 50. 7 .2 Radioactive Effluents 7 .2.1 Radioactive Liquid Effluents A. Concentration This specification is provided to ensure that the concentration of radioactive materials released in liquid waste effluents from the site to unrestricted areas will be less than 10 times the concentration levels specified in 10 CFR Part 20, Appendix 8, Table II, Column 2. This limitation provides additional assurance that the levels of radioactive materials iri bodies of water outside the site will result in exposures within (1) the Section II.A design objectives of Appendix I, 10 CFR Part 50, and (2) the limits of 1 O CFR Part 20.1001-20.2401 to the population.

The concentration limit for dissolved or entrained noble gases is based upon the assumption that Xe-133 is the controlling isotope and its effluent concentration in air (submersion) was converted to an equivalent concentration in water.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 7.2.1 (continued)

B. Dose Page 61 of 134 Revision 27 This specification is provided to implement the requirements of Sections II.A, Ill.A and IV.A of Appendix I, 10 CFR Part 50. The Limiting Condition for Operation implements the guides set forth in Section II.A of Appendix I. The ACTION statements provide the required operating flexibility and at the same time implement the guides set forth in Section IV.A of Appendix I to assure that the releases of radioactive material in liquid effluents will be kept "as low as is reasonably achievable".

Also, with fresh water sites with drinking water supplies which can be potentially affected by plant operations, there is reasonable assurance that the operation of the facility will not result in radionuclide concentrations in the finished drinking water that are in excess of the requirements of 40 CFR Part 141. The dose calculation methodology and parameters in Part II of the Off-Site Dose Calculation Manual, implement the requirements in Section Ill.A that conformance with the guides of Appendix I is to be shown by calculational procedures based on models and data such that the actual exposure of an individual through appropriate pathways is unlikely to be substantially underestimated.

The equations specified in Part II of the Off-Site Dose Calculation Manual, for calculating the doses due to the actual release rates of radioactive material in liquid effluents are consistent with the methodology provided in Regulatory Guide 1.109, "Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purpose of Evaluating Compliance with 10 CFR Part 50, Appendix l, 11 Revision 1, October 1977, and Regulatory Guide 1.113, "Estimating Aquatic Dispersion of Effluents from Accidental and Routine Reactor Releases for the Purpose of Implementing Appendix I," April 1977. C. Liquid Waste Treatment System The OPERABILITY of the liquid radwaste treatment system ensures that this system will be available for use Whenever liquid effluents require treatment prior to release to the environment.

The requirement that appropriate portions of this system be used when specified provides assurance that the releases of radioactive materials in liquid effluents will be kept "as low as is reasonably achievable".

This specification implements the requirements of 10 CFR Part 50.36a, General Design Criterion 60 of Appendix I to 10 CFR Part 50 and design objective and in Section 11.D of Appendix A to 10 CFR Part 50. The specified limits governing the use 9f appropriate portions of the liquid radwaste treatment system were specified to ensure the design objectives set forth in Section II.A of Appendix I, 10 CFR Part 50 for liquid effluents are not exceeded.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 7.2.1 (continued)

D. Liquid Holdup Tanks Page 62 of 134 Revision 27 Restricting the quantity of radioactive material contained in the specified tanks provides assurance that in the event of an uncontrolled release of the tanks' contents, the resulting concentrations would be less than the limits of 10 CFR Part 20, Appendix B, Table II, Column 2, at the nearest potable water supply and the nearest surface water supply in an unrestricted area. 7.2.2 Radioactive Gaseous Effluents A. Concentration This specification, in conjunction with Steps 4.2.2A and 4.2.3A, is provided to ensure that the dose at or beyond the Site Boundary from gaseous effluents will be within the annual dose limits of 10 CFR Part 20 for MEMBERS OF THE PUBLIC. The release rate of radioactive material in airborne effluents shall be controlled such that the instantaneous concentrations for these radionuclides do not exceed the values specified in 10 CFR Part 20 for airborne effluents at the unrestricted area boundary.

To support plant operations, Supervisor-System Chemistry may increase this limit up to the limits specified in Technical Specifications 5.16.1.g.

Technical Specification 5.16.1.g.

establishes the administrative control limit on the concentration resulting from radioactive material, other than noble gases, released in gaseous effluents to unrestricted areas conforming to ten times 10 CFR Part 20.1001-20.2401, Appendix B, Table 2, Column 1. For noble gases, the concentration shall be limited to five times 10 CFR Part 20.1001-20.2401, Appendix B, Table 2, Column 1. Because these concentrations are applied on an instantaneous basis and because of the overriding 10 CFR Part 50 Appendix I cumulative dose limitations, these limits provide reasonable assurance that radioactive material discharged in gaseous effluents will not result in the exposure of a MEMBER OF THE PUBLIC either within or outside the Site Boundary, to annual average concentrations that would result in exceeding the annual total effective dose equivalent limit specified in 10 CFR Part 20.1301 (a).

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 7.2.2 (continued)

B. Dose -Noble Gases Page 63 of 134 Revision 27 This specification is provided to implement the requirements of Sections 11.B, Ill.A and IV.A of Appendix I, 10 CFR Part 50. The Limiting Condition For Operation implements the guides set forth in Section 11.B of Appendix I. The ACTION statements provide the required operating flexibility and at the same time implement the guides set forth in Section IV.A of Appendix I assure that the releases of radioactive material in gaseous effluents will be kept as low as is reasonably achievable.

The surveillance requirements implement the requirements in Section Ill.A of Appendix I that conform with the guides of Appendix I to be shown by calculational procedures based on models and data such that the actual exposure of an individual through the appropriate pathways is unlikely to be substantially underestimated.

The dose calculation methodology and parameters established in Part II of the Site Dose Calculation Manual, for calculating the doses due to actual release rates of radioactive noble gases in gaseous effluents are consistent with the methodology provided in Regulatory Guide 1.109, Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purpose of Evaluating Compliance with 10 CFR Part 50, Appendix I, Revision 1, October 1977 and Regulatory Guide 1.111, Methods for Estimating Atmospheric Transport and Dispersion of Gaseous Effluents in Routine Releases from Light-Water-Cooled Reactors, Revision 1, July 1977. The Off-Site Dose Calculation Manual, equations provided for determining the air doses at the site boundary are consistent with Regulatory Guides 1.109 and 1.111.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 7.2.2 (continued)

Page 64 of 134 Revision 27 C. Dose 131, Radioactive Material in Particulate Form with Half-Lives Greater than Eight Days (Other than Noble Gases) and Tritium This specification is provided to implement the requirements of Sections 11.C, Ill.A and IV.A of Appendix I, 10 CFR Part 50. The Limiting Condition For Operation implements the guides set forth in Section 11.C of Appendix I. The ACTION statements provide the required operating flexibility and at the same time implement the guides set forth in Section IV.A of Appendix I assure that the releases of radioactive material in gaseous effluents will be kept as low as is reasonably achievable.

The surveillance requirements implement the requirements in Section II I.A of Appendix I that conform with the guides of Appendix I to be shown by calculational procedures based on models and data such that the actual exposure of an individual through the appropriate pathways is unlikely to be substantially underestimated.

ihe dose calculation methodology and parameters established in Part II of the Site Calculation Manual, for calculating the doses due to actual release rates of radioactive noble gases in gaseous effluents are consistent with the methodology provided in Regulatory Guide 1.109, Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purpose of Evaluating Compliance with 10 CFR Part 50, Appendix I, Revision 1, October 1977 and Regulatory Guide 1. 111, Methods for Estimating Atmospheric Transport and Dispersion of Gaseous Effluents in Routine Releases from Light-Water-Cooled Reactors, Revision 1, July 1977. The release rate specification for 1-131, radioactive material in particulate form with half-lives greater than eight days (other than noble gases) and tritium are dependent on the existing radionuclide pathways to man in the areas at or beyond the site boundary.

The pathways that were examined in the development of these calculations were: 1 ) individual inhalation of airborne radionuclides, 2) deposition of radionuclides onto green leafy vegetation with subsequent consumption by man, 3) deposition onto grassy areas where milk animals and meat producing animals graze with consumption of the milk and meat by man, and 4) deposition on the ground with subsequent exposure of man.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 7.2.2 (continued)

D. Gaseous Waste Treatment Page 65 of 134 Revision 27 The OPERABILITY of the gaseous radwaste treatment system and the ventilation exhaust treatment systems ensures that the systems will be available for use whenever gaseous effluents require treatment prior to release to the environment.

The requirement that appropriate portions of this system be used when specified provides assurance that the releases of radioactive materials in gaseous effluents will be kept as low as is reasonably achievable.

This specification implements the requirements of 10 CFR Part 50.36a, General Design Criterion 60 of Appendix I to 1 O CFR Part 50 and design objective and in Section 11.D of Appendix A to 10 CFR Part 50. The specified limits governing the use of appropriate portions of the systems were specifi~d to ensure the design objectives set forth in Section 11.B and 11.C of Appendix I, 10 CFR Part 50 for gaseous effluents are not exceeded.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 7.2.2 (continued)

E. Total Dose -Uranium Fuel Cycle Page 66 of 134 Revision 27 This specification is provided to meet the dose limitations of 40 CFR Part 190 that have been incorporated into 1 o CFR Part 20.1301 (d). This requires the preparation and submittal of a Special Report whenever the calculated doses due to releases of radioactivity and to radiation from uranium fuel cycle sources exceed 25 mRems to the total body or any organ, except the thyroid, which shall be limited to less than or equal to 75 mRems. It is highly unlikely that the resultant dose to a MEMBER OF THE PUBLIC will exceed the dose limits of 40 CFR Part 190 if the plant remains within twice the dose design objectives of Appendix I, 10 CFR Part 50, and if direct radiation doses (including outside storage tanks, etc.) are kept small. The Special Report shall describe a course of action that should result in the limitation of the annual dose to a MEMBER OF THE PUBLIC to within the 40 CFR Part 190 limits. For purposes of the Special Report, it may be assumed that the dose commitment to the MEMBER OF THE PUBLIC from other uranium fuel cycle sources is negligible, with the exception that dose contributions from other nuclear fuel cycle facilities at the same site or within a radius of 8 km must be considered.

If the dose to any MEMBER OF THE PUBLIC is estimated to exceed the requirements of 40 CFR Part 190, the Special Report, with a request for a variance (provided the release conditions resulting in violation of 40 CFR Part 190 have not already been corrected), in accordance with the provisions of 40 CFR Part 190.11 and 1 O CFR Part 20.2203(a)(4) and 20.2203(b) is considered to be a timely request and fulfills the requirements 40 CFR Part 190 until NRC staff action is completed.

The variance only relates to the limits of 40 CFR Part 190, and does not apply in any way to the other requirements for dose limitation of 10 CFR Part 20. An individual is not considered a MEMBER OF THE PUBLIC during any period in which he/she is engaged in carrying out any operation that is part of the nuclear fuel cycle. Demonstration of compliance with the limits of 40 CFR Part 190 or with the design objectives of Appendix I to 1 O CFR Part 50 will be considered to demonstrate compliance with the 0.1 rem limit of 10 CFR Part 20.1301.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 7 .3 Radiological Environmental Monitoring 7 .3.1 Monitoring Program Page 67 of 134 Revision 27 The radiological environmental monitoring program required by this specification provides measurements of radiation and radioactive materials in those e>eposure pathways and for radionuclides which lead to the highest potential radiation exposures of individuals resulting from the station operation.

This monitoring program thereby supplements the radiological effluent monitoring program by verifying that the measurable concentrations of radioactive materials and levels of radiation are not higher than expected on the basis of the effluent measurements and modeling of the environmental exposure pathways.

The initially specified monitoring program was effective for at least the first three years of commercial operation.

Following this period, program changes are initiated based on operational experience.

7.3.'2 Land Use Survey This specification is provided to -ensure that changes in the use of unrestricted areas are identified and that modifications to the monitoring program are made if required by the results of this survey. The frequency of the Land Use Survey has been reduce-0 to a biennial requirement in site procedures because persons knowledgeable in land use census monitor usage characteristics perform routine REMP sampling, This approach allows knowledge gained during sample collect{on to be integrated into the program, maintaining its effectiveness.

The best survey informatjon from door to door, aerial or consulting with local agricultural authorities, or equivalent, shall be 1.1sed. This survey satisfies the req1.1irements of $ectio11 IV.B.3 <>f Appendix I to 1 O CFR Part 50. Restricting the survey to gardens of greater than 500 square feet provides assurance that significant exposure pathways via leafy vegetables will be identified and monitored since a garden of this size is the minimum required to produce the quantity (26 kg/year) of leafy vegetables assumed in Regulatory Guide 1.109 for consumption by a child. To determine this minimum garden size, the following assumptions were used, 1) that 20% of the garden was used for growing broad leaf vegetation (i.e.; similar to lettuce and cabbage), and 2) a vegetation yield of 2 kg/m 2* For milk, the survey is restricted to only milk animals (cow or goat) procjucing milk for human consumption.

Air monitoring stations are strategically located to monitor the resident receptors who could potentially receive the highest doses from airborne radioactive material.

For groundwater, samples Shall be taken when sources are determined to potentially be affected by plant operations, and when sources are tapped for drinking or irrigation purposes in areas where the hydraulic gradient or recharge properties are suitable for contamination.

Guidance provided in the Branch Technical Position and Technical Specification 5.16.2 is used to meet the intent of NUREG-1301.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 7.3.3 lnterlaboratory Comparison Program Page 68 of 134 Revision 27 The requirement for participation in an lnterlaboratory Comparison Program is provided to ensure that independent checks on the precision and accuracy of the measurements of radioactive material in environmental sample matrices are performed as part of a quality assurance program for environmental monitoring in order to demonstrate that the results are reasonably valid for the purposes of Section IV.8.2 of Appendix I to 1 O CFR Part 50. 7.4 Abnormal Release or Abnormal Discharge Reporting

7.4.1 Specific

information should be reported concerning abnormal (airborne and/or liquid) releases on site and abnormal discharges to the unrestricted area. The report should describe each event in a way that would enable the NRC to adequately understand how the material was released and if there was a discharge to the unrestricted area. The report should describe the potential impact on the ingestion exposure pathway involving surface water and ground water, as applicable.

The report should also describe the impact (if any) on other affected exposure pathways (e.g., inhalation from pond evaporation).

7.4.2 The following are the thresholds for reporting abnormal releases and abnormal discharges in the supplemental information section: A. Abnormal release or Abnormal Discharges that are voluntarily reported to local authorities under NEI 07-07, Industry Ground Water Protection Initiative.

[AR 39127) " 8. Abnormal release or Abnormal discharges estimated to exceed 100 gallons of radioactive liquid where the presence of licensed radioactive material is positively identified (either in the on-site environs or in the source of the leak or spill) as greater than the minimum detectable activity for the laboratory instrumentation.

C. Abnormal releases to on-site areas that result in detectable residual radioactivity after remediation.

D. Abnormal releases that result in a high effluent radiation alarm without an anticipated trip occurring.

E. Abnormal discharges to an unrestricted area.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 69 of 134 Revision 27 7.4.3 Information on Abnormal releases or Abnormal discharges should include the following, as applicable:

  • Date and duration
  • Location
  • Volume *' E~timated activity of each radionuclide
  • Effluent monitoring results (if any)
  • On-site monitoring results {is any)
  • Depth to the. locc:11 water table
  • Classification(s) of subsurface aquifer(s) (e.g., drinking water, unfit for drinking water, not used for drinking water)
  • Size and extent of any ground water plume
  • Expected movement/mobility of any ground water plume
  • Land use characteristic::s

{e.g., water used for irrigation)

  • Remedial actions c_onsidered or taken and results obtained
  • Calculated member of the public dose attributable to the release
  • Calculated member of the public dose attributable to the discharge
  • Actions taken to prevent recurrence, as applicable
  • Whether the NRC was notified, the date(s), and the. contact organization CH-ODCM-0001 Reference Use Qff .. :Site Dose Calculation Manual (ODCM) PART II CALCULATIONS Page 70 of 134 Revision 27 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 1.0 EFFLUENT MONITOR SETPOINTS

1.1 Liquid

Effluents Page 71 of 134 Revision 27 1.1.1 There are two liquid discharge pathways to the Missouri River. These pathways originate with the radioactive liquid waste processing system (monitor or hotel tanks) and the steam generator blowdown system. Both of these pathways empty into the circulating water system which discharges to the Missouri River (see Figure 1 ). Figure 2 depicts the liquid discharge pathways and associated radiation monitors.

Figure 3 depicts the methods of liquid effluent treatment.

1. 1.2 The flowrate for dilution water varies with the number of circulating water pumps in service, the number of raw water pumps in service, and with tile operation of the warm water recirculation.

Some warm water from the condenser outlet is diverted from the circulating water discharge t9 upstream of the intake structure to help prevent ice from forming on the circulating water pump intakes during winter months. The varying dilution flowrate and utilization of warm water recirculation is accounted for in the dilution calculations for monitor tank and stream generation releases.

1.1.3 Technical

Specification 5.16.1.b establishes the administrative control limit on concentration of radioactive material, other than dissolved or entrained noble gases, released in liquid effluents to unrestricted areas conforming to ten times 10 CFR Part 20.1001-20.2401, Appendix 8, Table 2, Column 2. For dissolved or entrained noble gases, the concentration shall be limited to 2.0 E-04 µCi/ml total activity.

1.1.4 The liquid effluent monitoring instrumentation ALERT setpoints shall be established low enough to ensure that the concentration of radioactive material released in liquid effluents at site discharge will be less than the concentrations specified in 10 CFR Part 20, Appendix 8, Table 2, Column 2. 1.1.5 The liquid effluent monitoring instrumentation HIGH ALARM setpoints shall be established low enough to ensure that the concentration of radioactive material released in liquid effluents at site discharge will be less than 10 times the concentrations specified in 10 CFR Part 20, Appendix 8, Table 2, Column 2. 1.1.6 Cs-137 is used to calibrate the liquid effluent monitors.


~l CH-ODCM-0001 Reference Use Page 72 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) NOTE

  • If the annual average x/Q value exceeds 1.4E-04 sec/m 3 , consideration
  • I should be given to basing liquid radiation monitor setpoints on an 1-131 I instantaneous limit of 2.0E-09 µCi/ml at the unrestricted area boundary with 10% vapor/liquid separation.

Contact the Supervisor-System Chemistry for further instructions.

1.1. 7 Liquid Effluent Radiation Monitors A. Steam Generator Slowdown Monitors (RM-054A and B) 1. These process radiation detectors monitor the flow through the steam generator blowdown lines and automatically close the blowdown isolation valves if the monitor high alarm setpoint is reached. The monitor controls liquid effluent releases so that 10 times the 10 CFR Part 20 limit at the unrestricted area boundary of 1.0E-06 µCi/cc, is not exceeded at the site discharge.

2. The following calculations for maximum concentration and alarm setpoints are valid for simultaneous radioactive liquid releases of steam generator blowdown and monitor tank discharge.
3. The maximum allowable concentration in the blowdown line is calculated as follows: (1.0E -05µCi/ml)(F)

CMAX = f Where: 1.0E-05 µCi/ml = Ten times 10 CFR Part 20 Limit for unidentified radionuclides at site discharge (1 O CFR Part 20, Appendix B, Note 2). F = Total dilution flow in the discharge tunnel (gpm). (Normal flow is based on 1 circulating water pump at 120,000 gpm. Other flowrates may be used, as required.)

f = Slowdown flow rate (gpm). (Normal blowdown flow rate is based on 2 transfer pumps with a design flow of 135 gpm each, 270 gpm total. Other flow rates may be used, as required.)

CMAX = Maximum allowable blowdown concentration

(µCi/ml).

I CH-ODCM-0001 Reference Use Page 73 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 1.1.7A (continued)

  • 1 NOTE
  • I 1Setpoints may be recalculated based on adjusted dilution I flow and ad'usted blowd.own flow. The High Alarm Setpoint (CPM): Setpoint = 0.75 [( (K4)(s, )(CMAX)) + B] Where: 0.75 St B CMAX = An administrative correction factor which includes the following:

15% tolerance to ensLJre radmonitor response in accordance with License Event Report 77-17, Docket Number 050-0285 and Telecon FC-472-77.

10% tolerance to account for the difference in detector sensitivity for the range of isotopes detected.

= Detector sensitivity factor (CPM/µCi/ml). (Sensitivity based on Cs-137). * = Allocation factor for Individual Steam Ge.nerator Release (See Table 1) = Background (CPM) = Maximum allowable blowdown line activity (µCi/ml).

The Alert Setpoint will be chosen less than or equal to one tenth (1/10) the value of the high alarm setpoint yalue so that significant increases in activity will be identified prior to exceeding an Unrestricted Area fractional sum of 1.0. It will also provide additional time for corrective actions prior to exceeding the Alarm Setpoint.

CH-ODCM-0001 Reference Use Page 74 of 134 Revision 27 Off-Site Dose Calculation Manual (ODOM) 1 .. 1.7 (continued)

B. Overboard Discharge Header Monitor (RM-055) 1. This process radiation monitor provides control of the waste monitor tank effluent by monitoring the overboard header prior to its discharge into the circulating water discharge tunne_l. The concentration of activity .at discharge is controlled below ten times the 1 O CFR Part 20 limit of 1.0E-06 µCi/ml at site discharge for unidentified isotopes by the high alarm setpoint which closes the overboard flow control valve. 2. The following calculations for maximum concentration and alarm setpoints are valid for simultaneous radioactive liquid releases of monitor tank discharge and steam generator blowdown.

3. The maximum allowable con~ntration in the overboard discharge header is: (1.0E -05 µCi/ml) (F) CMAX = f Where: 1.0E-05 µCi/ml = Ten times 10 CFR Part 20 Limit for unidentified radionuclides at site discharge (10 CFR Part 20, Appendix B, Note 2). F = Total dilution flow in the discharge tunnel (gpm). (Normal flow is based on 1 circulating water pump at 120,000 gpm. Other flowrates such as raw water pump(s) may b.e used, as required.)

f = Maximum monitor tank discharge flow rate (gpm). (Normal monitor tank maximum flow is 50 gpm. Other flow rates such as raw water pump(s) m~y be used, as required.)

CMAX -Maximum allowable activity in discharge header (µCi/ml).

CH-ODCM-0001 Reference Use Page 75 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 1.1 :7B (continued)

The High Alarm Setpoint (CPM):, Setpoint*

= 0-.75 [(CKs)(s,)cc;..,AX))

+ B] Where: 0.75 St Ks B = An administrative correction factor=whi~h includes the following:

15% tolerance to ensure radmonitor VIAS response in accordance with License Event Report 77-17, Docket Number 050-0285 and Telecon FC-472-77.

10% tolerance to account for the difference in detector sensitivity for the range of isotopes detected.

= Detector sensitivity factor {CPM/µCi/ml).

{$ensitivity based on Cs-137). , , = Allocation factor for Waste Liquid Releases, (See Table 1) = Maximum allowable:

concentration in discharge header (µCi/ml).

= B~ckground (CPMJ The Alert Setpoint will .be chosen less than or equal to one tenth (1/10) the value of the high alarm setpoint value so that significant increases in activity will be identified prior to exceeding an Unrestricted Area fractional sum of 1 .0. It will also provide additional time for corrective actions priorto exceeding the Alarm Setpoint CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 1.2 Airborne Effluents Page 76 of 134 Revision 27 1.2.1 There are three air effluent discharge pathways at the Fort Calhoun Station: Condenser Offgas, Laboratory and Radioactive Waste Processing Building Exhaust Stack, and the Auxiliary Building Exhaust Stack. An airborne radioactive waste flow diagram with the applicable, associated radiation monitoring instrumentation and controls is presented as Figure 4. The airborne waste disposal system is presented in Figure 5.

  • Auxiliary Building -The Auxiliary Building Exhaust Stack receives discharges from the waste gas decay tanks, containment purge, containment vent systems and the auxiliary building ventilation system. Radiation Monitor RM-062 provides noble gas monitoring and iodine and particulate sampling for the Auxiliary Building Exhaust Stack. Backup noble gas mpnitoring and iodine and particulate sampling is provided by RM-052. Ventilation Isolation Actuation Signal {VIAS) is actuated by exceeding a monitor's alarm setpoint.

Actuation of VIAS will isolate releases from containment and waste gas decay tanks. The Auxiliary Building Exhaust fans will remain in operation.

  • Laboratory and Radioactive Waste Processing Building (LRWPB)-Noble gas monitoring and particulate and iodine sampling is provided by RM-043. This radiation monitor/sampler does not serve a control function. (
  • Condenser Off-Gas Monitors -Noble gas activity is monitored by RM-057. The condenser off-gas is discharged directly to the environment.

Exceeding the high alarm setpoint on RM-057 will activate isolation of main steam to the Auxiliary Steam System. Technical Specification 5.16.1.g.

establishes the administrative control limit on the concentration resulting from radioactive material, other than noble gases, released in gaseous effluents to unrestricted areas conforming to ten times 1 O CFR Part 20.1001-20.2401, Appendix B, Table 2, Column 1. For noble gases, the concentration shall be limited to five times 10 CFR Part 20.1001-20.2401, Appendix B, Table 2, Column 1. The airborne effluent monitoring instrumentation ALERT setpoints shall be established low enough to ensure that the concentration of radioactive material released in air effluents at site discharge will be less than the concentrations specified in 10 CFR Part 20, Appendix B, Table 2, Column 1. The airborne effluent monitoring instrumentation HIGH ALARM setpoints shall be established low enough to ensure that the concentration of radioactive material released in air effluents at site discharge will be less than 5 times the concentrations specified in 10 CFR Part 20, Appendix B, Table 2, Column 1.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 1.2.2 Airborne Effluent Radiation Monitors Page 77 of 134 Revision 27 A. Auxiliary Building Exhaust Stack Noble Gas Activity Monitor (RM-062/RM-052)

1. Either of these monitors may be used to measure the noble gas activity in the exhaust stack. The noble gas is monitored after passing through a particulate filter, and charcoal cartridge.

The monitor controls airborne releases so that five times the 10 CFR Part 20 limit at the unrestricted area boundary of 5.0E-07 µCi/cc, based upon Xe-133, is not exceeded.

The Ventilation Isolation Actuation Signal is initiated when the high alarm setpoint is reached. 2. The following calculations for maximum release rate and alarm setpoint are valid for simultaneous airborne releases from Auxiliary Building Exhaust Stack, Condenser Off-gas and the LRWPB Exhaust Stack. 3. The maximum allowable release rate for stack airborne activity is calculated as follows: * . (2.SE -06 µCi/ cc) 3 RMAX µCi/sec= x/Q sec/m 3 1.0E + 06 cc/m Where: 2.5E-06 µCi/cc = 5 times the 10 CFR Part 20 Limit at the unrestricted area boundary (based upon Xe-133). x/Q sec/m 3 = Annual average dispersion factor at the unrestricted area boundary from Part II Table 4, of the Off-Site Dose Calculation Manual. 1.0E+06 cc/m 3 = Constant of unit conversion.

CH-ODCM-0001 Reference Use Page 78 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 1.2.2A (continued)

The High Alarm Setpoint (CPM), . [ ((RMAX)(S1

)(60)) ] Setpomt = 0.75 K 1 (Fv)(ZS 317) + B Where:. 0.75 St K1 60 28317 Fv RMAX B -An administrative correction factor which includes the following:

= = = = = ;:: = 15% tolerance to ensure radmonitor VIAS response in accordance with License Event Report Tt-17, Docket Number 050-0285 and Telecon FC-472-77.

10% tolerance to allow for the contribution of noble gases otherthan Xe-133 towards the total ECL fraction sum. Detector sensitivity factor (CPM/µCi/cc). (Sensitivity based on Xe-133) Allocation factor for Auxiliary Building Exhaust Stack (See Table 1) Conversion (seconds to minutes).

Conversion factor (ft 3 to cc). Auxiliary Building Exhaust stack flow rate (SCFM). (Default maximum flow rate is 122,500 cfm for 3 Auxiliary Building exhaust fans and 2 containment purge fans in operation.

Other flow rates may be used, as required,)

Maximum Allowable Release Rate in µCi/sec Background

.(CPM) The Alert Setpoint will be chosen less than or equal to one fifth (1/5) the value of the high alarm setpoint value so that significant increases in activity will be identified, prior to exceeding an Unrestricted Area fractional sum of 1.0. It will also provide additional time for corrective actions prior to exceeding the Alarm Setpoint and VIAS actuation.

CH-ODCM-0001 Reference Use Page 79 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 1.2.2 (continued)

13. Condenser Off Gas Monitor (RM-057) 1. This monitor is located in the turbine building and monitors the condenser off-gas. The purpose bf this monitor is to monitor the condenser off;..gas discharges so that five times the 1 O CFR Part 20 limit at the unrestricted area boundary of 5.0E-07 µCi/cc, based upon Xe-133, is not exceeded.
2. The following calculations for maximum release rate and alarm setpoint are valid for simultaneous airborne releases from condenser off-gas, Auxiliary Building Exhaust Stack, and tt:le LRWPB Exhaust Stack. 3. The maximurn allowable release rate for condenser air ejector monitor is as follows: * . (2.SE -06 µCi/ cc) . .* 3 RMAXµCz/sec=

/Q I 3 1.0E+06cc/m x . sec m Where: 2.5E-06 µCi/cc = 5 times the 10 CFR Part 20 Limit at the unrestricted arec:;1 boundary (based upon .Xe-133).

K/Q sec/m 3 = Annual avera*ge dispersion factor at the unrestricted area boundary from Part II, Table 4, of the Off-Site Dose. Calculation Manual. 1.0E+06 cc/m 3 = Constant of unit conversion.

CH-ODCM-0001 Reference Use Page 80 of 134 Revision 27 Off-Site Dose Calculation Manual (ODOM) 1.2.28 (continued)

The High Alarm Setpoint (CPM): . -_ [ ((RMAX)(St

)((50)) ] Setpomt = 0.75 K 2 (Fv)C 28317) + B Where: 0.75 St 60 28317 Fv RMAX B = An administrative correction factor which includes the following:

= = = = = = = 15% tolerance to ensure radmonitar VIAS response in accordance with License Event Report 77-17, Docket Number 050-0285 and Telecon FC-472-77.

10% tolerance to allow for the contribution of noble gases other than Xe-133 towards the total ECL fraction sum. Detector sensitivity factor (CPM/µCi/cc). (Sensitivity based on Xe-133) Allocation factor for Condenser Off Gas (See TaQle 1) Conversion (seconds to minutes).

Conversion factor (ft3 to cc). Vent stack flow rate (SCFM). Default maximum flow rate is 4,755 scfm (3 vacuum pumps in hogging mode. Other flow rates may be used, as required.)

Maximum Allowable Release Rate in µCi/sec. Background (CPM) The Alert Setpoint will be chosen less than or equal to one fifth (1/5) the value of the high alarm setpoint value so that significant increc3ses in activity will be identified, prior to exceeding an Unrestricted Area fractional sum of 1.0. It will also provide additional time for corrective actions prior to exceeding the Alarm Setpoint and tripping of the auxiliary steam supply valve, RCV-978.

CH-ODCM-0001 Reference Use Page 81 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 1.2.2 (continued)

C. Laboratory and Radioactive Waste Processing 13uilding Exhaust Stack Noble Gas Activity Monitor and Iodine and Particulate.

Sampler (RM-043) 1. RM-043 is located in the Radwaste Building and samples the LRWPB Exhaust Stack. The monitor alarm setpoint is based on five times the 10 CFR Part 20 limit for xe .. 133 at the unrestricted area boundary.

2. The following calculations for maximum release rate and alarm setpoint are valid for simultaneous a.irborne releases from condenser off-gas, Auxiliary Building E:xhaust Stack, and the LRWPB Exhaust Stack. */ . (2.SE -06 µCi/ cc) 3 RMAX µCi sec= IQ . 3 1.0E + 06cc/m
  • x sec/m The maximum allowable release rate for RM..:043 is as follows: Where: 2.SE-06 µCi/cc x/Q = 5 times the 10 CFR Part 20 Limit at the unrestricted area boundary (based upon Xe-133). = Annual average dispersion factor at the unrestricted area boundary from Part II of the Off-Site Dose Calculation Manual, Table 4. *1.0E+OG cc/hl 3 = Constant of unit conversion CH-ODCM-0001 Reference Use Page 82 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 1.2.2C (continued)
  • NOTE II I This monitor alarms in the Control Room. There are no I automatic control functions associated with the actuation of the alarm. The High Alarm Setpoint (CPM): . . [ ((RMAx}{s,)(60))

] Setpomt = 0.75 K 3 . (Fv)(ZS 317) .. + B Where: 0.75 St K3 60 28317 Fv RMAX B = An administrative correction factor which includes the following:

-= = = = = 15% toierance to ensure radmonitor VIAS response in accordance with License Event Report 77-17, Docket Number 050-0285 and Telecon FC-472-77.

10% tolerance to allow. for the contribution of noble gases other than Xe-133 towards the total ECL fraction sum. Detector sensitivity factor (CPM/µCi/cc). (Sensitivity based on Xe-133) Allocation factor for LRWPB Exhaust Stack (See Table 1) Conversion (seconds to minutes).

Conversion factor (ft 3 to cc).

  • LRWPB Exhaust stack flow rate (SCFM). (Default flow rate is 28,700 cfm. Othefflow rates may be t1sed if required.)

Maximum Allowable Release Rate in µCi/sec. Background (CPM) The Alert Setpoint will be* chosen less than or equal to one fifth (1/5) the value of the high alarm setpoint value so that significant increases in activity will be identified, prior to exceeding an Unrestricted Area fractional sum of 1.0. It will also provide additional time for corrective actions prior to exceeding the Alarm Setpoint.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 83 of 134 Revision 27 Table 1 -Allocation Factors for Simultaneous Releases I NOTE

  • The Fort Calhoun Station is capable of performing simultaneous airborne releases.
  • I I The factors below may be adjusted to meet release requirements, provided that the I sum of the Unrestricted Area Fraction Sum for all airborne releases remains less than or eaual to 1.0. A. Allocation Factors for Simultaneous Airborne Releases 1. Auxiliary Building Exhaust Stack Total: 0.80 K1 Noble Gases (RM-062 or RM-052) 0.70 lodine/Particulateffritium 0.10 Contributing Pathways:

/ a) Auxiliary Building 0.10 b) Containment Building 0.65 c) Waste Gas Decay Tanks 0.05 2. Condenser/Off Gas Total: 0.10 K2 Noble Gases (RM-057) 0.05 Tritium 0.05 Contributing Pathways:

a) Condenser Off Gas 0.10 3. Laboratory and Radioactive Waste Building Exhaust Total: 0.10 Stack l<J Noble Gases (RM-043) 0.05 Iodine/Particulate 0.05 Contributing Pathways:

a) Laboratory and Radioactive Waste Building Exhaust Stack 0.10 Airborne Release Total 1.00 NOTE

  • The Fort Calhoun Station is capable of performing simultaneous liquid releases.
  • I I The factors below may be adjusted to meet release requirements provided that the sum of the Unrestricted Area Fraction Sum for all liquid releases remains less than or eaual to 1.0. B. Allocation Factors for Simultaneous Liquid Releases 1. Steam Generator Releases (RM-054A/054B)

Total: 0.30 Contributing Pathways:

a) Alpha Steam Generator (RM-054A) 0.15 b) Bravo Steam Generator (RM-054B) 0.15 2. l<5 Waste Liquid Releases (RM-055) 0.70 Liquid Release Total 1.00 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Figure 1 -Exclusion and Site Boundary Map TO BLAIR I ~* -----;;~------" doNTRowm .AREA. I I I I " I I I I \ ' ' UNRESTICTED~

AREA BOUNDARY ', ' CD LIQUID EFFLUENTS DISCHAR<1E AIRBORNE EFFLUENT$

DI$dHARGE SdALE IN MILES " 1 r EXCLUSION AND SITE BOUNDARY MAP Page 84 of 134 Revision 27 N TO OMAHA CH-ODCM-0001 Reference.

Use Off-Site Dose Calculation Manual (ODCM) Figure 2 -Liquid Radioactive Discharge Pathways HOTEL TANKS MONITOR TANKS S/G A SLOWDOWN S/G B SLOWDOWN CIRCULATING WATER WARM WATER RECIRCULATION (D RM-054A (V RM-0548 @ RM-055 Page 85 of 134 *Revision 27 RAW WATER LIQUID RADIOACTIVE DISCHARGE PATHWAYS CH-ODCM-0001 Reference Use Page 86 of 134 Revision 27 Off-Site Dose Calculation Manual {ODCM) Figure 3 -Liquid Radioactive Waste Disposal System AUXILIARY SYSTEMS BEaCIDB CIJOLe~I WASTE l:Ul!EL ~aSJE PROCESS WASTE CVCS BlDOdaf"f Spent. Fciganat-ant Tanks 553(11 Gal. Floor DN1Ln5 Sump Flow, a D 0 D 11 EQuipment Dl"alans RC Loop DreJn=; ' ODO w .. );::;la, Hold"P Tanks

  • 45,800 GDl. DamJnel'ah.zer v-..l* .--3fZI Cu. Ft.. Lau-dry WDlri.o Shover ll-a:in1 + DD Haw! Tank5 1200 cw. '----s--1~

00000 Cll;;aal \ F'Llt.ar 6~ Cu, Ft. , f ( cpt,Jcnal>

1 DD toi:o1. t Ovi:,rboard H1111adir C To Fbver) LIQUID RADIOACTIVE WASTE DISPOSAL SYSTEM Figure 4 -Airborne Effluent Discharge Pathways CH-ODCM-0001 Reference Use Page 87 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) RM 043 Noble Ge.s Monitor, e.nd Iodine & ?artioulate Sampler Labo!'atory LABO~r:'O~Y AND RA:JIOAC':'IVE WASTE ?ROC::i'SSING 3UILD:NG RM 057 Nob:e Gas Monitor RM . 062,052 Noble Gas Monitor :adine & Particulate Sam:9ler AUX:LIA3Y 3UILD:NG-ElXEAUS':'

S':'AC3: COND~NS~~

OF~GAS Co::ic.eneer Auxiliary 3uilding Ven tile.ti on Contamtnent Building Ventilation AI3BORNEJ 3:~FLU:iNT DISCHARGE

?ATEWAYS CH-'ODCM-0001 Reference Use Off-Site Dose Calculation.

Manual_ {ODCM) Figure 5 -Airborne Radioactive Waste Disposal System J3.d. To Root Vent Condenser To.. AtmPJlphere Condenser Va.ouum "'"""'~ Pumps Charcoal Ab,iorber Pag-e 88 of 134 Revision 27 Auxiliary Bun~ Ventilation

'3tacl5: 122,500 oFM: Blow:down Fla$h Taiilc Ga$ Holdup Ta.nkr,i (4) 400 CuFt (each) ....... ~9 J3CFM w,.,:,.a..:.==

HEPA Filter WASTE OAS AND CONDENSER OFF-GAS SYSTEMS dontfiinmelit N' Ol'II18Uy .dlo$ed dc:>Oliiig find Internal Recirculti.t.ion

$Yfiltem-HEPA Charcoal Filters HEPA Filter Roll Filterl!'I Purge Inlet ~50,000 ~CFM CONTAINMENT BUILDINC VENTILATION CONTROL Charc.l Fuel' Handling Area,i afety Injection Area11 Other Area$ Filters AIRBORNE RADIOACTIVE WASTE DISPOSAL SYSTEM 2.0 EFFLUENT CONCENTRATIONS dround CH-ODCM..;0001 Reference Use Page 89 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 2.1 Liquid Effluent Concentrations i 2.1.1 The concentration of r:adioactive material in liquid effluents (after dilution in the Circulating Water System) will be limited to the concentrations as specified in 10 CFR Part 20, Appendix B, Table 2, Column 2. For batch releases (Monitor and Hotel Waste Tanks and Steam Generators) and'for continuous releases (Steam Generator Blowdown),the analyses will be performed in accordance with Part I, Table 4.1, of the Off-Site Dose Calculation Manual, a-nd the concentration of each radionuclide at site discharge will be calculated, based on the following equation:

aif A---*-t*-F+f .n L Ai and --* -S1 wee* i=1 l Radionuclide conc_entration at site discharge:

Where: Ai = concentration at site discharge for radionuclide (I), in µCi/ml. a = concentration of radionuclide (I) in the undiluted effluent, in µCi/ml. f = undiluted effluent flowrate, in gpm. F = total diluted effluent flowrate in gpm. weci = water effluent concentration limit for radionuclide (I) per 10 CFR Part 20, Appendix*s, Table 2, Column 2. NOTE In addition to the above defined method, Notes 1 throu~h 4 of 10 CFR Part 20, Aooendix B, will also be applicable.

i 2.2 Airborne Effluent Concentrations 2.2.1 The concentration at the unrestricted area boundary, due to airborne effluent releases, will be limited to *1ess than Appendix B, Table 2, Column 1, values. Radiation monitor alarm setpoints are established to ensure that these release limits are not exceeded.

In the event an airborne effluent release from the station result in an alarm setpoint being exceeded, an evaluation of the unrestricted area boundary concentration resulting from the release Will be performed:

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 90 of 134 Revision 27 2.2.2 To determine the concentration and air effluent concentration (aec) fraction summation at the unrestricted area boundary, the following equations will be used: n A* and LEC~-S 1 i=l l Where: Ai = Concentration of radionuclide (I) at the unrestricted area boundary Ko = Constant of unit conversion.

(1.0E-6 m3/cc) ECLi = Effluent concentration limit (10 CFR Part 20, Appendix B, Table 2, Column 1 value for radioliuclide(I))

Q1 = The release rate of radionuclide (I) in airborne effluents from all vent releases (in µCi/sec.) (x/Q) = Annual Average Dispersion Factor at the Unrestricted Area Boundary from Part II, Table 4, of the Off-Site Dose Calculation Manual. 2.2.3 As appropriate, simultaneous releases from the Auxiliary Building Ventilation Stack, Laboratory and Radwaste Building Stack and condenser off gas will be considered in evaluating compliance with the release rate limits of 10 CFR Part 20. Monitor indications (readings) may be averaged over a time period not to exceed 15 minutes when determining noble gas release rate based on correlation of the monitor reading and monitor sensitivity.

Historical annual average dispersion parameters, as presented in 'Table 4, may be used for evaluating the airborne effluent dose rate. 2.2.4 For administrative purposes, more conservative alarm setpoints than those as prescribed above may be imposed. However, conditions exceeding those more limiting alarm setpoints do not necessarily indicate radioactive material release rates exceeding 1 O CFR Part 20 limits. Provided actual releases do not result in radiation monitor indications exceeding alarm setpoint values based upon the above criteria, no further analyses are required for demonstrating compliance with 10 CFR Part 20. 3.0 RADIOACTIVE EFFLUENT DOSE CALCULATIONS

3.1 Liquid

Effluent Dose Calculations CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 91 of 134 Revision 27 3.1.1 Three pathways for human exposure to liquid releases from FCS to the Missouri River exists: 1) fish, 2) drinking water, and 3) Shoreline deposition.

Fish are considered to be taken from the vicinity of the plant discharge.

The drinking water for Omaha is located 19 miles downstream from FCS. The dilution factors for these pathways are derived from the Revised

  • Environmental Report for FCS, (1974), (page 4-2e c;1nd 4-31'). This report *states that during Low-Low river conditions, the concentration at Omaha's water intake will be ::,14% of the concentration at discharge from FCS and will average 3%. This equates to a dilution factor of 7.14, which is used to calculate the maximum dose to an individual from liquid pathways and a dilution factor of 33.33, for calculating the average dose. All pathways combine to give the dose to an individual in unrestricted areas. 3.1.2 10 CFR Part 50, Appendix I restricts the dose to individuals in the unrestricted areas from radioactive materials in liquid effluents from the Fort Calhoun Station to th.e following limits:
  • during any calendar quarter s 1.5 mrem to total body s 5.0 mrem to any organ and
  • during any calendar year s 3.0 mrem to total body s 10.0 mrem to any organ The following calculational methods shall be use.d for determining the dose or dose commitment from liquid effluents.

CH-ODCM-0001 Reference Use Page 92 of 134 Revision 27 Off,.Site Dose Calculation Manual (ODCM) 3.1.3 Doses from Liquid Effluent Pathways A. Potable Water Where: Rapj = is the total annual dose to organ(j) of individuals of age group (a) from all of the radionuclides (I) in pathway (p), in mrem/yr. Uap is a usage factor that specifies the intake rate* for an individual of age group (a) associated with pathway (p), in Vyr. (Table 6) Mp = is the mbcing ratio (reciprocal of the dilution factor) at the F = Oi = Daipi = A., = tp = 1100 = point of withd.rawal of drinking water, dimensionless.

{Table 17) is the flow rate of the liquid effluent, in ft 3/ sec. is the annual release rate of radio.nuclide (I), in Ci/yr. is the do:se factor*specific to a given age gro.up (a), radionuclide (1), pathway (p), and organ 0) which can be used to calculate the radiation dose from an intake of a radionuclide, in mrem/pCJ. (Tables. 13,.16) is the radiologi~I decay constant of radionuclide (I), in hr 1* is the average transit time required for radionuclides to reach the point of exposure.

For internal dose, tp is the total time elapsed between release of the radionuclides and ingestion of water, in hours. (Table 17) Constant (pdi yr* ft 3/Ci

  • sec
  • L) . I CH-ODCM-0001 Reference Use Page 93 of 134 . Revision 27 Off-'Site Dose Calculation Manual (ODCM) 3.1.3 (continued)

B. Aquatic Foods Where: Rapj = is the total annual dose to 'Organ m of individuals of age group (a) from all of the radionuclides (I) in pathway (p ), in mrem/yr.

  • Uap = is a usage factor that specifies the intake rate for an .individual of age. group (a)associated with pathway (p), in kg/yr. (Table 6) Mp = is the mixing ratio (reciprocal of the* dilution factor) at the' point of harvel:it of ~q1,1atic food, dimensionless. (Table 17) F -is the flow rate of the liquid effluent, in ft 3/sec. Oi = is the annual release rate of radionuclide (I), in Ci/yr. Bip = is-the_ equilibrium bioaccum.ulation factor for radionuclide (I) in pathway (p) expressed as the ratio of the concentration in biota (in pCi/kg) to the radionuclide concentration in water (in pCi/liter);

in (pCi/kg)l(pOi/liter). (Table 3) .Da1pj = is the dose factor specific to a giv~n age group (a), radionuclide (I), pathway {p), and organ 0), Which can be used to calculate the radiation dose .from an intake of a radionuclide; in mrem/pCi. (Tables 13-16) J...1 = is the radiological decay constant of radionuclide (I), in hr1. tp = is the average transit. time required for radionuclides to reach the point of exposure.

For internal dose, *tp. is the total time elapsed between release of the radionuclides and ingestion of fopd, ih h.ours*. (Table 17) 1100 = Constant (pCi

  • yr
  • ft: 3/Ci
  • sec
  • L)

CH-ODCM-0001 Reference Use Page 94 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 3.1.3 (continued)

C. Shoreline Deposits Where: RapJ = is the total annual dose to organ 0) of individuals of age group (a) from all of the radionuclides (I). in pathway (p), in mrem/yr. Uap = is a usage factor that specifies the exposure time for an Mp = w = F = Oi = Tip = DaipJ = Ai = tp = lb = 110,000= individual of age group (a) associated with pathway*(p), in hr/yr. (Table 6) is the mixing ratio (reciprocal of the dilution factor) at the point of exposure, dimensionless. (Table 17) is the shore-width factor, dimensionless

.. (Table 17) is the flow rate of the liquid effluent, in ft 3/sec. is the annual release rate of radionuclide

{I), in Ci/yr. is the radioactive half life of radionuclide (I), in days. is the dose factor specific radionuclide (I) which can be used to calculate the radiation dose from exposure to a given concentration of a radionuclide in sediment, expressed as a ratio of the dose rate (in mrem/hr) and the real radionuclide concentration (in pCi/m 2). (Table 8) is the radiological decay constant of radionuclide (I), in hr1. .is the average transit time required for radionuclides to reach the point of exposure, in hours. (Table 17) is the period of time for which sediment or soil is exposed to the contaminated water, in hours. (Table 17) Constant [(100

  • pCi
  • yr** ft3)/(Ci *sec* L)]

CH-ODCM-0001_

Reference Use Page 95 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 3.2 Airborne Effluent Dose Calculations

3.2.1 Noble

Gas 10 CFR Part 50, Appendix I, restricts the dose to individuals in the unrestricted areas from noble gases in airborne effluents from the fort Calhoun Station to the fQllowing limits:

  • During any calendar quarter s 5 mrad-gamma air dose s 1 0 mrad-beta air dose and
  • Puring any calendar year s 10 mrad-gamma air dose :s; 20 mrad-beta air dose The following general equations shall be used to calculate the gamma-air and beta-air doses: ,A. Doses from Noble Gases 1. Annual Gamma/Beta Air Dose from All Other Noble Gas Releases n DY (t, O)or DP (r, 6) :-3.17 x 10 4 I Qi[x/QJD (r, B)(DFT or DFf) Where: DFiv or b.Fif3 = [x/Q]D(r,0)

= 3.17x10 4 = i=l are the gamma and beta air dose factors for a uniform semi-infinite cloud of radionuclide (1), in rnrad-m 3/pCi-yr. (Table 2) are the annual gamma and beta air doses at distance r, in the sector at angle e, from the discharge point, in mrad/yr. is the annual release rate of radionuclide (I), in Ci/yr. is the annual average gaseous dispersion factor at distance r, in the sector at angle a, in sec/m 3* (Table 4)

  • is the number of pCi per Ci divided by the number of seconqs per year.

CH-ODCM-0001 Reference Use Page 96 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 3.2.1A (continued)

2. Annual Total Body Dose from All Other Noble Gas .Releases Where: DFB1 D'L(r,8) x,(r,8) Sf n D~ (r, e) = Sr L Xi (r, e)DFBi i=1 = is the total body dose factor for a semi-infinite cloud of the radionuclide (I), which includes the attenuation of 5 g/cm 2 of tissue, in mrem-m 3/pCi-yr. (Table 2) = i~ the annual total body dose due to immersion in a semi-,infinite cloud at distance r, in the sector at angle 8, in mrem/yr. = is the annual average ground-level concentration of radionuclide (I) at distance r, in the sector at angle 8, in pCi/m 3* (Table 4) = Shielding Factor {Table 17) 3. Annual Skin Dose from All Other Noble Gas Releases n n D~ (r, 8) = 1.11 Sr 'L xi (r, O)DF[ + L x, (r, B)DFSi Where: D!(r,8) DFS1 1.11 i=1 i=1 = is the annual skin dose due to immersion in a semi-infinite cloud at distance r, in the sector at angle 9, in mrem/yr. = is the beta skin dose factor for a semiinfinite cloud of radionuclide (I), in mrem-m 3/pCi-:yr. (Table 2) = is the average ratio of tissue to air energy absorption coefficients.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 3.2.2 Radioiodine, Tritium, and Particulates Page 97 of 134 Revision 27 10 CFR Part 50, Appendix I, restricts the dose to individuals in the unrestricted areas from radioactive materials in gaseous airborne from the Fort Calhoun Station to:

  • During any calendar quarter s 7 .5 mrem to any organ and
  • During any calendar year s 15 mrem to any organ The dose to an individual from radioiodines, radioactive materials in particulate form, and radionuclides other than noble gases with half-lives greater than 8 days in airborne effluents ieleased to unrestricted areas should be determined by the following expressions:

Radioiodine, Tritium, and Particulates (continued)

CH-ODCM-0001 Reference Use Page 98 of 134 Revision 27 Qff;.Site Dose Calculation Manual (ODCM) '3.2.2 (continued}

Iii NOTE

  • I In all cases, for releases of tritium, use the dispersion I parameter for inhalation lv/Q). A. Annual Organ Dose from External Irradiation from Radioactivity Deposited on the Ground Plane The ground plane concentration of radionu.clide (I) at distance r, in the sector at angle 9, with respect to the release point, may be determined by: [1 Ox10 12][o* (r B)*Q*] ct (r, 8) =
  • ili i
  • i [1 -exp(-ilitb)]

Where: oi(r,8) Ai 1.ox10 12 = is the ground plane concentration of the radionuclide (I) at distance r, in the sector at angle 9, from the release point, iii pCi/m2. = is the annual release rate of radionuclide (I) to the atmosphere, in Ci/yr. = is the time period over which the accumulation is evaluated, which is assumed to be 20 years (mid-point of plant oper~ting life). (Table 17) = is the annual average relative deposition of radionuclide (I) at distance r, in the sector at angle 8, considering depletion of the plume by deposition during transport, in m-2. Table 4 * = is the radiological decay constant for radionuclide (1), in yr-1. = is th~ number of pCi/Ci CH-ODCM-0001 Reference Use Page 99 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 3.2.2A (continued)

The annual organ dose is then calculated using the following equation:

n DP (r, 8) = 8760 s 1 L ciG (r, B)DFGii Where: C'f(r,8) DFGii D'f(r,8) St 8760 i.=1 = is the ground plane concentration of radionuclide (i) at distance r, in the sector at angle 8, in pCi/m 2* = is the open field ground plane dose conversion factor for organ (j) fr.om radionuclide (i), in mrem-m 2/pCi-hr. {Table 8) = is the annual dose to the organ (j) at dista_nce r, in the sector at angle *a,. in mrem/yr. = is the shielding factor that accounts for the dose reduction due to shielc:jing provided by residential structures during occupancy, dimensionless. (Table 17) = . is the number of hours in a year B. Annual Dose from Inhalation of Ra_dionuclides in Air The annual average airborne concentration of radionuclide (i) at distance r, in the sector at angle e, with respect to the release point, may be determined as:* Xi (r, 8) = 3 . .17 x.10 4 Qi [x/Q]D (r, fl) Where: Ci (x/Q]D {r,8) 3.17x10 4 3.2.28 (continued)

= is the annual release rate of radionuclide (i) to the atmosphere, in Ci/yr. = is the annual average ground-level concentration of radionuclide (i) in air at distance r, in the seGtor at angle 0, in pCi/m 3. . u = is the annual average atmosphere dispersion factor, in sec/m 3 (see Reg Guide 1.111 ). Thi.s inc.ludes depletion (for radioiodines and particulates) and radiological decay of the plume. (Table 4) = is the number of pCi/Ci divided by the number of sec/yr.

CH-ODCM-0001 Reference Use Page 100 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) The annual dose associated with inhalation of all radionuclides to organ (j) of an individual in age group (a), is then: n D/a (r, 8) = Ra L xi (r, 8)D F Aija Where: D'ia(r,8)

Ra DFAia i=1 = is the annual dose to organ 0) of an individual in the age group (a) at distance r, in the sector at angle 8, due to inhalation, in mrem/yr. = is the annual air intake for individuals in the age group (a), in m 3/yr. (Table 6) = is the inhalation dose factor for radionuclide (i), organ 0), and age group (a), in mrem/pCi. (Tables 9-12) 3.2.3 Concentrations of Radionuclides in Foods and Vegetation from Atmospheric Releases A. Parameters for Calculating Concentrations in Forage, Produce, and Leafy Vegetables, excluding Tritium Where: CY(r,9) di (r,8) = is the concentration of radionuclide (i) in and on vegetation at distance r, in the sector at angle 8, in pCi/kg. = is the deposition rate of radionuclide (i) at distance r, in the sector at angle 8, in pCi/m 2 hr.

CH-ODCM-0001 Reference Use Page 101 of 134 Revision 27 Off-Site Dose Calculation.

Manual (ODCM) 3.2.3A (continued)

The deposition rate from the plume is defined by (Reg. Guide 1.109, Rev. 1, Page 1.109-26, Equa. C-6): di (r, 6) = 1.1 x 10 8 oi (r, fJ)Qi Where: d1(r,8) B1(r,8) 1.1x10 8 = is the deposition rate of radionuclide (i). = is the relative deposition of radionuclide (i), considering depletion and decay, in m*2 (see Reg Guide 1.111 ). (Table 4) = is the number of pCi/Ci (10 12) divided by the number of hours per year (8760). = is the annual release rate of radionuclide (i) to the atmosphere, In Ci/yr.

CH-ODCM-0001 Reference Use Page 102 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 3,2.3 (continued)

B. For radioiodines, the model considers only the elemental fraction of the effluent:

Where: di (r, 8) 3.3x 10 7 oi (r, 8) Qi r i,.Ei te Yv Biv Ai p = The deposition rate of radioippine (i). = The number of pCi/Ci (1012) divided by the number of hours per year (8180), then multiplied by the amount of radioiodine emissions considered to be elemental (0.5). =

  • The relative deposition
of radioiodine (i), considering depletion and decay, in m-2. (Table 4) = The total (elementr:il and nonelemental) radioiodine (I) emission rate: = is the fraction .of deposited activity retained on crops, dimensionless.

{Table 17) = is the effective removal rate constant for radionuclide (i) from crops, in hr-1. *AEi = Ai + Aw Aw= 0.0021/hr. (Table 17) = i$ the time period that crops are exposed to contamination during the growing season, in hours. (Table 17) * = is the agricultural prod.uctivity (yield) in kg (wet Weight)/in2. (Table 17) = is the concentration factor for uptake of radionuclide (i) from soil by edible parts of crops, in pCi/ kg (wet weight) per pCi/kg dry soil. (Table 5)' * * = is the radiological decay constant of radionuclide (I), in hr-1 = is the period of time for which sediment or soil is exposed to the contaminated water; .in hours (mid,.point .of plant life). (Table 17) = is the effective "surface density" for soil, in kg (dry soil)/rn2. (Table 17} = is the holdup time that represents the time interval between harvest and consumption of the food, in hours. {Table 17) Different values for the parameters te, Yv, a.nd th, may be used to allow the LJse of'the Eql,lation for different purposes:.

estimating concentrations in produce consumed by man; in leafy v~getables consumed py man; in forage consumed directly as pasture grass by dairy cows, beef cattle, or goats; and in forage consumed as stored feed by dairy cows, beef cattle or goats. See Table 17, CH-ODCM-0001 Reference Use Page 103 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 3.2.3 (continued)

C. Parameters for Calculating the Concentration of Radionuclide (i) in the Animal's Feed (Milk Cow, Beef Cow, and Goat) er (r, (}) = {p Is er (r, 8) + (1-tr,)ct (r, 8) + {p (1-fs)Cl (r, 8) Where: CY (r,9) CPi(r,8) C~r,0) fs = is the concentration of radionuclide (i) in the animal's feed, in pCi/kg. = is the concentration of radionuclide (i) on pasture grass (calculated using Equation 3.2.3C with th=O), in pCi/kg. = is the concentration of radionuclide (i) in stored feeds (calculated using Equation 3.2.3C with th=90 days), in pCi/kg. = is the fraction of the year that animals graze on pasture. (Table 17) = is the fraction of daily feed that is pasture grass while the animal grazes on pasture. (Table 17) 3.2.4 Parameters for Calculating Radionuclide Concentration in Cow and Goat Milk Where: C'i (r,8) = is the concentration of radionuclide (i) in milk, in pCi/liter.

CY (r,8) = is the concentration of radionuclide (i) in the animal's feed, in pCi/kg. Fm = is the average fraction of the animal's daily intake of radionuclide (i) which appears in each liter of milk, in days/liter. (Table 5) OF = is the amount of feed consumed by the animal per day, in kg/day. (Table 7) tt = is the average transport time of the radionuclide (i) from the feed to the milk and to the receptor (a value of 2 days is assumed). (Table 17) Ai = is the radiological decay constant of radionuclide (i), in days*1.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 104 of 134 Revisiqn 27 3.2.5 Parameters for Calculating Radionuclide Concentration in Cow Meat, excluding Tritium C{ (r, 8) = F 1 er (r, 8)Qp exp(-ili t 1) Where: CFi (r;0} = is the concentration of radionuclide (i) in meat, in pCi/liter.

Ft = is the average fraction of the animal's daily intake of radionuclide (i) which appears in each kilogram of flesh, iii days/kilogram. (Table 5) ts = is the average time from slaughter to consumption. (Table 17) 3.2.6 Parameters for Calculating Tritium Concentrations in Vegetation The concentration of tritium in vegetation is calculated from its concentration in the air surrounding the vegetation.

c: (r, 8) = 3.17 x 10 7 Qr [x/Q](r, 9~0*75)(0.5) = 1.2 x 10 7 Qr [x/Qt(r, 9) Where: C'f(r, 8) = is the concentration of tritium in vegetation grown at distance r, in the sector at angle 8, in pCi/kg. H = is the absolute humidity of the atmosphere at distance r, in the sector at angle 8, in g/m 3* H=8 gm/kg. Or = is the annual release rate of tritium, in Ci/yr. [x/Q](r,8)

= is the atmospheric dispersion factor, in sec/m 3* (Table 4) 0.5 = is the ratio of tritium concentration in plant water to tritium c.oncentration in atmospheriG water, dimensionless.

0. 75 -is the fraction of total plant mass that is water, dimensionless.

CH-ODCM-0001 Reference Use Page 105 of 134 Revision 27 Off-Site Dose Calculation Manual (ODCM) 3.2.7 Annual Dose from Atmospherically Released Radionuclides in Foods A. The total annual dose to organ 0) of an individual in age group (a) resulting from ingestion of all radionuclides ii") produce, milk, and leafy vegetables is given by: Dfa (r,O) = I DFiija [ur [g er (r, 8) + u: er (r, 8) + u: er (r, 0) + u~ ftCf (r,6)] ;i Where: D~a(r,.9)

= is the annual dose to organ (j) of an individual in age group (a) from dietary intake of atmospherically released radionuclides, in mrem/yr. DFliia = is the dose conversion factor for the ingestion of radionuclide (i), organ {j), and age group (a), in mrem/pCi.

Tables 13-16. U'ii, U~ = are the ingestion rates of produce (non-leafy vegetables, fruits, and grains); milk, meat, and leafy UFa,Ul.a vegetables, respectively for individuals in age group (a). (Table 6) f 9 = Fraction of ingested produce grown in garden of interest (Table 17) f( = Fraction of leafy vegetables grown in garden of interest (Table 17)

CH-ODCM.,0001 Reference Use Page 106 of 134 Revision 27 Off-Site Dose Calculation Manual (ODOM) 3.2.7 (continued)

B. Calculating the Ingested Dose from Leafy and Non.,Leafy (produce)

Vegetation for Radionuclide (i) to Each Organ 0) and Age Group (a) Dfa (r, 8) = DFlja [Uk ft Cf (r, 8) + UK [0 er (r, 8)] Where: D9a(r,0) = is the annual dose from the ingestion of radionuclide (i) to organ (j) of an individual in age group (a) from dietary intake of atmospherically released radionuclides in vegetation, in mrem/yr.

  • DFhia -is the dose conversion factor for the ingestion of radionuclide (i), organ 0), and age group (a), in mrem/pci.

Tables 13-16 Ula,U\a = are the ingestion rates of leafy vegetables and produce (non.,leafy vegetables, fruits, and grains), for individuals in age group (a), in kg/yr. (Table 6) CU = is the concentration of radionuclide (i) in and on leafy vegetation, in pCi/kg. C\l = is the concentration of radionuclide (i) in and on produce, in pCi/kg. C. Calculation Determining the Ingested Dose from Cow Milk for Radionuclide (i), Organ 0), and Age Group (a) Dfa (r, 8) = DFiija [U: er (r, 8)] Where: D9a(r,9) = is the annual dose from the ingestion of radionur;;lide (i), organ 0) of an individual in age group (a) from dietary intake of atmospherically released radionuclides in cow milk, in mrem/yr. DFhJa = is the dose conversion factor for the ingestion of radionuclide (i), organ G), and age group (a), in mrem/pCi. (Tables f3.,16) U~ = is the ingestion rate of cow milk for individuals in age group (a), in ~/yr. (Table 6) Ctlf = is the radionuclide concentration in cow milk, in pCi/kg. Equati.on 3.2.4 CH-ODCM-0001 Reference Use Off .:Site Dose Calculation Manual (OOCM) 3.2.7 (continued)

Page 107 of 134 Revision 27 D. Calculation Determining the Ingested Dose from Meat for Radionuclide (i) to Organ (j) and Age Group (a) Dfa (r, 9) = DFlija [Uf C{ (r, fJ)] Where: D~a(r,0) = is the annual dose from the ingestion of radionuclide (i), organ (j) of an individual in age group (a) from dietary intake of atmospherically released radionuclides in meat, in mremlyr. DFliJa = i_s the dose conversion factor for the ingestion of radionuclide (i), organ (j), and age group (a), in mrem/pCi. (Tables 13-16) U~ = is the ingestion rate of meat for individuals in age group (a), in kg/yr. (Table 6} Clf = is the radionuclide (i) concentration in meat, in pCi/kg. 3.2.8 Annual Dose from Carbon 14 A. This is a calculated value ba$ed on power generation and days of operation.

Critical organ doses from C-14 were calculated using a ratio of 15% as CO2. Ttiis ratio was determined during. an NRC in-plantsource term study conducted at the Fort Calhoun Station between 1976 and 1977, NUREG/CR-0140.

-_ _J CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) 4.0 LOWER LIMIT OF DETECTION (LLD) Page 108 of 134 Revision 27 4.1 The lower limit of detection (LLD) for liquid and airborne effluent discharges and environmental samples referenced in Part I, Tables 4.1, 4.2 and 5.3, ofthe Off-Site Dose Calculation Manual, is defined as the smallest concentration of radioactive material in a sample that will yield a net count, above system background, that will be detected with 95 percent probability with only 5 percent probability of falsely concluding that a blank observation represents a "real" signal. 4.2 For a particular measurement system, which may include radiochemical separation:

4.66

  • Sb LLD= . E
  • V
  • D
  • Y
  • exp(-..1.dt)

Where: LLD = the lower limit of detection as defined above, in either picoCuries or microCuries, per unit mass or volume as a function of the value of D Sb. = the standard deviation of the background counting rate or of the counting rate of a blank sample, as appropriate, as counts per minute E = the counting efficiency, as counts per disintegration V = the sample size in units of mass or volume D = 2.22E+06 of disintegrations per minute per microCurie or 2.22 disintegrations per minute per picoCurie Y = the fractional radiochemical yield, when applicable A = the radioactive decay constant for the particular radionuclide at = the elapsed time between the midpoint of sample collection and time of counting Appropriate values of E, V, Y, and at should be used in the calculation.

4.3 It should be recognized that the LLD is defined as an A Priori limit representing the capability.

of a measurement system and not as a limit for a particular measurement.

4.4 LLD verifications will be performed on a periodic bas.is~ This deten:nination is to ensure that the counting system is able to detect levels .of radiation at the LLD values for the specific type of analysis required.

They will be performed with a blank (non-radioactive) sample in the same counting geometry as the actual sample.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 109 of 134 Revision 27 Table 2-Dose Factors for Exposure to a Semi-Infinite Cloud of Noble Gases Nuclide P-Air 1 (DP1) (3-Skin 2 (DFSi) y-Air 1 (DfVi) y-Body 2 (DFB1) . Kr-83m 2.88E-04 -1,9.3E-05 7.56E-08 Kr-85m 1.97E-03 1..46E-03 1.23E-03 1.17E-03 Kr-85 1.95E-03 1.34E-03 1.72E~05 1.61E-05 Kr-87 1.03E-02 9.73E-03 6.17E-03 5i926~03 Kr-88 2.936-03 .2.37E-03 1.52E-02 1.47E-02 Kr-89 1.06E-02 1.01E-02 1.731::-02 1.66E-02 Kr-90 7.83E-03 7.29E-03 1.63E-02 1 .. 56E-02 Xe-131m 1.11E-03 4.67E-04 1.56E-04 9;15E-05 Xe-133m 1.48E-03 9.94E-04 3.27E-04 2.51E-04 . Xe-133 1.0SE-03.

3.06E-04 3.53E-04 2.94E-04 Xe-135n, 7.39E-04 7.11E-04 3.36E-03 3 .. t2E-03 Xe-135 2.46E-03 1.86E-03 1.92E.;03 1.81E-03 Xe-137 1.27E-02 1.22E-02 1.51E-0.3 1.426-03 Xe-138 4.75E-03 4.13E-03 9.21E-03 8.83E-03 Ar-41 3.28E-03 2.69!=-03 9.30E-03 8.846-03 mrad-m 3 1. . . pCi -yr mrem-m 3 2 .. ----pCi-r 3. 2.HBE -04 = '2.8.8 x 10-4 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) *Element H C Na p. Cr Mn Fe Co Ni Cu Zn Br Rb Sr y Zr Nb Mo Tc RLi Rh Te I Cs Ba La Ce Pr Nd w Np Table 3 -Bioaccumulation Factors .(pCi/kg per pCi/liter)

FRESHWATER Fish 9.0E-01 4.6E+03 1.0E+02 1.0E+OS 2.0E+02 4.0E+02 1.0E+02 5.0E+01 1.0E+02 5.0E+01 2.0E+03 4.2E+02* 2.0E+03 3.0E+01 2.5E+01 3,3E+OO 3.0E+04 1.0E+01 1.5E+01 1.0E+01 t.OE+01 4.0E+02 1.5E+01 2,0E+03 4 .. 0E+OO 2.5E+01 t.OE+OO 2.5E+.01 2.5E+01 1.2E+03 1.0E+01 Page 110 of 134 Revision 27 Invertebrate 9.0E-01

  • 9.1E+03 2.0E+02 2.0E+04 2.0E+03 9.0E+04 3.2E+03 2.0E+02 1.0E+02 4.0E+02 1.0E+04 3.3E+02 1.0E+03 1.0E+02 1'.0E+03 6.7E+OO 1.0E+02 1.0E+0.1 5.0E+OO 3.0E+Q2 3.0E+02 6.1E+03 5.0E+OO 1.0E+03 2.0E+02 1.0E+03 1.0E+03 1.0E+03 1;0E+03 1.0E+01 4.0E+02 CH-ODCM-0001 Reference Use Off-Site Dose Calcul~tion Manual (ODCM) Page 111 of 134 Revision 27 Table 4 -Highest Potential Exposure Pathways for .Estimating Dose NOTE
  • I. The Annual Radiological Effluent Report uses the liighest calculated VaJue from real time meteorological data .obtained for the entire year for calculating dose. I
  • I Distance XJQ.-' 0/Q" Exp*osure Location 8 Direction 8 from {xia {r,8)} {6 (r,8)} Pathway Containment (sec/m 3) (m-2) (miles) 8 birect .Exposure Site SSE 0.60 1.30E~05 N/A Boundary Inhalation Site SSE 0.60 i.30E-05 NiA Boundary Ingestion Residence SSE 0.60 NIA 7.6E-08 A. These* values are us.e.d for calculating quarterly dose estimates during the annual reporting period and are based on a 2 year average, updated only upon a +10% change from the previous value. At least ten percent (10%) should be added to these values for dose estimates during the reporting periocis.

B. The location is subjecHo change based .on ,an annual evalu_ation and is utilized e>nly for ingestion exposure pathway dose estimates.

This location may differ frqm the highest ingestion exposure pathway for offsite air monitoring locations as determined by the Land Use Survey performed biennially in accordance with Part 1, Section 7 .3.2, of the Off-Site Dose Calculation Manual.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Table 5 -Stable Element Transfer Data Element B1v Fm (cow) Veg./Soil Milk {d/1) H 4.BE+OO 1.0E-02 C 5.5E+OO 1.26-02 Na 5.2E-02 4.0E-02 p 1.1E+OO 2.SE-02 Cr 2.5E-04 2.2E-03 Mn 2.9E-02 2.5E-04 Fe 6.6E-04 1.2E-03 Co 9.4E-03 1.0E-03 Ni 1.9E-02 6.7E-03 Cu 1.2E-01 1.4E-02 Zn 4.0E-01 3.9E-02 Rb 1.3E-01 3.0E-02 Sr 1.7E-02 8.0E-04 y 2.6E-03 1.0E-05 Zr 1.7E-04 5.0E-06 Nb 9.4E-03 2.5E-03 Mo 1.2E-01 7.5E-03 Tc 2.sE:.01 .2.SE-02 Ru 5.0E-02 1.0E-06 Rh 1,3E+1 1.0E-02 Ag 1.5E-01 5.0E-02 Te 1.3E+OO 1.01= .. 03 I 2.0E-02 6.0E-03 Cs 1.0E-02 1.2E-02 Ba 5.0E-03 4.0E-04 La 2.SE-03 5.0E-06 Ce 2.5E-03 1.0E-04 Pr 2.5E-03 5.0E-06 Nd 2.4E-03 5.0E-06 w 1.BE-02 5.0E-04 Np 2.5E-03 5.0E-06 F, Page 112 of 134

  • Revision 27 Meat (d/kg) 1.2E-02 3.1E-02 3.0E-02 4.6E-02 2.4.E-03 8.0E-04 4.0E-02 1.3E-02 5.3E-02 8.0E-03 3.0E-02 3.1E-02 6.0E-04 4.6E-03 3.4E-02 2.BE-01: 8.0E-03 4.0E-01 4.0E-01 1.5E-03 1.7E-02 7.7E-02 2.9E-03 4.0E-03 3.2e:.03 2.0E-04 1.2E-03 4.7E:.Q3 3.3E-03 1.3E~03 2.0E-04 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 113 of 134 Revision 27 Table 6-Recommended Values for Uap to Be Used for the Maximum
  • Exposed Individual in Lieu of Site Specific Data Pathway Infant Chiici Teen Adult Fruits, vegetables, & grain (kg/yr) ---520 630 620 Leafy vegetables (kg/yr) ---26 42 64 Milk (Nyr) 330 330 400 310. Meat & poultry (kg/yr) --41 65 110 Fish (fresh or salt)(kg/yr)

--6.9 16 21 Other Seafood (kg/yr) ---1.7 3.8 5 Drinking water (~/yr) 330 510 510 730 Shoreline recreation (hr/yr) ---14 67 12 Inhalation (m 3/yr) 1400 3700 8000 8000 Table. 7 -Animal Consumption Rates Animal QF Feed or Forage [Kg/day (wet weigh)] QAW Water (etday) Milk Cow 50 60 Beef Cattle 50 50 Goats 6 8 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 114 of 134 Revision 27 Table 8 -External Dose Factors for Standing on Contaminated Ground (mrem/hr per pCi/m2) Element Total Body Skin H-3 -----C-14 ---Na-24 2.SOE-08 2.90E-08 P-32 ------Cr-51 2.20E-10 2.60E-10 Mn-54 5.80E-09 6.80E-09 Mn-56 1.10E-08 1.30E-08 Fe-55 ---Fe-59 8.00E-09 9.40E-09 Co-58 7.00E-09 8.20E-09 Co-60 1.70E-08 2.00E-08 Ni-63 ------Nr-65 3.70E-09 4.30E-09 Cu-64 1.50E-09 1.70E-09 Zn-65 4.00E-09 4.SOE-09 Zn-69 ----Br-83 6.40E-11 9.30E-11 Br-84 1.20E-08 1.40E-08 Br-85 ---Rb-86 6.30E-10 7.20E-10 Rb-88 3.SOE-09 4.00E-09 Rb-89 1.SOE-08 1.BOE-08 Sr-89 5.60E-13 6.SOE-13 Sr-91 7.10E-09 8.30E-09 Sr-92 9.00E-09 1.00E-08 Y-90 2.20E-12 2.60E-12 Y-91M 3.BOE-09 4.40E-09 Y-91 2.40E-11 2.70E-11 Y-92 1.SOE-09 1.90E-09 Y-93 5.70E-10 7.80E-10 Zr-95 5.00E-09 5.BOE-09 Zr-97 5.SOE-09 6.40E-09 Nb-95 5.10E-09 6.00E-09 Mo-99 1.SOE-09 2.20E-09 Tc-99M 9.60E-10 1.10E-09 Tc-101 2.70E-09 3.00E-09 Ru-103 3.60E-09 4.20E-09 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 115 of 134 Revision 27 Table 8 -External Dose Factors for Standing on Contaminated Ground (mrem/hr per pCi/m 2) Element Tc;,tal Body .Skin Ru-105 4.SOE-09 5.10E-09 Ru:.106 1.SOE-09 1.80E-09 Ag-110M 1.80E-08 2.10E-08 Te-125M 3.SOE-11 4.80E-11 Te-127M 1.10E-12 1.30E-12 Te-127 1.00E-11 1.10E~11 Te-129M 7.70E-10 9.00E-10 Te-129 7.10E-10 8.40E-10 Te-131M 8.40E-09 9.90E-09 Te-131 2.20E-09 2.90E-06 Te-132 1.70E-09 2.00E-09 1-130 1.40E-08 1.70E-08 1-131 2.BOE-09 3.40E-09 1-132 1.70E-08 2.00E-08 1-133' 3 .. 70E-09 4.50E-09 1-134 1.60E-08 1.90E-08 1-135 1.20E-08 1.40E-08 Cs-134 1.20E-08 1.40E-08 Cs-136 1.50E-08 1.70E-08 Cs,-137 4.20E-09 4.90E-09 ' Cs-138 2.10E-08 .2.40E-08 Ba-139 2.40E-09 2.70E-09 Ba-140 2.10E,-09 2.40E-09 Ba-141 4.30E-09 4.90E-09 Ba-142 7:90E-09 9.00E-09 La-140 1.SOE-08 1~70E-08 La-142 1.SOE-08 1.80E-08 Ce-'141 5.SOE-10 6.20E-10 Ce-143 2:20E-09 2.SOE-09 Ce-1.44 3,20E-tO 3.70E-10 Pr-143 -----Pr-144 2.00E-10 2.30E-10 Nd'-147 1.0QE,.09 1.20E-09 W-187 3.10E-09 3;60E-09 Np-239 9.SOE-10 1.10E-09 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM} Nuclide Bone H-3 ---C-14 2.27E-06 Na-24 1.28E-06 P-32 1.65E-04 Cr-51 -Mn-54 -Mn-56 --Fe-55 3.07E-06 Fe-59 1.47E-06 Co-58 --Co-60 --Ni-63 5.40E-05 Ni-65 1.92E-10 Cu-64 -Zn-65 4.0SE-06 Zn-69 4.23E-12 Br-83 ---Br-84 ---Br-85 --Rb-86 --Rb-88 -Rb-89 -Sr-89 3.BOE-05 Sr-90 3.59E-03 Sr-91 7.74E-09 Sr-92 8.43E-10 Y-90 2.61E-07 Y-91M 3.26E-11 Y-91 5.78E-05 Y-92 1.29E-09 Y-93 1.18E-08 Zr-95 1.34E-05 Zr-97 1.21E-08 Nb-95 1.76E-06 Mo-99 --Tc-99M 1.29E-13 Tc-101 5.22E-15 Table 9 -Inhalation Dose Factors for Adult (mrem per pCi Inhaled) Liver T.Body Thyroid Kidney 8.98E-08 8.98E-08 8.98E-08 8.98E-08 4.26E-07 4.26E-07 4.26E-07 4.26E-07 1.28E-06 1.28E-06 1.28E-06 1.28E-06 9.64E-06 6.26E-06 ------1.25E-08 7.44E-09 2.85E-09 4:95E-06 7.87E-07 ---1.23E-06 1.55E-10 2.29E-11 --1.63E-10 2.12E-06 4.93E-07 ----3.47E-06 1.32E-06 --1.98E-07 2.59E-07 ------1.44E-06 1.85E-06 -----3.93E-06 1.81 E-06 ----2.62E-11 1.14E-11 -----1.83E-10 7.69E-11 -5.78E-10 1.29E-05 5.82E-06 -8.62E-06 8.14E-12 5.65E-13 -5.27E-12 -~.01E-08 ------3.91E-08 -----1.60E-09 ------1.69E-05 7.37E-06 ----4.84E-08 2.41 E-08 -----3.20E-08 2.12E-08 ----1.09E-06 ----7.21E-05 -----3.13E-10 ----3.64E-11 --------7.01E-09 -----1.27E-12 ------1.55E-06 -------3.77E-11 --------3.26E-10 -----4.30E-06 2.91E-06 ---6.77E-06 2.45E-09 1.13E-09 ---3.71E-09 9.77E-07 5.26E-07 --9.67E-07 1.51E-08 2.87E-09 ---3.64E-08 3.64E-13 4.63E-12 --5.52E-12 7.52E-15 7.38E-14 -1.35E-13 Page 116 of 134 Revision 27 Lung GI-LLI 8.98E-08 8.98E-08 4.26E-07 4.26E-07 1.28E-06 1.28E-06 ---1.0BE-05 1.80E-06 4.15E-07 1.75E-04 9.67E-06 1.18E-06 2.53E-06 9.01E-06 7.54E-07 1.27E-04 2.35E-05 1.16E-04 1.33E-05 7.46E-04 3.56E-05 2.23E-05 1.67E-06 7.00E-07 1.54E-06 8.48E-07 6.12E-06 1.0BE-04 6.68E-06 1.15E-07 2.04E-09 --2.90E-08 --2.05E-13 -----2.08E-06 ---4.18E-19 -1.16E-21 1.75E-04 4.37E-05 1.20E-03 9.02E-05 4.56E-06 2.39E-05 2.0SE-06 5.38E-06 2.12E-05 6.32E-05 2.40E-07 1.66E-10 2.13E-04 4.81E-05 1.96E-06 9.19E-06 6.06E-06 5.27E-05 2.21E-04 1.88E-05 9.84E-06 6.54E-05 6.31E-05 1.30E-05 1.14E-05 3.10E-05 9.55E-08 5.20E-07 4.99E-08 1.36E-21 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone Ru-103 1.91E-07 Ru-105 9.88E-11 Ru-106 8.64E-06 Ag-110M 1.35E-06 Te-125M 4.27E-07 Te-127M 1.58E-06 Te-127 1.75E-10 Te-129M 1.22E-06 Te-129 6.22E-12 Te-1~1M 8.74E-09 Te-131 1.39E-12 Te-132 3.25E-08 1-130 5.72E-07 1-131 3.15E-06 1-132 1.45E-07 1-133 1.0BE-06 1-134 8.05E-08 1-135 3.35E-07 Cs-134 4.66E-05 Cs-136 4.BBE-06 Cs-137 5.98E-05 Cs-138 4.14E-OB Ba-139 1.17E-10 Ba-140 4.BBE-06 Ba-141 1.25E-11 Ba-142 3.29E-12 La-140 4.30E-08 La-142 B.54E-11 Ce-141 2.49E-06 Ce-143 2.33E-08 Ce-144 4.29E-04 Pr-143 1.17E-06 Pr-144 3.76E-12 Nd-147 6.59E-07 W-187 1.06E-09 Np-239 2.87E-08 Table 9 -Inhalation Dose Factors for Adult (mrem per pCi Inhaled) Liver T.Body Thyroid Kidney -8.23E-08 -7.29E-07 --3.89E-11 ---1.27E-10 ---1.09E-06 --1.67E..Q5 1.25E-06 7.43E-07 -2.46E-06 1.98E-07 5.84E-08 1.31E-07 1.55E-06 7.21E-07 1.96E-07 4.11E-07 5.72E-06 8.03E-11 3.87E-11 1.32E-10 6.37E-10 5.84E-07 1.98E-07 4.30E-07 4.57E..Q6 2.99E-12 1.55E-12 4.87E-12 2.34E-11 5.45E-09 3.63E-09 6.BBE-09 3.86E..Q8 7.44E-13 4.49E-13 1.17E-12 5.46E-12 2.69E-08 2.02E-08 2.37E-08 1.82E-07 1.68E-06 6.60E-07 1.42E-04 2.61E-06 4.47E-06 2.5SE-06 1.49E-03 7.66E-06 4.07E-07 1.45E-07 1.43E-05 6.48E-07 1.85E-06 5.65E-07 2.69E-04 3.23E-06 2.16E-07 7.69E-08 3.73E-06 3.44E-07 8.73E-07 3.21E-07 5.f,OE-05 1.39E-06 1.06E-04 9.10E-05 --3.59E-05 1.83E-05 1.3BE-05 --1.07E-05 7.76E-05 5.35E-05 --2.78E-05 7.76E-08 4.0SE-08 ---6.00E-08 8.32E-14 3.42E-12 ---7.78E-14 6.13E-09 3.21E-07 -2.09E-09 9.41E-15 4.20E-13 ---8.75E-15 3.38E-15 2.07E-13 -2.86E-15 2.17E-08 5.73E-09 ------3.BBE-11 9.65E-12 ----1.69E-06 1.91E-07 ---7.83E-07 1.72E-08 1.91E-09 --7.60E..Q9 1.79E-04 2.30E-05 --1.06E-04 4.69E-07 5.SOE-08 --2.70E..Q7 1.56E-12 1.91E-13 --8.81E-13 7.62E-07 4.56E-08 --4.45E-07 8.85E-10 3.10E-10 ------2.54E-08 1.55E-09 ---8.75E-09 Page 117 of 134 Revision 27 Lung GI-LLI 6.31E-05 1.38E-05 1.37E-06 6.02E-06 1.17E-03 1.14E-04 5.79E-04 3.78E-05 3.92E-05 B.83E-06 1.20E-04 1.87E-05 8.14E-07 7.17E-06 1.45E-04 4.79E-05 2.42E-07 1.96E-08 1.82E-05 6.95E-05 1.74E-07 2.30E-09 3.60E-05 6.37E-05 9.61E-07 --7.85E-07 --5.0BE-08 ---1.11E-06 ---1.26E-10 -6.56E-07 1.22E-05 1.30E-06 1.SOE-06 1.46E-06 9.40E-06 1.05E-06 6.07E-09 2.33E-13 , 4.70E-07 1.12E-07 1.59E-04 2.73E-05 2.42E-07 1.45E-17 1.49E-07 1.96E-26 1.70E-05 5.73E.:.05 7.91E-07 2.64E-07 4.52E-05 1.50E-05 9.97E-06 2.83E-05 9.72E-04 1.02E-04 3.51E-05 2.SOE-05 1.27E-07 2.69E-18 2.76E-05 2.16E-05 3.63E-06 1.94E-05 4.70E-06 1.49E-05 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone H-3 ---C-14 3.25E-06 Na-24 1.72E-06 P-32 2.36E-04 Cr-51 ---Mn-54 ---Mn-56 ---Fe-55 4.18E-06 Fe-59 1.99E-06 Co-58 --Co-60 --Ni-63 7.25E-05 Ni-65 2.73E-10 Cu-64 --Zn-65 4.82E-06 Zn-69 6.04E-12 Br-83 ---Br-84 ---Br-85 --Rb-86 --Rb-88 ---Rb-89 -Sr-89 5.43E-05 Sr-90 4.14E-03 Sr-91 1.10E-08 Sr-92 1.19E-09 Y-90 3.73E-07 Y-91M 4.63E-11 Y-91 8.26E-05 Y-92 1.84E-09 Y-93 1.69E-08 Zr-95 1.82E-05 Zr-97 1.72E-08 Nb-95 2.32E-06 Mo-99 ---Tc-99M 1.73E-13 Tc-101 7.40E-15 Table 10 -Inhalation Dose Factors for Teenager {mrem per pCi Inhaled) Liver T.Body Thyroid Kidney 9.06E-08 9.06E-08 9.0SE-08 9.0SE-08 6.09E-07 6.09E-07' 6.09E-07 6.019E-07 1.72E-06 1.72E-06 1.72E-06 1.72E-06 1.37E-05 8.95E-06 ------1.69E-08 9.37E-09 3.84E-09 6.39E-06 1.0SE-06 ---1.59E-06 2.12E-10 3.15E-11 ---*2.24E-10 2.98E-06 6.93E-07 ---4.62E-06 1.79E-06 ---2.59E-07 3.47E-07 ----1.89E-06 2.48E-06 -----5.43E-06 2.47E-06 -----3.66E-11 1.59E-11 ----2.54E-10 1.0SE-10 ---8.01E-10 1.67E-05 7.BOE-06 ---1.0BE-05 1.15E-11 8.07E-13 -7.53E-12 --4.30E-08 --------5.41E-08 -------2.29E-09 --2.38E-05 1.0SE-05 --6.82E-08 3.40E-08 --4.40E-08 2.91E-08 ---1.56E-06 --------8.33E-05 -------4.39E-10 -----5.08E-11 -----1.00E-08 -----1.77E-12 -----2.21E-06 ------5.36E-11 --------4.65E-10 -----5.73E-06 3.94E-06 -8.42E-06 3.40E-09 1.57E-09 --5.15E-09 1.29E-06 7.0BE-07 ---1.25E-06 2.11E-08 4.03E-09 -5.14E-08 4.83E-13 6.24E-12 --7.20E-12 1.0SE-14 1.03E-13 ---1.90E-13 Page 118 of 134 Revision 27 Lung GI-LLI 9.06E-08 9.0SE-08 6.09E-07 6.09E-07 1.72E-06 1.72E-06 --1.16E-05 2.62E-06 3.75E-07 2.48E-04 8.35E-06 1.90E-06 7.18E-06 1.SSE-05 7.99E-07 1.91E-04 2.23E-05 1.68E-04 1.19E-05 1.09E-03 3.24E-05 3.84E-05 1.77E-06 1.17E-06 4.59E-06 1.39E-06 7.68E-06 1.55E-04 5.83E-06 1.98E-07 3.56E-08 ----------------2.21E-06 ---3.65E-15 -4.22E-17 3.02E-04 4.64E-05 2.06E-03 9.56E-05 7.59E-06 3.24E-05 3.43E-06 1.49E-05 3.66E-05 6.99E-05 4.00E-07 3.77E-09 3.67E-04 5.11E-05 3.35E-06 2.06E-05 1.04E-05 7.24E-05 3.36E-04 1.86E-05 1.62E-05 7.88E-05 9.39E-05 1.21E-05 1.92E-05 3.36E-05 1.44E-07 7.66E-07 8.34E-08 1.09E-16 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone Ru-103 2.63E-07 Ru-105 1.40E-10 Ru-106 1.23E-05 Ag-110M 1.73E-06 Te-125M 6.10E-07 Te-127M 2.25E-06 Te-127 2.51E-10 Te-129M 1.74E-06 Te-129 8.87E-12 Te-131M 1.23E-08 Te-131 1.97E-12 Te-132 4.SOE-08 1-130 7.BOE-07 1-131 4.43E-06 1-132 1.99E-07 1-133 1.52E-06 1-134 1..11E-07 1-135 4.62E-07 Cs-134 6.28E-05 Cs-136 6.44E-06 Cs-137 8.38E-05 Cs-138 5.82E-08 Ba-139 1.67E-10 Ba-140 6.84E-06 Ba-141 1.78E-11 Ba-142 4.62E-12 La-140 5.99E-08 La-142 1.20E-10 Ce-141 3.55E-06 Ce-143 3.32E-08 Ce-144 6.11E-04 Pr-143 1.67E-06 Pr-144 5.37E-12 Nd-147 9.83E-07 W-187 1.50E-09 Np-239 4.23E-08 Table 10 -Inhalation Dose Factors for Teenager (mrem per pCi Inhaled) Liver T.Body Thyroid Kidney ---1.12E-07 -9.29E-07 --5.42E-11 --1.76E-10 -1.55E-06 --2.38E-05 1.64E-06 9.99E-07 ---3.13E-06 2.BOE-07 8.34E-08 1.75E-07 -1.02E-06 2.73E-07 5.48E-07 8.17E-06 1.14E-10 5.52E-11 1.77E-10 9.10E-10 8.23E-07 2.81E-07 5.72E-07 6.49E-06 4.22E-12 2.20E-12 6.48E-12 3.32E-11 7.51E-09 5.03E-09 9.0SE-09 5.49E-08 1.04E-12 6.30E-13 1.55E-12 7.72E-12 3.63E-08 2.74E-08 3.07E-08 2.44E-07 2.24E-06 8.96E-07 1.86E-04 3.44E-06 6.14E-06 3.30E-06 1.83E-03 1.0SE-05 5.47E-07 1.97E-07 1.89E-05 8.65E-07 2.56E-06 7.78E-07 3.65E-04 4.49E-06 2.90E-07 1.0SE-07 4.94E-06 4.SBE-07 1.18E-06 4.36E-07 7.76E-05 1.86E-06 1.41 E-04 6.86E-05 ---4.69E-05 2.42E-05 1.71E-05 ---1.38E-05 1.06E-04 3.89E-05 --3.BOE-05 1.07E-07 5.58E-08 --8.2BE-OB 1.18E-13 4.87E-12 --1.11 E-13 8.38E-09 4.40E-07 --2.BSE-09 1.32E-14 5.93E-13 ---1.23E-14 4.63E-15 2.84E-13 --3.92E-15 2.95E-08 7.82E-09 ---5.31E-11 1.32E-11 ----2.37E-06 2.71E-07 --1.11E-06 2.42E-08 2.70E-09 -1.0BE-08 2.53E-04 3.28E-05 --1.51E-04 6.64E-07 8.28E-08 ---3.86E-07 2.20E-12 2.72E-13 ---1.26E-12 1.07E-06 6.411::-08

---6.28E-07 1.22E-09 4.29E-10 -----3.60E-08 2.21E-09 ---1.25E-08 Page 119 of 134 Revision 27 Lung GI-LLI 9.79E-05 1.36E-05 2.27E-06 1.13E-05 2.01E-03 1.20E-04 8.44E-04 3.41E-05 6.70E-05 9.38E-06 2.07E-04 1.99E-05 1.40E-06 1.01E-05 2.47E-04 5.06E-05 4.12E-07 2.02E-07 2.97E-05 7.76E-05 2.92E-07 1.89E-09 5.61E-05 5.79E-05 ---1.14E-06 ---8.11E-07 ---1.59E-07 ---1.29E-06 ---2.SSE-09 -8.69E-07 1.83E-05 1.22E-06 2.22E-06 1.36E-06 1.51E-05 1.06E-06 9.84E-09 3.3BE-11 8.0BE-07 8.06E-07 2.54E-04 2.86E-05 4.11E-07 9.33E-14 2.39E-07 5.99E-20 2.68E-05 6.09E-05 1.27E-06 1.SOE-06 7.67E-05 1.SBE-05 1.63E-05 3.19E-05 1.67E-03 1.0BE-04 6.04E.,Q5 2.67E-05 2.19E-07 2.94E-14 4.65E-05 2.28E-05 5.92E-06 2.21E-05 8.11E-06 1.65E-05 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone H-3 -C-14 9.70E-06 Na-24 4.35E-06 P-32 7.04E-04 Cr-51 ---Mn-54 --Mn-56 --Fe-55 1.28E-05 Fe-59 5.59E-06 Co-58 ---Co-60 -Ni-63 2.22E-04 Ni-65 8.0BE-10 Cu-64 ---Zn-65 1.15E-05 Zn-69 1.81E-11 Br-83 ---Br-84 ---Br-85 -Rb-86 ---Rb-88 ---Rb-89 ---Sr-89 1.62E-04 Sr-90 1.04E-02 Sr-91 3.28E-08 Sr-92 3.54E-09 Y-90 1.11E-06 Y-91M 1.37E-10 Y-91 2.47E-04 Y-92 5.SOE-09 Y-93 5.04E-08 Zr-95 5.13E-05 Zr-97 5.07E-08 Nb-95 6.35E-06 Mo-99 ---Tc-99M 4.81E-13 Tc-101 2.19E-14 Table 11 -Inhalation Dose Factors for Child (mrem per pCi Inhaled) Liver T. Body Thyroid Kidney 1.73E-07 1.73E-07 1.73E-07 1.73E-07 1.82E-06 1.82E-06 1.82E-06 1.82E-06 4.35E-06 4.35E-06 4.35E-06 4.35E-06 3.09E-05 2.67E-05 --------4.17E-08 2.31E-08 6.57E-09 1.16E-05 2.57E-06 --2.71E-06 4.48E-10 8.43E-11 -4.52E-10 6.BOE-06 2.10E-06 ----9.04E-06 4.51E-06 ---4.79E-07 8.55E-07 ----3.55E-06 6.12E-06 ------1.25E-05 7.56E-06 ------7.99E-11 4.44E-11 ------5.39E-10 2.90E-10 --1.63E-09 3.06E-05 1.90E-05 --1.93E-05 2.61E-11 2.41E-12 --1.58E-11 --1.28E-07 --------1.48E-07 --------6.84E-09 --5.36E-05 3.09E-05 ---1.52E-07 9.90E-08 -----9.33E-08 7.BSE-08 ------4.66E-06 --------2.07E-04 --------1.24E-09 ------1.42E-10 ----2.99E-OB ----4.98E-12 -------6.59E-06 ------1.57E-10 -----1.38E-09 ----1.13E-05 1.00E-05 ---1.61 E-05 7.34E-09 4.32E-09 ---1.0SE-08 2.48E-06 1.77E-06 ---2.33E-06 4.66E-08 1.15E-08 --1.0SE-07 9.41E-13 1.56E-11 --1.37E-11 2.30E-14 2.91E-13 ---3.92E-13 Page 120 of 134 Revision 27 Lung GI-LLI 1.73E-07 1.73E-07 1.82E-06 1.82E-06 4.35E-06 4.35E-06 ---1.14E-05 4.59E-06 2.93E-07 4.26E-04 6.19E-06 3.SSE-06 3.33E-05 3.00E-05 7.75E-07 3.43E-04 1.91E-05 2.99E-04 9.29E-06 1.91E-03 2.60E-05 7.43E-05 1.71E-06 2.21E-06 2.27E-05 2.59E-06 9.92E-06 2.69E-04 4.41E-06 3.84E-07 2.75E-06 --------------2.16E-06 ---4.66E-09 ---5.11E-10 5.83E-04 4.52E-05 3.99E-03 9.28E-05 1.44E-05 4.70E-05 6.49E-06 6.55E-05 7.07E-05 7.24E-05 7.60E-07 4.64E-07 7.10E-04 4.97E-05 6.46E-06 6.46E-05 2.01E-05 1.0SE-04 6.03E-04 1.65E-05 3.06E-05 9.49E-05 1.66E-04 1.00E-05 3.66E-05 3.42E-05 2.57E-07 1.30E-06 1.58E-07 4.41E-09 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone Ru-103 7.55E-07 Ru-105 4.13E-10 Ru-106 3.68E-05 Ag-110M 4.56E-06 Te-125M 1.82E-06 Te-127M 6.72E-06 Te-127 7.49E-10 Te-129M 5.19E-06 Te-129 2.64E-11 Te-131M 3.63E-08 Te-131 5.87E-12 Te-132 1.30E-07 1-130 2.21E-06 1-131 1.30E-05 1-132 5.72E-07 1-133 4.48E-06 1-134 3.17E-07 1-135 1.33E-06 Cs-134 1.76E-04 Cs-136 1.76E-05 Cs-137 2.45E-04 Cs-138 1.71E-07 Ba-139 4.98E-10 Ba-140 2.00E-05 Ba-141 5.29E-11 Ba-142 1.35E-11 La-140 1.74E-07 La-142 3.SOE-10 Ce-141 1.06E-05 Ce'-143 9.89E-08 Ce-144 1.83E-03 Pr-143 4.99E-06 Pr-144 1.61E-11 Nd-147 2.92E-06 W-187 4.41E-09 Np-239 1.26E-07 Table 11 -Inhalation Dose Factors for Child (mrem per pCi Inhaled) Liver T.Body Thyroid Kidney --2.90E-07 ---1.90E-06 -1.SOE-10 -3.63E-10.

--4.57E-06 -4.97E-05 3.0BE-06 2.47E-06 -5.74E-06 6.29E-07 2.47E-07 5.20E-07 --2.31E-06 8.16E-07 1.64E-06 1.72E-05 2.57E-10 1.65E-10 5.30E-10 1.91E-09 1.85E-06 8.22E-07 1.71E-06 1.36E-05 9.45E-12 6.44E-12 1.93E-11 6.94E-11 1.60E-08 1.37E-08 2.64E-08 1.08E-07 2.28E-12 1.78E-12 4.59E-12 1.59E-11 7.36E-08 7.12E-08 8.58E-08 4.79E-07 4.43E-06 2.28E-06 4.99E-04 6.61E-06 1.30E-05 7.37E-06 4.39E-03 2.13E-05 1.10E-06 5.07E-07 5.23E-05 1.69E-06 5.49E-06 2.0SE-06 1.04E-03 9.13E-06 5.84E-07 2.69E-07 1.37E-05 8.92E-07 2.36E-06 1.12E-06 2.14E-04 3.62E-06 2.74E-04 6.07E-05 ---8.93E-05 4.62E-05 3.14E-05 -2.SBE-05 2.23E-04 3.47E-05 --7.63E-05 2.27E-07 1.SOE-07 ---1.68E-07 2.66E-13 1.45E-11 --2.33E-13 1.75E-08 1.17E-06 --5.71E-09 2.95E-14 1.72E-12 -2.56E-14 9.73E-15 7.54E-13 ---7.87E-15 6.0BE-08 2.04E-08 ------1.11E-10 3.49E-11 -----5.28E-06 7.83E-07 ---2.31E-06 5.37E-08 7.77E-09 ---2.26E-08 5.72E-04 9.77E-05 -3.17E-04 1.SOE-06 2.47E-07 ---8.11E-07 4.99E-12 8.10E-13 ---2.64E-12 2.36E-06 1.84E-07 --* 1.30E-06 2.61E-09 1.17E-09 ---8.14E-08 6.35E-09 -2.63E-08 Page 121 of 134 Revision 27 Lung Gl-LLI 1.79E-04 1.21E-05 4.30E-06 2.69E-05 3.87E-03 1.16E-04 1.48E-03 2.71E-05 1.29E-04 9.13E-06 4.00E-04 1.93E-05 2.71E-06 1.52E-05 4.76E-04 4.91E-05 7.93E-07 6.89E-06 5.56E-05 8.32E-05 5.55E-07 3.60E-07 1.02E-04 3.72E-05 ---1.38E-06 --7.68E-07 -8.65E-07 -1.48E-06 -2.58E-07 --1.20E-06 3.27E-05 1.04E-06 3.93E-06 1.13E-06 2.81E-05 9.78E-07 1.84E-08 7.29E-08 1.56E-06 1.56E-05 4.71E-04 2.75E-05 7.89E-07 7.44E-08 4.44E-07 7.41E-10 4.94E-05 6.10E-05 2.35E-06 2.0SE-05 1.47E-04 1.53E-05 3.12E-05 3.44E-05 3.23E-03 1.0SE-04 1.17E-04 2.63E-05 4.23E-07 5.32E-08 8.87E-05 2.22E-05 1.11E-05 2.46E-05 1.57E-05 1.73E-05 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone H-3 --C-14 1.89E-05 Na-24 7.54E-06 P-32 1.45E-03 Cr-51 --Mn-54 ---Mn-56 -Fe-55 1.41E-05 Fe-59 9.69E-06 Co-58 --Co-60 -Ni-63 2.42E-04 Ni.;65 1.71E-09 Cu-64 ---Zn-65 1.38E-05 Zn-69 3.85E-11 Br-83 ---Br-84 --Br-85 ---Rb-86 --Rb-88 --Rb-89 ---Sr-89 2.84E-04 Sr-90 1.11 E-02 Sr-91 6.83E-08 Sr-92 7.50E-09 Y-90 2.35E-06 Y-91M 2.91E-10 Y-91 4.20E-04 Y-92 1.17E-08 Y-93 1.07E-07 Zr-95 8.24E-05 Zr-97 1.07E-07 Nb-95 1.12E-05 Mo .. 99 --Tc-99M 9.98E-13 Tc-101 4.65E-14 Table 12 -Inhalation Dose Factors for Infant (mrem per pCi Inhaled) Liver T.Body Thyroid Kidney 2.63E-07 2.63E-07 2.63E-07 2.63E-07 3.79E-06 3.79E-06 3.79E-06 3.79E-06 7.54E-06 7.54E-06 7.54E-06 7.54E-06 8.03E-05 5.53E-05 --------6.39E-08 4.11E-08 9.45E-09 1.81E-05 3.56E-06 ---3.56E-06 1.10E-09 1.58E-10 ---7.86E-10 8.39E-06 2.38E-06 ----1.68E-05 6.77E-06 -----8.71E-07 1.30E-06 ----5.73E-06 8.41E-06 --1.46E-05 8.29E-06 ----2.03E-10 8.79E-11 ----1.34E-09 5.53E-10 ---2.84E-09 4.47E-05 2.22E-05 -2.32E-05 6.91E-11 5.13E-12 --2.87E-11 ---2.72E-07 ------2.86E-07 ------1.46E-08 -----1.36E-04 6.30E-05 ----3.98E-07 2.0SE-07 -----2.29E-07 1.47E-07 -----8.15E-06 -----2.23E-04 --------2.47E-09 -----2.79E-10 ----6.30E-08 -------9.90E-12 -------1.12E-05 -------3.29E-10 -------2.91E-09 ------1.99E-05 1.45E-05 --2.22E-05 1.83E-OB 8.36E-09 -1.85E-08 4.59E-06 2.70E-06 ---3.37E-06 1.18E-07 2.31E-08 -1.89E-07 2.0SE-12 2.66E-1'1

--2.22E-11 5.88E-14 5.BOE-13 ---6.99E-13 Page 122 of 134 Revision 27 Lung GI-LLI 2.63E-07 2.63E-07 3.79E-06 3.79E-06 7.54E-06 7.54E-06 -1.15E-05 9.17E-06 2.55E-07 7.14E-04 5.04E-06 8.95E-06 5.12E-05 6.21E-05 7.82E-07 7.25E-04 1.77E-05 5.SSE-04 7.95E-06 3.22E-03 2.28E-05 1.49E-04 1.73E-06 5.BOE-06 3.58E-05 6.64E-06 1.07E-05 4.62E-04 3.67E-05 1.05E-06 9.44E-06 ---------------2.17E-06 --2.42E-07 --4.87E-08 1.45E-03 4.57E-05 8.03E-03 9.36E-05 3.76E-05 5.24E-05 1.70E-05 1.bOE-04 1.92E-04 7.43E-05 1.99E-06 1.68E-06 1.75E-03 5.02E-05 1.75E-05 9.04E-05 5.46E-05 1.19E-04 1.25E-03 1.55E-05 7.BBE-05 1.00E-04 3.42E-04 9.0SE-06 9.63E-05 3.48E-05 5.79E-07 1.45E-06 4.17E-07 6.03E-07 CH-ODCM-0001 Reference Use Off-Site Dose Ccilculation Manual (ODCM) Nuclide Bone Ru-103 1.44E-06 Ru-105 8.74E-10 Ru-106 6.20E-05 Ag-110M 7.13E-06 Te-125M 3.40E-06 Te-127M 1.19E-05 Te-127 1.59E-09 Te-129M 1.01E-05 Te-129 5.63E-11 Te-131M 7.62E-08 Te-131 1.24E-11 Te-132 2.66E-07 1-130 4.54E-06 1-131 2.71E-05 1-132 1.21E-06 1-133 9.46E-06 1-134 6.58E-07 1-135 2.76E-06 Cs-134 2.83E-04 Cs-136 3.45E-05 Cs-137 3.92E-04 Cs-138 3.61E-07 Ba-139 123.06E-09 Ba-140 4.00E-05 Ba-141 1.12E-10 Ba-142 2.84E-11 La-140 3.61E-07 La-142 7.36E-10 Ce-141 1.98E-05 Ce-143 2.09E-07 Ce-144 2.2BE-03 Pr-143 1.00E-05 Pr-144 3.42E-11 Nd-147 5.67E-06 W-187 9.26E-09 Np-239 2.65E-07 Table 12 -Inhalation Dose Factors for Infant (mrem per pCi Inhaled) Liver T.Body Thyroid Kidney --4.BSE-07 ---3.03E-06 -2.93E-10 -6.42E-10 ---7.77E-06 -7.61E-05 5.16E-06 3.57E-06 ---7.BOE-06 1.42E-06 4.70E-07 1.16E-06 -4.93E-06 1.48E-06 3.48E-06 2.68E-05 6.81E-10 3.40E-10 1.32E-09 3.47E-09 4.35E-06 1.59E-06 3.91E-06 2.27E-05 2.48E-11 1.34E-11 4.82E-11 1.25E-10 3.93E-08 2.59E-08 6.38E-08 1.89E-07 5.87E-12 3.57E-12 1.13E-11 2.BSE-11 1.69E.,Q7 1.26E-07 1.99E-07 7.39E-07 9.91E-06 3.98E-06 1.14E-03 1.09E-05 3.17E-05 1.40E-05 1.06E-02 3.70E-05 2.53E-06 8.99E-07 1.21E-04 2.82E-06 1.37E-05 4.00E-06 2.54E-03 1.60E-05 1.34E-06 4.75E-07 3.18E-05 1.49E-06 5.43E-06 1.98E-06 4.97E-04 6.0SE-06 5.02E-04 5.32E-05 -1.36E-04 9.61E-05 3.78E-05 ---4.03E-05 4.37E-04 3.25E-05 ---1.23E-04 5.58E-07 2.84E-07 -2.93E-07 7.03E-13 3.07E-11 ---4.23E-13 4.00E-08 2.07E-06 ---9.59E-09 7.70E-14 3.55E-12 ---4.64E-14 2.36E-14 1.40E-12 ---1.36E-14 1.43E-07 3.68E-08 --2.69E-10 6.46E-11 --1.19E-05 1.42E-06 -3.75E-06 1.3BE-07 1.58E-08 ---4.03E-08 8.65E-04 1.26E-04 ---3.84E-04 3.74E-06 4.99E-07 ---1.41 E-06 1.32E-11 1.72E-12 ---4.BOE-12 5.81E-06 3.57E-07 -2.25E-06 6.44E-09 2.23E-09 ---2.13E-07 1.34E-08 --4.73E-08 Page 123 of 134 Revision 27 Lung GI-LLI 3.94E-04 1.15E-05 1.12E-05 3.46E-05 8.26E-03 1.17E-04 2.62E-03 2.36E-05 3.19E-04 9.22E-06 9.37E-04 1.95E-05 7.39E-06 1.74E-05 1.20E-03 4.93E-05 2.14E-06 1.88E-05 1.42E-04 B.51E-05 1.47E-06 5.87E-06 2.43E-04 3.15E-05 -1.42E-06 -7.56E-07 ---1.36E-06 -1.54E-06 ---9.21E-07 -1.31E-06 5.69E-05 9.53E-07 8.40E-06 1.02E-06 5.09E-05 9.53E-07 4.67E-08 6.26E-07 4.25E-06 3.64E-05 1.14E-03 2.74E-05 2.12E-06 ,3.39E-06 1.11E-06 4.95E-07 1.20E-04 6.06E-05 5.87E-06 4.25E-05 3.69E-04 1.54E-05 8.30E-05 3.55E-05 7.03E-03 1.06E-04 3.09E-04 2.66E-05 1.15E-06 3.06E-06 2.30E-04 2.23E-05 2.83E-05

  • 2.54E-05 4.25E-05 1.78E-05 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone H-3 ---C-14 2.84E-06 Na-24 1.70E-06 P-32 1.93E-04 Cr-51 ---Mn-54 ---Mn-56 --Fe-55 2.75E-06 Fe-59 4.34E-06 Co-58 ---Co-60 --Ni-63 1.30E-04 Ni-65 5.28E-07 Cu-64 ---Zn-65 4.84E-06 Zn-69 1.03E-08 Br-83 --Br-84 -Br-85 ---Rb-86 ---Rb-88 --Rb-89 -Sr-89 3.0SE-04 Sr-90 8.71E-03 Sr-91 5.67E-06 Sr-92 2.15E-06 Y-90 9.62E-09 Y-91M 9.09E-11 Y-91 1.41E-07 Y-92 8.45E-10 Y-93 2.68E-09 Zr-95 3.04E-08 Zr-97 1.68E-09 Nb-95 6.22E-09 Mo-99 --Tc-99M 2.47E-10 Tc-101 2.54E-10 Table 13 -Ingestion Dose Factors for Adult (mrem per pCi Ingested)

Liver T.Body Thyroid Kidney 5.99E-08 5.99E-08 5.99E-08 5.99E-08 5.68E-07 5.68E-07 5.68E-07 5.68E-07 1.70E-06 1.70E-06 1.70E-06 1.70E-06 1.20E-05 7.46E-06 ------2.66E-09 1.59E-09 5.86E-10 4.57E-06 8.72E-07 ---1.36E-06 1.15E-07 2.04E-08 -1.46E-07 1.90E-06 4.43E-07 -----1.02E-05 3.91E-06 ------7.45E-07 1.67E-06 --2.14E-06 4.72E-06 --9.01E-06 4.36E-06 -----6.86E-08 3.13E-08 ----8.33E-08 3.91E-08 -2.10E-07 1.54E-05 6.96E-06 ---1.03E-05 1.97E-08 1.37E-09 -1.28E-08 --4.02E-08 ------5.21E-08 --------2.14E-09 -----2.11E-05 9.83E-06 ---6.0SE-08 3.21E-08 ---4.01E-08 2.82E-08 ------8.84E-06 -------1.75E-04 -------2.29E-07 ---------9.30E-08 -----2.58E-10 ----3.52E'-12


3.77E-09 ------2.47E-11 -------7.40E-11 ----9.75E-09 6.SOE-09 --1.53E-08 3.39E-10 1.55E-10 --5.12E-10 3.46E-09 1.86E-09 ---3.42E-09 4.31E-06 8.20E-07 -9.76E-06 6.98E-10 8.89E-09 -1.0SE-08 3.66E-10 3.59E-09 ---6.59E-09 Page 124 of 134 Revision 27 Lung GI-LLI 5.99E-08 5.99E-08 5.68E-07 5.68E-07 1.70E-06 1.70E-06 --2.17E-05 3.53E-09 6.69E-07 ---1.40E-05 --3.67E-06 1.06E-06 1.09E-06 2.85E-06 3.40E-05 ---1.51E-05 --4.02E-05 --1.88E-06 -1.74E-06 --7.10E-06 ---9.70E-06 ---2.96E-09 --5.79E-08 --4.09E-13 -----4.16E-06 --8.36E-19 -2.33E-21 --4.94E-05 --2.19E-04 --2.70E-05 ---4.26E-05 --1.02E-04 --2.67E-10 --7.76E-05 -1.48E-05 ---8.50E-05 ---3.09E-05 ---1.05E-04 ---2.10E-05 --9.99E-06 3.42E-10 4.13E-07 1.87E-10 1.10E-21 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone Ru-103 1.85E-07 Ru-105 1.54E-08 Ru-106 2.75E-06 Ag-110M 1.60E-07 Te-125M 2.68E-06 Te-127M 6.77E-06 Te-127 1.10E-07 Te-129M 1.15E-05 Te-129 3.14E-08 Te-131M 1.73E-06 Te-131 1.97E-08 Te-132 2.52E-06 1-130 7.56E-07 1-131 4.16E-06 1-132 2.03E-07 1-133 1.42E-06 1-134 1.06E-07 1-135 4.43E-07 Cs-134 6.22E-05 Cs-136 6.51E-06 Cs-137 7.97E-05 Cs-138 5.52E-08 Ba-139 9.70E-08 Ba-140 2.03E-05 Ba-141 4.71E-08 Ba-142 2.13E-08 La-140 2.SOE-09 La-142 1.28E-10 Ce-141 9.36E-09 Ce-143 1.65E-09 Ce-144 4.BBE-07 Pr-143 9.20E-09 Pr-144 3.01E-11 Nd-147 6.29E-09 W-187 1.03E-07 Np-239 1.19E-09 Table 13 -Ingestion Dose Factors for Adult (mrem per pCi Ingested)

Liver T.Body Thyroid Kidney ---7.97E-08 -7.06E-07 ---6.0SE-09 ---1.99E-07 ---3.4SE-07 --5.31E-06 1.48E-07 8.79E-08 ---2.91E-07 9.71E-07 3.59E-07 8.06E-07 1.09E-05 2.42E-06 8.25E-07 1.73E-06 2.75E-05 3.95E-08 2.38E-08 8.15E-08 4.48E-07 4.29E-06 1.82E-06 3.95E-06 4.BOE-05 1.18E-08 7.65E-09 2.41E-08 1.32E-07 8.46E-07 7.05E-07 1.34E-06 8.57E-06 8.23E-09 6.22E-09 1.62E-,08 8.63E-08 1.63E-06 1.53E-06 1.BOE-06 1.57E-05 2.23E-06 8.SOE-07 1.89E-04 3.48E-06 5.95E-06 3.41E-06 1.95E-03 1.02E-05 5.43E-07 1.90E-07 1.90E-05 8.65E-07 2.47E-06 7.53E-07 3.63E-04 4.31E-06 2.88E-07 1.03E-07 4.99E-06 4.58E-07 1.16E-06 4.28E-07 7.65E-05 1.86E-06 1.48E-04 1.21E-04 -4.79E-05 2.57E-05 1.85E-05 --1.43E-05 1.09E-04 7.14E-05 -3.70E-05 1.09E-07 5.40E-08 ---8.01E-08 6.91E-11 2.84E-09 ---6.46E-11 2.55E-08 1.33E-06 ---8.67E-09 3.56E-11 1.59E-09 --3.31E-11 2.19E-11 1.34E-09 ---1.85E-11 1.26E-09 3.33E-10 ------5.82E-11 1.45E-11 ------6.33E-09 7.18E-10 --2.94E-09 1.22E-06 1.35E-10 -5.37E-10 2.04E-07 2.62E-08 --1.21E-07 3.69E-09 4.56E-10 ---2.13E-09 1.25E-11 1.53E-12 ---7.05E-12 7.27E-09 4.35E-10 ---4.25E-09 8.61E-08 3.01E-08 ----1.17E-10 6.45E-11 --3.65E-10 Page 125 of 134 Revision 27 Lung GI-LLI -2.16E-05 -9.42E-06 ---1.78E-04 ---6.04E-05 ---1.07E-05 ---2.27E-05 ---8.68E-06 --5.79E-05 --'2.37E-08

--8.40E-05 ---2.79E-09 --7.71E-05 ---1.92E-06 ---1.57E-06 ---1.02E-07 -2.22E-06 --2.51E-10 --1.31 E-06 1.59E-05 2.59E-06 1.96E-06 2.92E-06 1.23E-05 2.11E-06 7.91E-09 4.65E-13 3.92E-11 1.72E-07 1.46E-08 4.18E-05 2.02E-11 2.22E-17 1.24E-11 3.00E-26 -9.25E-05 --4.25E-07 --2.42E-05 -4.56E-05 --1.65E-04 -4.03E-05 ---4.33E-18 --3.49E-05 ---2.82E-05 ---2.40E-05 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone H-3 -C-14 4.06E-06 Na-24 2.30E-06 P-32 2.76E-04 Cr-51 --Mn-54 --Mn-56 --Fe-55 3.7BE-06 Fe-59 5.87E-06 Co-58 --Co-60 ---Ni-63 1.77E-04 Ni-65 7.49E-07 Cu-64 --Zn-65 5.76E-06 Zn-69 1.47E-08 Br-83 ---Br-84 ---Br-85 ---Rb-86 ---Rb-88 --Rb-89 -Sr-89 4.40E-04 Sr-90 1.02E-02 Sr-91 8.07E-06 Sr-92 3.0SE-06 Y-90 1.37E-08 Y-91M 1.29E-10 Y-91 2.01E-07 Y-92 1.21E-09 Y-93 3.83E-09 Zr-95 4.12E-08 Zr-97 2.37E-09 Nb-95 8.22E-09 Mo-99 --Tc-99M 3.32E-10 Tc-101 3.60E-10 Table 14 -Ingestion Dose Factors for Teenager (mrem per pCi Ingested)

Liver T.Body Thyroid Kidney 6.04E-08 6.04E-08 6.04E-OB 6.04E-08 8.12E-07 8.12E-07 8.12E-07 8.12E-07 2.30E-06 2.30E-06

  • 2.30E-06 2.30E-06 1.71E-05 1.07E-05 -------3.60E-09 2.00E-09 7.89E-10 5.90E-06 1.17E-06 ---1.76E-06 1.SBE-07 2.81E-08 ---2.00E-07 2.68E-06 6.25E-07 ------1.37E-05 5.29E-06 ----9.72E-07 2.24E-06 ----2.81E-06 6.33E-06 ---1.25E-05 6.00E-06 ---9.57E-08 4.36E-08 -----1 .15E-07 5.41E-08 --'2.91E-07 2.00E-05 9.33E-06 ---1.28E-05 2.BOE-08 1.96E-09 --1.83E-08 -5.74E-08 --------7.22E-08 -----3.0SE-09 -----2.98E-05 1.40E-05 --8.52E-08 4.54E-08 ---5.SOE-08 3.89E-08 ----1.26E-05 -----2.04E-04 -------3.21E-07 ------1.30E-07 ------3.69E-10 ------4.93E-12 -------5.39E-09 -------3.SOE-11 -------1.0SE-10 ---1.30E-08 8.94E-09 --1.91E-08 4.69E-10 2.16E-10 --7.11E-10 4.56E-09 2.51E-09 --4.42E-09 6.03E-06 1.15E-06 ---1.38E-05 9.26E-10 1.20E-08 ---1.38E-08 5.12E-10 5.03E-09 ---9.26E-09 Page 126 of 134 Revision 27 Lung GI-LLI 6.04E-08 6.04E-08 8.12E-07 8.12E-07 2.30E-06 2.30E-06 --2.32E-05 5.14E-09 6.05E-07 ---1.21E-05 ---1.04E-05 1.70E-06 1.16E-06 4.32E-06 3.24E-05 --1.34E-05 --3.66E-05 -1.99E-06 ---5.19E-06 ---8.92E-06 ---8.47E-06 ---5.16E-08 --------------4.41E-06 --7.30E-15 -8.43E-17 ---5.24E-05 -2.33E-04 -3.66E-05 ---7.77E-05 ---1.13E-04 --6.09E-09 --8.24E-05 -3.32E-05 ---1.17E-04 -3.00E-05 -1.27E-04 ---1.95E-05 -1.0BE-05 5.14E-10 6.0BE-07 3.12E-10 8.75E-17 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone Ru-103 2.55E-07 Ru-105 2.18E-08 Ru-106 3.92E-06 Ag-110M 2.05E-07 Te-125M 3.83E-06 Te-127M 9.67E-06 Te-127 1.58E-07 Te-129M 1.63E-05 Te-129 4.48E-08 Te-131M 2.44E-06 Te-131 2.79E-08 Te-132 3.49E-06 1-130 1.03E-06 1-131 5.85E-06 1-132 . 2.79E-07 1-133 2.01E-06 1-134 1.461;-07 1-135 6.10E-07 Cs-134 8.37E-05 Cs-136 8.59E-06 Cs-137 1.12E-04 Cs-138 7.76E-08 Ba-139 1.39E-07 Ba-140 2.84E-05 Ba-141 6.71E-08 Ba-142 2.99E-OB La-140 3.48E-09 La-142 1.79E-10 Ce-141 1.33E-08 Ce-143 2.35E-09 Ce-144 6.96E-07 Pr-143 1.31E-08 Pr-144 4.30E-11 Nd-147 9.38E-09 W-187 1.46E-07 Np-239 1.76E-09 Table 14 -Ingestion Dose Factors for Teenager (mrem per pCi Ingested)

Liver T.Body Thyroid Kidney -1.09E-07 ---8.99E-07 *-8.46E-09 ---2.75E-07 -4.94E-07 --7.56E-06 1.94E-07 1.18E-07 --3.70E-07 1.38E-06 5.12E-07 1.07E-06 / --3.43E-06 1.15E-06 2.30E-06 3.92E-05 5.SOE-08 3.40E-OB 1.09E-07 6.40E-07 6.05E-06 2.58E-06 5.26E-06 6.82E-05 1.67E-08 1.09E-08 3.20E-08 1.88E-07 1.17E-06 9.76E-07 . 1.76E-06 1.22E-05 1.15E-08 8.72E-09 2.15E-08 1.22E-07 2.21E-06 2.0BE-06 2.33E-06 2.12E-05 2.98E-06 1.19E-06 2.43E-04 4.59E-06 8.19E-06 4.40E-06 2.39E-03 1.41E-05 7.30E-07 2.62E-07 2.46E-05 1.15E-06 3.41E-06 1.04E-06 4.76E-04 5.98E-06 3.87E-07 1.39E-07 6.45E-06 6.10E-07 1.57E-06 5.82E-07 1.01E-04 2.48E-06 1.97E-04 9.14E-05 ---6.26E-05 3.38E-05 2.27E-05 ---1.84E-05 1.49E-04 5.19E-05 --5.07E-05 1.49E-07 7.45E-08 --1.10E-07 9.78E-11 4.0SE-09 --9.22E-11 3.48E-08 1.83E-06 ---1.18E-08 5.01E-11 2.24E-09 -4.65E-11 2.99E-11 1.84E-09 --2.53E-11 1.71E-09 4.55E-10 ------7.95E-11 1.98E-11 ----8.BBE-09 1.02E-09 ---4.18E-09 1.71E-06 1.91E-10 ---7,67E-10 2.BBE-07 3.74E-08 ---1.72E-07 5.23E-09 6.52E-10 --3.04E-09 1.76E-11 2.18E-12 --1.01E-11 1.02E-08 6.11E-10 -5.99E-09 1.19E-07 4.17E-08 ----1.66E-10 9.22E-11 --5.21E-10 Page 127 of 134 Revision 27 Lung Gl-LLI --2.13E-05 --1.76E-05 -1.BBE-04 ---5.45E-05 --1.13E-05 --2.41E-05 ---1.22E-05 -6.12E-05 ---' 2.45E-07 ---9.39E-05 ---2.29E-09 ---7.00E-05 ---2.29E-06 --1.62E-06 ... 3.18E-07 --2.58E-06 -5.10E-09 -1.74E-06 2.39E-05 2.45E-06 2.90E-06 2.72E-06 1.97E-05 2.12E-06 1.28E-OB 4.76E-11 6.74E-11 1.24E-06 2.34E-08 4.38E-05 3.43E-11 1.43E-13 1.99E-11 9.18E-20 -9.28E-05 -2.42E-06 -2.54E-05 -5.14E-05 ---1.75E-04 ---4.31E-05 --4.74E-14 --3.68E-05 --3.22E-05 -2.67E-05 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone H-3 ---C-14 1.21E-05 Na-24 5.BOE-06 P-32 8.25E-04 Cr-51 --Mn-54 ---Mn-56 ---Fe-55 1.15E-05 Fe-59 1.65E-05 Co-58 **-Co-60 ---Ni-63 5.38E-04 Ni-65 2.22E-06 Cu-64 --Zn-65 1.37E-05 Zn-69 4.38E-08 Br-83 ---Br-84 ---Br-85 --Rb-86 ---Rb-88 ---Rb-89 ---Sr-89 1.32E-03 Sr-90 2.56E-02 Sr-91 2.40E-05 Sr-92 9.03E-06 Y-90 4.11E-08 Y-91M 3.82E-10 Y-91 6.02E-07 Y-92 3.60E-09 Y-93 1.14E-08 Zr-95 1.16E-07 Zr-97 6.99E-09 Nb-95 2.25E-08 Mo-99 -Tc-99M 9.23E-10 Tc-101 1.07E-09 Table 15 -Ingestion Dose Factors for Child (mrem per pCi Ingested)

Liver T.Body Thyroid Kidney 1.16E-07 1.16E-07 1.16E-07 1.16E-07 2.42E-06 2.42E-06 2.42E-06 2.42E-06 5.BOE-06 5.80E-06 5.80E-06 5.BOE-06 3.86E-05 3.18E-05 --* ----8.90E-09 4.94E-09 1.35E-09 1.07E-05 2.85E-06 ---3.00E-06 3.34E-07 7.54E-08 ---4.04E-07 6.10E-06 1.89E-06 ----2.67E-05 1.33E-05 -----1.BOE-06 5.51E-06 ------5.29E-06 1.56E-05 ----2.88E-05 1.83E-05 ------2.09E-07 1.22E-07 -----2.45E-07 1.48E-07 ---5.92E-07 3.65E-05 2.27E-05 --2.30E-05 6.33E-08 5.85E-09 ---3.84E-08 ---1.71E-07 --------1.98E-07 --------9.12E-09 ---6.70E-05 4.12E-05 --1.90E-07 1.32E-07 ... ---1.17E-07 1.04E-07 -------3.77E-05 --------5.15E-04 -------9.06E-07 -----3.62E-07 --------1.10E-09 -----*-1.39E-11 --------1.61E-08 -------1.03E-10 -----3.13E-10 ------2.55E-08 2.27E-08 ---3.65E-08 1.01E-09 5.96E-10 --1.45E-09 8.76E-09 6.26E-09 ---8.23E-09 1.33E-05 3.29E-06 ---2.84E-05 1.81E-09 3.00E-08 ---2.63E-08 1.12E-09 1.42E-08 ---1.91E-08 Page 128 of 134 Revision 27 Lung GI-LLI 1.16E-07 1.16E-07 2.42E-06 2.42E-06 5.SOE-06 5.BOE-06 ---2.28E-05 9.02E-09 4.72E-07 ---8.98E-06 --4.84E-05 3.45E-06 1.13E-06 7.74E-06 2.78E-05 ---1.05E-05 ---2.93E-05 ---1.94E-06 ---2.56E-05 --1.15E-05 ---6.41E-06 --3.99E-06 -----------------4.31E-06 -9.32E-09 ---1.02E-09 ---5.11 E-05 ---2.29E-04 ---5.30E-05 --1.71E-04 --1.17E-04 --7.48E-07 ---8.02E-05 --1.04E-04 -1.70E-04 -2.66E-05 --1.53E-04 --1.62E-05 ---1.10E-05 9.19E-10 1.03E-06 5.92E-10 3.56E-09 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Table 15 -Ingestion Dose Factors for Child (mrem per pCi Ingested)

Nuclide Bone Liver T.Body Thyroid Kidney Ru-103 7.31E-07 ---2.81E-07 -1.84E-06 Ru-105 6.45E-08 ---2.34E-08 ---5.67E-07 Ru-106 1.17E-05 --1.46E-06 ---1.58E-05 Ag-110M 5.39E-07 3.64E-07 2.91E-07 ---6.78E-07 Te-125M 1.14E-05 3.09E-06 1.52E-06 3.20E-06 --Te-127M 2.89E-05 7.78E-06 3.43E-06 6.91E-06 8.24E-05 Te-127 4.71E-07 1.27E-07 1.01E-07 3.26E-07 1.34E-06 Te-129M 4.87E-05 1.36E-05 7.56E-06 1.57E-05 1.43E-04 Te-129 1.34E-07 3.74E-08 3.18E-08 9.56E-08 3.92E-07 Te-131M 7.20E-06 2.49E-06 2.65E-06 5.12E-06 2.41E-05 Te-131 8.30E-08 2.53E-08 2.47E-08 6.35E-08 2.51E-07 Te-132 1.01E-05 4.47E-06 5.40E-06 6.51E-06 4.15E-05 1-130 2.92E-06 5.90E-06 3.04E-06 6.50E-04 8.82E-06 1-131 1.72E-05 1.73E-05 9.83E-06 5.72E-03 2.84E-05 1-132 8.00E-07 1.47E-06 6.76E-07 6.82E-05 2.25E-06 1-133 5.92E-06 7.32E-06 2.77E-06 1.36E-03 1.22E-05 1-134 4.19E-07 7.78E-07 3.58E-07 1.79E-05 1.19E-06 1-135 1.75E-06 3.15E-06 1.49E-OI:>

2.79E-04 4.83E-06 Cs-134 2.34E-04 3.84E-04 8.10E-05 ---1.19E-04 Cs-136 2.35E-05 6.46E-05 4.1BE-05 --3.44E-05 Cs-137 3.27E-04 3.13E-04 4.62E-05 --1.02E-04 Cs-138 2.28E-07 3.17E-07 2.01E-07 ---2.23E-07 Ba-139 4.14E-07 2.21E-10 1.20E-08 --1.93E-10 Ba-140 8.31E-05 7.28E-08 4.85E-06 -2.37E-08 Ba.;;141 2.00E-07 1.12E-10 6.51E-09 --9.69E-11 Ba-142 8.74E-08 6.29E-1*1 4.88E-09 --5.09E-11 La-140 1.01E-08 3.53E-09 1.19E-09 ---La-142 5.24E-10 1.67E-10 5.23E-11 -----Ce-141 3.97E-08 1.98E-08 2.94E-09 ---8.68E-09 Ce-143 6.99E-09 3.79E-06 5.49E-10 --1.59E-09 Ce-144 2.0BE-06 6.52E-07 1.11E-07 ---3.61E-07 Pr-143 3.93E-08 1.18E-08 1.95E-09 --6.39E-09 Pr-144 1.29E-10 3.99E-11 6.49E-12 ---2.11E-11 Nd-147 2.79E-08 2.26E-08 1.75E-09 --1.24E-08 W-187 4.29E-07 2.54E-07 1.14E-07 ----Np-239 5.25E-09 3.77E-10 2.65E-10 --1.09E-09 Page 129 of 134 Revision 27 Lung Gl*LLI --1.89E-05 ---4.21E-05 ---1.82E-04 ---4.33E-05 -1.10E-05 --2.34E-05 ---1.84E-05 --5.94E-05 --8.34E-06 ---1.01E-04 ---4.36E-07 --4.SOE-05 ---2.76E-06 --1.54E-06 -1.73E-06 ---2.95E-06 ---5.16E-07 --2.40E-06 4.27E-05 2.07E-06 5.13E-06 2.27E-06 3.67E-05 1.96E-06-2.40E-08 1.46E-07 1.30E-10 2.39E-05 4.34E-08 4.21E-05 6.58E-10 1.14E-07 3.70E-11 1.14E-09 ---9.84E-05 -3.31E-05 ---2.47E-05 ---5.55E-05 ---1.70E-04 ---4.24E-05 --8.59E-08 -3.58E-05 -3.57E-05 -2.79E-05 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone I H-3 --C-14 2.37E-05 Na-24 1.01E-05 P-32 1.70E-03 Cr-51 ---Mn-54 ---Mn-56 ---Fe-55 1.39E-05 Fe-59 3.0SE-05 Co-58 -Co-60 --Ni-63 6.34E-04 Ni-65 4.70E-06 Cu-64 -Zn-65 1.84E-05 Zn-69 9.33E-08 Br-83 ---Br-84 -Br-85 ---Rb-86 ---Rb-88 --Rb-89 --Sr-89 2.51E-03 Sr-90 2.83E-02 Sr-91 5.00E-05 Sr-92 1.92E-05 Y-90 8.69E-08 Y-91M 8.10E-10 Y-91 1.13E-06 Y-92 7.65E-09 Y-93 2.43E-08 Zr-95 2.06E-07 Zr-97 1.48E-08 Nb-95 4.20E-08 Mo-99 ---Tc-99M 1.92E-09 Tc-101 2.27E-09 Table 16 -Ingestion Dose Factors for Infant (mrem per pCi Ingested)

Liver T.Body Thyroid Kidney 1.76E-07 1.76E-07 1.76E-07 1.76E-07 5.06E-06 5.06E-06 5.06E-06 5.06E-06 1.01E-05 1.01E-05 1.01E-05 1.01E-05 1.00E-04 6.59E-05 -------1.41E-08 9.20E-09 2.01E-09 1.99E-05 4.51E-06 ---4.41E-06 8.18E-07 1.41E-07 --7.03E-07 8.98E-06 2.40E-06 -----5.38E-05 2.12E-05 -----3.60E-06 8.98E-06 -----1.0BE-05 2.55E-05 -----3.92E-05 2.20E-05 ---5.32E-07 2.42E-07 -----6.09E-07 2.82E-07 -1.03E-06 6.31E-05 2.91E-05 ---3.06E-05 1.68E-07 1.25E-08 --6.98E-08 ---3.63E-07 ------3.82E-07 ----1.94E-08 ---1.70E-04 8.40E-05 ----4.98E-07 2.73E-07 ---2.86E-07 1.97E-07 -----7.20E-05 ------5.74E-04 ---------1.81 E-06 -------7.13E-07 --------2.33E-09 -------2.76E-11 --------3.01E-08 -------2.15E-10 ------6.62E-10 ----5.02E-08 3.56E-08 --5.41E-08 2.54E-09 1.16E-09 -2.56E-09 1.73E-08 1.00E-08 ---1.24E-08 3.40E-05 6.63E-06 --5.0BE-05 3.96E-09 5.10E-OB ---4.26E-08 2.86E-09 2.83E-08 --3.40E-08 Page 130 of 134 Revision 27 Lung GI-LLI 1.76E-07 1.76E-07 5.06E-06 5.06E-06 1.01E-05 1.01E-05 --2.30E-05 1.79E-08 4.11E-07 --7.31E-06 --7.43E-05 4.36E-06 1.14E-06 1.59E-05 2.57E-05 --8.97E-06 -2.57E-05 ---1.95E-06 --4.0SE-05 --1.25E-05 --5.33E-05 ---1.37E-05 ----------------4.35E-06 ---4.85E-07 --9.74E-08 ---5.16E-05 ---2.31E-04 --5.92E-05 --2.07E-04 ---1.20E-04 --2.70E-06 --8.10E-05 --1.46E-04 ---1.92E-04 ---2.SOE-05 -1.62E-04 --1.46E-05 -1.12E-05 2.07E-09 1.15E-06 1.56E-09 4.86E-07 CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Nuclide Bone Ru-103 1.48E-06 Ru-105 1.36E-07 Ru-106 2.41E-05 Ag-110M 9.96E-07 Te-125M 2.33E-05 Te-127M 5.BSE-05 Te-127 1.00E-06 Te-129M 1.00E-04 Te-129 2.84E-07 Te-131M 1.52E-05 Te-131 1.76E-07 Te-132 2.0BE-05 1-130 6.00E-06 1-131 3.59E-05 1-132 1.66E-06 1-133 1.25E-05 1-134 8.69E-07 1-135 3.64E-06 Cs-134 3.77E-04 Cs-136 4.59E-05 Cs-137 5.22E-04 Cs-138 4.81E-07 Ba-139 8.81E-07 Ba-140 1.71E-04 Ba-141 4.25E-07 Ba-142 1.84E-07 La-140 2.11E-08 La-142 1.10E-09 Ce-141 7.87E-08 Ce-143 1.48E-08 Ce-144 2.98E-06 Pr-143 8.13E-08 Pr-144 2.74E-10 Nd-147 5.53E-08 W-187 9.03E-07 Np-239 1.11E-08 Table 16 -Ingestion Dose Factors for Infant (mrem per pCi Ingested)

Liver T.Body Thyroid Kidney -4.95E-07 -3.0SE-06 -4.58E-08 --1.00E-06 --3.01E-06 -2.85E-05 7.27E-07 4.81E-07 ---1.04E-06 7.79E-06 3.15E-06 7.84E-06 -1.94E-05 7.0BE-06 1.69E-05 1.44E-04 3.35E-07 2.15E-07 8.14E-07 2.44E-06 3.43E-05 1.54E-05 3.84E-05 2.SOE-04 9.79E-08 6.63E-08 2.38E-07 7.07E-07 6.12E-06 5.0SE-06 1.24E-05 4.21E-05 6.SOE-08 4.94E-08 1.57E-07 4.SOE-07 1.03E-05 9.61E-06 1.52E-05 6.44E-05 1.32E-05 5.30E-06 1.48E-03 1.45E-05 4.23E-05 1.86E-05 1.39E-02 4.94E-05 3.37E-06 1.20E-06 1.58E-04 3.76E-06 1.82E-05 5.33E-06 3.31E-03 2.14E-05 1.78E-06 6.33E-07 4.15E-05 1.99E-06 7.24E-06 2.64E-06 6.49E-04 8.07E-06 7.03E-04 7.10E-05 --1.81E-04 1.35E-04 5.04E-05 --5.3BE-05 6.11E-04 4.33E-05 ---1.64E-04 7.82E-07 3.79E-07 -3.90E-07 5.84E-10 2.55E-08 --3.51E-10 1.71E-07 8.81E-06 ---4.0SE-08 2.91E-10 1.34E-08 ---1.75E-10 1.53E-10 9.06E-09 --8.81E-11 8.32E-09 2.14E-09 ---4.04E-10 9.67E-11 --4.BOE-08 5.65E-09 ---1.48E-08 9.82E-06 1.12E-09 ---2.86E-09 1.22E-06 1.67E-07 4.93E-07 3.04E-08 4.03E-09 ---1.13E-08 1.06E-10 1.38E-11 ---3.84E-11 5.68E-08 3.48E-09 -2.19E-08 6.28E-07 2.17E-07 ---9.93E-10 5.61 E-10 -1.98E-09 Page 131 of 134 Revision 27 Lung GI-LLI --1.SOE-05 --5.41E-05 ---1.83E-04 --3.77E-05 --1.11E-05 ---2.36E-05 ---2.10E-05 -5.97E-05 --2.27E-05 --1.03E-04 ---7.11E-06 --3.81E-05 ---2.83E-06 --1.51E-06 -2.73E-06 -3.0BE-06 -1.84E-06 -2.62E-06 7.42E-05 1.91E-06 1.10E-05 2.0SE-06 6.64E-05 1.91E-06 6.09E-08 1.25E-06 3.54E-10 5.SBE-05 1.0SE-07 4.20E-05 1.77E-10 5.19E-06 9.26E-11 7.59E-07 ---9.77E-05 -6.86E-05 -2.48E-05 --5.73E-05 -1.71E-04 -4.29E-05 ---4.93E-06 ---3.60E-05 ---3.69E-05 -2.87E CH-ODCM-0001 Reference Use Off-$Jte Dose Calc.ulation Manual (ODCM) Page 132 of 134 Revision 27 Table 17 -Recommended Values for Other Parameters Parameter Definition Values Symbol fg Fraction of ingested produce grown in garden 0.76 of interest.

fQ Fraction of leafy vegetables grown in garden of 1.0 interest.

p Effective .surface density of soil (assumes a 240 kg/m 2 15 .cm plow layer, expressed in dry weight) r Fraction of deposited activity retained on crops, 0.25 leafy vegetables, or pasture grass 1.0 (iodines) 0.2 .(other particulates)

St Attenuation factor accounting for shielding 0.7 (maximum individual) provi_ded by residential ,structures 0.5 (general population) ti, Period of tong-term buildup for activity in 1.752E5hr sediment or soil (20 years) te Period of crop, leafy vegetable, or pasture 30 days (grass"cow-milk-man grass. exposure during growing season pathway) 60 days (crop/vegetation-man pathway) f Transport time from animal feed-milk-man 2 days (maximum individual) provided by residential structures 4 days (general population) bi Time delay between harvest of vegetation or crops and ingestion:

  • For ingestion of forage by animals Zero (pasture grass) 90 days (stored feed)
  • For ingestion of crops by man 1 day (leafy vegetables and* max. individual feed) 60 days (produce and max. individual) 14 days (general population) fs The fraction of daily feed that is pasture grass 1.0 while the animals graze on pasture. Mp The mi_xing ratio at the point of withdrawal of Site Discharge 7.14 drinking water. M.U.D .. Intake 30~8 fp Fraction of the year that animals graze on 0.5 pasture.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 133 of 134 Revision 27 Table 17 -Recommended Values for Other Parameters Parameter Definition Values Symbol tp Environmental transit time, release to receptor 12 hrs. (maximum) (add time from release to exposure individual 1 day (maximum individual) point to minimums shown for distribution) 1 day (general population) 7 days (population-,sport fish doses) 10 days (population--

commercial fish doses) ts Average time from slaughter of meat animal to 20days consumption Yv Agricultural productivity by unit area (measured 0.7 kg/m 2 (grass-cow-milk:-man in wet weight) pathway) 2.G kgim 2 (produce or ieafy veg~table ingested by man) w Shore-width factor for river shoreline 0.2 Aw Rate constant for removal of activity on plant or 0.0021 hr 1 leaf structures by weathering (corresponds to a 14-eday half-life)

%CO2 Fraction of C-14 used for organ dose 0.15 calculations from gaseous releases.

CH-ODCM-0001 Reference Use Off-Site Dose Calculation Manual (ODCM) Page 134 of 134 Revision 27 Table 18 -Estimated Doses Received by the General Public from On-Site Exposure

  • NOTE I
  • I The Dose Estimates are based on normal public activities conducted within the,* I Fort Calhoun Station Site Boundary.
  • Estimated Individual Dose Estimated Total Combined Distance Rate (mR/hour)

Annual Dose (mRem)e from Direct Inhalation Direct lnhalatlon Containment Exposure (Critical Exposure (Critical Location Direction (miles) (Total Body) OrganA) (Total Body) OrganA) Firing Range 200° 0.24 4.0BE-05 9.67E-06 5.0BE+OO 1.20E+OO Burn Pad 241° 0.33 1.95E-05 4.63E*06 1.41E-01 3.34E-02 On-Site Farming 11a* 0.52 2.12E-05 5.03E-06 2.38E-02 5.64E-03 On-Site Farming 200° 0.51 1.0JE-05 2.45E-06 2.30E-02 5.SOE-03 On-Site Farming 308° 0.50 2.77E-05 6.64E-06 4.66E-02 1.12E-02 Site Maintenance Admin Bldg 145° 0.20 1.18E-04 2.64E-05 5.SOE-02 1.33E-02 Site Maintenance Training Center 1eo 0 0.20 1.45E-04 3.SOE-05 6.78E-02 1.64E-02 A. Critical organ doses are based on adult thyroid. B. Estim*ated totals are based on summation of all individual doses for members of the General Public while within the Fort Calhoun Station site boundary.