Omaha Public Power District Fort Calhoun Station Unit No. 1 Annual Report For Technical Specification Section 5.9.4.a January 1, 2002 to December 31, 2002 DOCKET NO. 50-285 OPERATING LICENSE DPR-40
Omaha Public Power District Fort Calhoun Station Unit No. I Annual Report For Technical Specifications, Section 5.9.4.A January 1, 2002 to December 31, 2002
DOCKET NO. 50-285 OPERATING LICENSE DPR40 Annual Radiological Effluent Release Report This report is submitted in accordance with Section 5.9.4.a of the Technical Specifications of Fort Calhoun Station Unit No. 1, Facility Operating License DPR-40 for the period January 1, 2002 through December 31, 2002. The Effluent Report is presented in the format outlined in Regulatory Guide 1.21, Revision 1.
In addition, this report provides the results of quarterly dose calculations performed in accordance with the Offsite Dose Calculation Manual.
Results are presented by quarter for the period January 1, 2002 through December 31, 2002.
Further description of any changes made during the preceding twelve months to the Offsite Dose Calculation Manual and/or the Process Control Program for the Fort Calhoun Station are presented.
RC RECOMMENDS APPPO"'A-MAR 2 6 203 FeFC NITG. M1NUTgS Manager-Fort Calhoun Station
TABLE OF CONTENTS Section Section Title
- 1.
1.0 Introduction 1.1 Executive Summary 2.0 Supplemental Information 2.1 Regulatory Limits 2.2 Effluent Concentration Limits 2.3 Measurements and Approximations of Total Radioactivity 2.4 Estimation of Total Percent Error 2.5 Batch Releases 2.6 Abnormal Releases 3.0 Gaseous Effluents 4.0 Liquid Effluents 5.0 Solid Wastes 6.0 Related Information 6.1 Operability of Liquid and Gaseous Monitoring Instrumentation 6.2 Changes to Offsite Dose Calculation Manual (ODCM) or Process Control Program (PCP) 6.3 New Locations or Modifications for Dose Calculations or Environmental Monitoring 6.4 Noncompliance with Radiological Effluent Control Requirements 6.5 Modifications to Liquid and Gaseous Waste Treatment and Ventilation Exhaust Systems 6.6 Meteorological Monitoring Program 6.7 Assessment of Doses
- 11.
Quarterly Doses from Effluents, Offsite Dose Calculation Manual
TABLE OF CONTENTS Ill.
Radiological Effluent Releases, Technical Specification (5.9.4a)
Table 111.1; Batch Liquid and Gas Release Summary Table 111.2; Abnormal Batch Liquid and Gaseous Release Summary Table 111.3; Gaseous Effluents -Summation of All Releases Table 111.4; Gaseous Effluent Releases - Batch Mode Table 111.5; Gaseous Effluent Releases - Continuous Mode Table 111.6; Liquid Effluents - Summation of All Releases Table 111.7; Liquid Effluent Releases - Batch Mode Table 111.8; Liquid Effluent Releases - Continuous Mode IV.
Dose From Gaseous Effluents - GASPAR II Output Tables IV-A-1 through IV-A Receptor Dose Projections Table IV-B Dose Contributions at Unrestricted Area Boundary Table IV-C ALARA Annual Integrated Dose Summary V.
Dose From Liquid Effluents - LADTAP II Output Summary Dose Projections from Liquid Effluent Releases VI.
Radioactive Effluent Releases-Solid Radioactive Waste, Technical Specifications (5.9.4.a)
VIl.
ATTACHMENTS
- 1.
Offsite Dose Calculation Manual (ODCM) and Process Control Program (PCP) Revisions, Technical Specifications (5.17.d and 5.18.d)
- 2.
Joint Frequency Distribution Wind Direction vs. Wind Speed by Stability Class and Meteorological Data
- 3.
Annual Occupational Exposure Report, Technical Specification (5.9.1.b)
1.0 INTRODUCTION
This Annual Radiological Effluent Release Report, for Fort Calhoun Station Unit No. 1, is submitted as required by Technical Specification 5.9.4.a for the period January 1, 2002 through December 31, 2002.
1.1 Executive Summary The Radioactive Effluent Monitoring program for the year 2002 was conducted as described in the following report.
Major efforts were made to maintain the release of radioactive effluents to the environment as low as reasonably achievable. Activity released was significantly reduced due to the replacement of defective fuel in the spring of 2002.
The total gaseous activity released for 2002 was 2259.8 Curies. This was 32.14% less than the 3330 Curies released in 2001.
Dose contributions from gaseous effluents at the unrestricted area boundary were 2.20E-01 millirad maximum gamma air dose, and 7.12E-01 millirad maximum beta air dose. This was a decrease from the 2001 values of 3.24E-01 millirad and 1.19E+00 millirad respectively.
Total activity (excluding tritium, dissolved gases and alpha) released in 2002 in liquid effluents was 4.20E-01 Curies.
This was lower than the 2001 value of 5.60E-01 Curies.
The total tritium activity released in 2002 in liquid effluents was 293 Curies. This was an increase from the 2001 value of 175.4 Curies. This was due to an increase in liquid effluent releases during the 1st and 2nd quarters of 2002 when reactor coolant system tritium levels were higher.
The calculated whole body dose due to liquid effluents at the site discharge from all sources in 2002 was 1.69E-01 mRem. This was a decrease from the 2001 dose of 4.41 E-01 mRem.
The calculated critical organ dose due to liquid effluents at the site discharge from all sources in 2002 was 2.22E-01 mRem. This was a decrease from the 2001 dose of 5.94E-01 mRem.
1-1
The Fort Calhoun Station meteorological system achieved a cumulative availability rate of 94.41 % for the joint frequency parameters required by Regulatory Guide 1.23 of wind speed, wind direction and delta temperature.
There were no abnormal releases during 2002.
During 2002 there was one change to the Offsite Dose Calculations Manual (ODCM) and no changes to the Process Control Program (PCP).
For 2002, the total volume of buried solid radwaste was 23.30 cubic meters, essentially unchanged from the 21.8 cubic meters of solid waste buried in 2001. The total buried activity for 2002 was 952.76 Curies, 952 of which came from spent resin. This was an increase from the 2001 value of 175.4 Curies.
Overall, the radioactive effluent monitoring program was conducted in a manner to ensure the activity released and associated dose to the public were maintained as low as reasonably achievable.
2.0 SUPPLEMENTAL INFORMATION 2.1 Regulatory Limits The ODCM Radiological Effluent Control Specifications applicable to the release of radioactive material in liquid and gaseous effluents are described in the following sections.
2.1.1 Fission and Activation Gases (Noble Gases)
The release rate of radioactive material in airborne effluents shall be controlled such that the instantaneous concentrations of radionuclides do not exceed the values specified in 10 CFR 20 for airborne effluents at the unrestricted area boundary. To support plant operations, Supervisor - System Chemistry may increase this limit up to the limits specified in Technical Specification 5.16.1.g.
Technical Specification 5.16.1.g establishes the administrative control limit on the concentration resulting from radioactive material, other than noble gases, released in gaseous effluents to unrestricted areas conforming to ten times 10 CFR 20.1001-20.2401, Appendix B, Table 2, 1-2
Column 1. For noble gases, the concentration shall be limited to five times 10 CFR 20.1001-20.2401, Appendix B, Table 2, Column 1.
The air dose due to noble gases released in gaseous effluents to areas at or beyond the unrestricted area boundary shall be limited to the following:
- a.
During any calendar quarter: Less than or equal to 5 mrad for gamma radiation and less than or equal to 10 mrad for beta radiation, and
- b.
During any calendar year: Less than or equal to 10 mrad for gamma radiation and less than or equal to 20 mrad for beta radiation.
2.1.2 Dose - lodine-131, Radioactive Material in Particulate Form with Half Lives Greater than 8 Days (Other than Noble Gases) and Tritium
- a.
The dose to an individual or dose commitment to any organ of an individual in unrestricted areas due to the release of 1-131, radioactive material in particulate form with half-lives greater than eight days (other than noble gases), and tritium in airborne effluents shall not exceed 7.5 millirem from all exposure pathways during any calendar quarter.
- b.
The dose to an individual or dose commitment to any organ of an individual in unrestricted areas due to the release of 1-131, radioactive materials in particulate form with half-lives greater than eight days (other than noble gases), and tritium in airborne effluents shall not exceed 15 millirem from all exposure pathways during any calendar year.
2.1.3 Liquid Effluents The release rate of radioactive material in liquid effluents shall be controlled such that the instantaneous concentrations for radionuclides, other than dissolved or entrained noble gases, do not exceed the values specified in 10 CFR 20 for liquid 1-3
effluents at site discharge. To support plant operations, Supervisor - System Chemistry may increase this limit up to the limit specified in Technical Specifications 5.16.1.b.
Technical Specification 5.16.1.b establishes the administrative control limit on concentration of radioactive material, other than dissolved or entrained noble gases, released in liquid effluents to unrestricted areas conforming to ten times 10 CFR 20.1001-20.2401, Appendix B, Table 2, Column 2. For dissolved or entrained noble gases, the concentration shall be limited to 2.OE-04 ptCi/ml total activity.
The dose or dose commitment to a MEMBER OF THE PUBLIC from radioactive materials in liquid effluents released to unrestricted areas shall be limited to:
- a.
During any calendar quarter: Less than or equal to 1.5 mRem to the whole body and less than or equal to 5 mRem to any organ, and
- b.
During any calendar year: Less than or equal to 3 mRem to the whole body and less than or equal to 10 mRem to any organ.
2.1.4 Total Dose-Uranium Fuel Cycle The dose to any real individual from uranium fuel cycle sources shall be limited to ' 25 mRem to the total body or any organ (except the thyroid, which shall be limited to s 75 mRem) during each calendar year.
2.2 Effluent Concentration Limits (ECL) 2.2.1 Liquid Effluents The values specified in 10 CFR Part 20, Appendix B, Column 2 are used as the ECL for liquid radioactive effluents released to unrestricted areas. A value of 2.OE-04 pCi/ml is used as the ECL for dissolved and entrained noble gases in liquid effluents.
1-4
2.2.2 Gaseous Effluents The values specified in 10 CFR Part 20, Appendix B, Column 1 are used as the ECL for gaseous radioactive effluents released to unrestricted areas.
2.3 Measurements and Approximations of Total Radioactivity Measurements of total radioactivity in liquid and gaseous radioactive effluents were accomplished in accordance with the sampling and analysis requirements of Tables 3.1 and 3.2 of Part I of the ODCM.
2.3.1 Liquid Radioactive Effluents Each batch was sampled and analyzed for gamma emitting radionuclides using gamma spectroscopy, prior to release. Composite samples were analyzed monthly and quarterly for the Monitor and Hotel Waste Tanks. Composite samples were analyzed monthly in the onsite laboratory for tritium and gross alpha radioactivity using liquid scintillation and proportional counting techniques respectively.
Composite samples were analyzed quarterly for Sr-89, Sr-90 and Fe-55 by a contract laboratory (Teledyne Brown Engineering). A software program was used to project the total body and critical organ dose contribution at the unrestricted area boundary for each release and the percent contribution to the annual objective dose.
For continuous releases from the Steam Generator blowdown, daily grab samples were obtained for weekly, monthly and quarterly composites, in proportion to the rate of blowdown. Samples were analyzed using gamma spectroscopy techniques weekly. Composites were also analyzed monthly in the onsite laboratory for tritium and gross alpha radioactivity using liquid scintillation and proportional counting techniques, respectively. Composite samples were analyzed quarterly for Sr-89, Sr-90, and Fe-55 by a contract laboratory (Teledyne Brown Engineering).
1-5
2.3.2 Gaseous Radioactive Effluents Each gaseous batch release was sampled and analyzed for radioactivity prior to release. For release of Waste Gas Decay Tanks, noble gas grab samples were analyzed for gamma emitting radionuclides using gamma spectroscopy. For releases from the Containment Building, samples were taken using charcoal and particulate filters, in addition to noble gas and tritium grab samples, and analyzed for gamma emitting radionuclides prior to each release.
The results of the analysis and the total volume of effluent released were used to determine the total amount of radioactivity released in the batch mode. A software program was developed and installed that can project the total body and critical organ dose contribution at the unrestricted area boundary for each release and the percent contribution to the annual objective dose. This program also adds the projected dose to the current actual dose totals in a temporary file, until it is updated with actual release data at the completion of a purge.
Continuous release effluent pathways were continuously sampled using charcoal and particulate filters and analyzed weekly for gamma emitting radionuclides using gamma spectroscopy. Weekly particulate filters were analyzed for gross alpha radioactivity in the onsite laboratory using proportional counting techniques. Quarterly composites of particulate filters were analyzed for Sr-89 and Sr-90 by an offsite laboratory (Teledyne Brown Engineering).
2.4 Estimation of Total Percent Error The estimated total percent error is calculated as follows:
Total Percent Error = (E12 + E22 + E32 +... + En2)
Where En = Percent Error Associated with each contributing parameter.
Sample counting error is estimated by the Canberra Genie System Software for samples analyzed by gamma U
spectroscopy. This calculation can include the error 1-6
associated with peak area determination, gamma ray abundance, efficiency and half-life. Systematic error is estimated for gaseous and liquid effluent analyses and dilution and wastewater volume.
2.5
-,Batch Releases A summary of information for liquid and gaseous batch releases is included in Table 111-1.
2.6 Abnormal Releases Abnormal Releases are defined as unplanned and unmonitored releases of radioactive material from the site.
A summary of information for liquid and gaseous abnormal releases is included in Table 111-2.
3.0 GASEOUS EFFLUENTS The quantities of radioactive material released in gaseous effluents are summarized in Tables 111-3, 111-4 and 111-5. All radioactive material released in gaseous form is considered to be ground level releases.
4.0 LIQUID EFFLUENTS The quantities of radioactive material released in liquid effluents are summarized in Tables 111-6, 111-7 and 111-8.
5.0 SOLID WASTES The quantities of radioactive material released as solid effluents are summarized in Section VI.
6.0 RELATED INFORMATION
.6.1 Operability of Liquid and Gaseous Monitoring Instrumentation -
During the reporting period no instruments used to monitor radioactive effluent releases were in violation of the reportable instrument operability requirements listed in the ODCM.
1-7
6.2 Changes to the Offsite Dose Calculation Manual (ODCM) or Process Control Program (PCP)
During 2002 there was one change made to the ODCM and no changes made to the PCP.
6.3 New Locations or Modifications for Dose Calculations or Environmental Monitoring New receptor locations were identified in the 2002 Land Use Survey which resulted in changes to our environmental monitoring sample locations. These changes are reflected in the attached revision to the Offsite Dose Calculation Manual (ODCM).
6.4 Noncompliance with Radiological Effluent Control Requirements This section provides a list of any event that did not comply with the applicable requirements of the Radiological Effluent Controls given in the Offsite Dose Calculation Manual (ODCM). Detailed documentation concerning the evaluations and corrective actions is maintained onsite.
6.4.1 Abnormal Gaseous and Liquid Releases No abnormal releases were made during the calendar year of 2002.
6.4.2 Failure to Meet Specified Sampling Requirements During 2002 there were no instances in which specified sampling requirements were not met.
6.5 Modifications to Liquid and Gaseous Waste Treatment and Ventilation Exhaust SVstems During the reporting period no design modifications were approved nor implemented involving major changes to the Liquid and Gaseous Waste Treatment Systems.
6.6 Meteorological Monitoring Program A summary of hourly meteorological data, collected during 2002, is retained onsite. This data is available for review by the Nuclear Regulatory Commission upon request. Joint Frequency tables are included in Section VII, Attachment 2.
1-8
Real time hourly meteorological data is used to calculate the annual air effluent dose to individuals. For quarterly estimates during the year an annual average X/Q is used which is an average of the highest X/Qs calculated for each of the previous two years.
6.7 Assessment of Doses 6.7.1 Doses Due to Liquid Effluents Total body, skin, and organ dose for liquid releases were calculated in mRem for all significant liquid pathways using the annual configuration of the LADTAP II program. The site discharge location was chosen to present a most conservative estimate of dose for an average adult, teenager, child and infant.
A conservative approach is also presented by the assumption that Omaha and Council Bluffs receive all drinking water from the Missouri River.
The LADTAP II program in its annual configuration was also used to calculate the total body and organ doses for the population of 853,274 within a 50-mile radius of the plant (based on the 2000 census). The results of the calculations are listed in Section V.
The dose due to liquid effluents for total body and critical organ are also calculated quarterly using the methods in the ODCM. The results are listed in Section II.
6.7.2 Doses Due to Gaseous Effluents Total body, skin and organ doses from ground releases were calculated in mRem to an average adult, teenager, child, and infant in each receptor using the annual configuration of the GASPAR II program. Also, the doses to the same groups, in units of mrad, due to gamma and beta radiation carried by air, were computed using GASPAR II.
The GASPAR II program in its annual configuration was also used to calculate the ALARA integrated population dose summary for the total body, skin and organ doses in person-rem for all individuals within a 50-mile radius. The results of the calculations are shown in Section IV.
1-9
The dose due to gaseous effluents for total body gamma and beta noble gas air dose are calculated quarterly using the methods in the ODCM with an annual average X/Q. The results are listed in Section II.
6.7.3 Doses Due to 1-131. Tritium and Particulates with Half Lives Greater than 8 days.
The doses due to 1-131, Tritium and Particulates with half lives greater than 8 days for total body and critical organ dose are calculated quarterly using the highest of infant or child dose factors and an annual average XIQ. The results are listed in Section II for inhalation, ground and food.
6.7.4 Direct Radiation Dose to Individuals and Populations Direct radiation doses attributed to the gamma radiation emitted from the containment structure were not observed above local background at any TLD sample locations for this annual period.
6.7.5 40 CFR 190 Dose Evaluation ODCM Radiological Effluent Controls require dose evaluations to demonstrate compliance with 40 CFR Part 190 only if calculated yearly doses exceed two times the annual design objectives for liquid and/or gaseous effluents. At no time during 2002 were any of these limits exceeded, therefore, no evaluations were required.
1-10
SECTION II QUARTERLY DOSES FROM EFFLUENTS Offsite Dose Calculation Manual January 1, 2002 - December 31, 2002 11-1
Quarterly Dose Calculation Results January 1, 2002 through December 31, 2002 With the implementation of the Fort Calhoun Station Radiological Effluent Technical Specifications (RETS) on October 1, 1985, radiation doses in the unrestricted area from liquid and gaseous effluents must be calculated on a quarterly basis in accordance with the Offsite Dose Calculation Manual (ODCM). These calculations are performed to ensure the annual dose limits delineated in Appendix I of 10 CFR 50 and implemented by RETS are not exceeded. If the results of the quarterly calculations exceed fifty percent (50%) of the annual limits of Appendix I, actions are taken to reduce effluents so that the resultant doses do not exceed the annual limits during the remainder of the year and a special report is submitted to the Nuclear Regulatory Commission.
This section presents the results of the quarterly dose calculations performed during the period January 1, 2002 through December 31, 2002.
Details are shown as to the types, sources and resultant doses from the effluents, the annual limits and a comparison to the annual limits.
11-2
FORT CALHOUN STATION CHEMISTRY FORM FC-421 R6 QUARTERLY CUMULATIVE DOSE CONTRIBUTION FROM RADIOACTIVE EFFLUENTS FORT CALHOUN FIRST QUARTER 2002 DOSE PROJECTIONS I. Liquid Effluents:
Batch:
Continuous:
Totals:
ODCM Quarterly Objective:
Percent of Quarterly Obj:
ODCM Annual Objective:
YTD Percent ofAnnual Obj:
YTD Percent of Annual Obj:
Total Body Dose (mrem) 2.67E-02 0.00E+00 2.67E-02 1.50E+00 1.78 %
3.00E+00 0.89 %
Critical Organ Dose (mrem) 3.40E-02 0.00E+00 3.40E-02 5.OOE+00 0.68 %
1.00E+01 0.34 %
'_I II.
Gaseous Effluents:
Total Body Gamma Dose (mrad)
A. Noble Gas Air Dose:
3.23E-02 ODCM Quarterly Objective:
5.00E+00 Percent of Quarterly Obj:
0.65 %
ODCM Annual Objective:
1.00E+01 YTD_ ercetof Ann al_____0 32_
YTD Percent of Annual Obj:
0.32%
Total Body Beta Dose (mrad) 1.04E-01 1.OOE+01 1.04 %
2.00E+01 0.52 %
B. I-131, H-3, and Particulates with Half-lives > 8 Days:
Inhalation:
Ground and Food:
Totals:
ODCM Quarterly Objective:
Percent of Quarterly Obj:
ODCM Annual Objective:
YTD Percent of Annual Obj:
Total Body Dose (mrem) 2.46E-05 1.38E-04 1.63E-04 7.50E+00 0.00 %
1.50E+01 0.00 %
Critical Organ Dose (mrem) 3.02E-03 2.98E-02 3.28E-02 7.50E+00 0.44 %
1.50E+01 0.22 %
Reviewed by:
K 11-3
FORT CALHOUN STATION CHEMISTRY FORM FC-421 R6 QUARTERLY CUMULATIVE DOSE CONTRIBUTION FROM RADIOACTIVE EFFLUENTS FORT CALHOUN SECOND QUARTER 2002 DOSE PROJECTIONS I. Liquid Effluents:
Batch:
Continuous:
Totals:
ODCM Quarterly Objective:
Percent of Quarterly Obj:
ODCM Annual Objective:
YTD Percent ofAnnual___i:
YTD Percent of Annual Obj:
Total Body Dose (mrem) 9.95E-02 2.06E-08 9.95E-02 1.50E+00 6.63 %
- 3. OE+00 4.20 %
Critical Organ Dose (mrem) 1.33E-01 4.68E-08 1.33E-01 5.OOE+00 2.66 %
- 1. OE+01 1.66 %
II.~~~~~~~~~
~
~
~~
Gaeuflet:TtlBd am oa oyBt II. Gaseous Effluents:
Total Body Gamma Dose (mrad)
A. Noble Gas Air Dose:
2.44E-01 ODCM Quarterly Objective:
5.OOE+00 Percent of Quarterly Obj:
4.88 %
ODCM Annual Objective:
1.OOE+01 YTD_ Percento_
Annual_____
YTD Percent of Annual Obj:
2.76%
Total Body Beta Dose (mrad) 7.91E-01 1.OOE+01 7.91 %
2.00E+01 4.47 %
B. I-131, H-3, and Particulates with Half-lives > 8 Days:
Inhalation:
Ground and Food:
Totals:
ODCM Quarterly Objective:
Percent of Quarterly Obj:
ODCM Annual Objective:
_TDPercentofAnnual
_b__
YTD Percent of Annual Obj:
Total Body Dose (mrem) 5.65E-04 3.42E-03 3.98E-03 7.50E+00 0.05 %
1.50E+01 0.03 %
Critical Organ Dose (mrem) 5.06E-02 7.30E-01 7.81E-01 7.50E+00 10.41 %
1.50E+01 5.42 %
Reviewed by:
1 11-4
FORT CALHOUN STATION CHEMISTRY FORM FC-421 R6 QUARTERLY CUMULATIVE DOSE CONTRIBUTION FROM RADIOACTIVE EFFLUENTS FORT CALHOUN THIRD QUARTER 2002 DOSE PROJECTIONS I. Liquid Effluents:
Batch:
Continuous:
Totals:
ODCM Quarterly Objective:
Percent of Quarterly Obj:
ODCM Annual Objective:
_TDPercentofAnnual__b__
YTD Percent of Annual Obj:
Total Body Dose (mrem) 3.18E-02
- 0. OOE+00 3.18E-02 1.50E+00 2.12 %
3.OOE+00 5.27 %
Critical Organ Dose (mrem) 4.36E-02 0.OOE+00 4.36E-02 5.00E+00 0.87 %
1.OOE+01 2.10 %
NJ II.
Gaseous Effluents:
Total Body Gamma II. Gaseous Effluents:
Total Body Gamma Dose (mrad)
A. Noble Gas Air Dose:
1.26E-03 ODCM Quarterly Objective:
5.00E+00 Percent of Quarterly Obj:
0.03 %
ODCM Annual Objective:
1.OOE+01 YTD Percent of Annual Obj:
2.78 %
Total Body Beta Dose (mrad) 5.48E-03 1.OOE+01 0.05 %
2.OOE+01 4.50 %
B. I-131, H-3, and Particulates with Half-lives > 8 Days:
Inhalation:
Ground and Food:
Totals:
ODCM Quarterly Objective:
Percent of Quarterly Obj:
ODCM Annual Objective:
_T__PercentofAnnual_____
YTD Percent of Annual Obj:
Total Body Dose (mrem) 2.24E-05 1.24E-04 1.46E-04 7.50E+00 0.00 %
1.50E+01 0.03 %
Critical Organ Dose (mrem) 1.28E-03 1.84E-02 1.97E-02 7.50E+00 0.26 %
1.50E+01 5.55 Reviewed by:
11-5
FORT CALHOUN STATION CHEMISTRY FORM FC-421 R6 QUARTERLY CUMULATIVE DOSE CONTRIBUTION FROM RADIOACTIVE EFFLUENTS FORT CALHOUN FOURTH QUARTER 2002 DOSE PROJECTIONS I. Liquid Effluents:
Batch:
Continuous:
Totals:
ODCM Quarterly Objective:
Percent__ofQuarterly__b__
Percent of Quarterly Obj:
Total Body Dose (mrem) 9.55E-03 0.0OE+00 9.55E-03 1.50E+00 0.64 %
Critical Organ Dose (mrem) 1.22E-02 0.00E+00 1.22E-02 5.OOE+00 0.24 %
ODCM Annual Objective:
YTDPercentofAnnual__b__
YTD Percent of Annual Obj:
3. 00E+00 5.60 %
- 1. OOE+01 2.21 %
II.
Gaseous Effluents:
Total Body Gamma Total Body Beta II. Gaseous Effluents:
Total Body Gamma Dose (mrad)
A. Noble Gas Air Dose:
2.20E-01 ODCM Quarterly Objective:
5.00E+00 Percent of Quarterly Obj:
4.40 %
ODCM Annual Objective:
1.00E+01 YTD_
ercetofAnnal_____279_
YTD Percent of Annual Obj:
2.79%
Total Body Beta Dose (mrad) 7.12E-01 1.00E+01 7.12 %
2.OOE+01 4.51 %
B. I-131, H-3, and Particulates with Half-lives > 8 Days:
Inhalation:
Ground and Food:
Totals:
ODCM Quarterly Objective:
Percent of Quarterly Obj:
ODCM Annual Objective:
YTDPercentofAnnual_____
YTD Percent of Annual Ob j:
Total Body Dose (mrem) 4.91E-04 6.61E-03 7.11E-03 7.50E+00 0.09 %
1.50E+01 0.03 %
Critical Organ Dose (mrem) 4.21E-02 2.87E+00 2.91E+00 7.50E+00 38.83 %
1.50E+01 5.56 %
Reviewed by:
11-6
SECTION III RADIOLOGICAL EFFLUENT RELEASES Technical Specification (5.9.4a)
Table 111-1 Table 111-2 Table 111-3 Table 111-4 Table 111-5 Table 111-6 Table 111-7 Table 111-8 Batch Liquid and Gas Release Summary Abnormal Batch Liquid and Gaseous Release Summary Gaseous Effluents - Summation of all Releases Gaseous Effluent Releases - Batch Mode Gaseous Effluent Releases - Continuous Mode Liquid Effluents - Summation of all Releases Liquid Effluent Releases - Batch Mode Liquid Effluent Releases - Continuous Mode January 1, 2002 - December 31, 2002 111-1
(
((
f ( (e,
(Q C' (( j (, C (
C, ( (,
C
( I C
(I (
(
(C
( (I ( ( ('
C
( ( (
(
' (
C A
(
( ((
(,
TABLE III.1 BATCH LIQUID AND GASEOUS RELEASE
SUMMARY
JANUARY THROUGH DECEMBER 2002 A. Liquid Releases All Sources 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter 1.
2.
3.
4.
5.
6.
Number of Batch Releases:
Total Time Period for Batch Releases(min):
Maximum Time Period for Batch Releases(min):
Average Time Period for Batch Releases(min):
Minimum Time Period for Batch Releases(min):
Average Dilution Stream Flow During Periods of Release into the Missouri River(mls/min):
23 2,913 235 127 91 1.343E+09 100 17,883 565 179 9
8.519E+08 30 13, 844 9,353 461 103 1.284E+ 09 24 2, 772 128 116 106
- 1. 325E+09 B. Gaseous Releases All Sources 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter 1.
2.
3.
4.
5.
Number of Batch Releases:
Total Time Period for Batch Releases(min):
Maximum Time Period for Batch Releases(min):
Average Time Period for Batch Releases(min):
Minimum Time Period for Batch Releases(min):
16 63,978 5,547 3, 999 342 70 81, 315 6,967 1,162 56 18 67,535 5,369 3,752 352 18 69, 932 7,505 3, 885 150 III-2
TABLE III.2 ABNORMAL BATCH LIQUID AND GASEOUS RELEASE
SUMMARY
JANUARY THROUGH DECEMBER 2002 A. Liquid Releases All Sources Number of Releases:
Total Activity Releases(Ci):
1st Quarter 2nd Quarter 0
0 3rd Quarter 0
- 0. OOE+00 4th Quarter 0
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00 B. Gaseous Releases All Sources Number of Releases:
0 0
0 0
Total Activity Releases (Ci):
0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 III-3
(
(
(
(
t-(
(
(
(
f
(
(
(
(
(
(
t
(
(
(a
(
(
(
(
- t.
X
(
(a
(
(
(
(
t c
at a,
t
(,
(
(
(
(
TABLE III.3 GASEOUS EFFLUENTS--SUMMATION OF ALL RELEASES JANUARY THROUGH DECEMBER 2002 A.
Fission & Activation Gases Total Release (Ci):
Avg. Release Rate for period (uCi/sec):
Total Error(%): 33.98 1st Quarter 2.57E+02 3.35E+01 2nd Quarter 1.99E+03 2.56E+02 3rd Quarter 8.51E+00 1.08E+00 4th Quarter 4.29E+00 5.46E-01 B. -Iodines Total Release (Ci):
Avg. Release Rate for period (uCi/sec):
Total Error(%): 37.38 C.
Particulates Total Release (Ci):
Avg. Release Rate for period (uCi/sec):
Total Error(%): 49.17 Gross Alpha Total Error(%): 20.62 D.
Tritium Total Release (Ci):
Avg. Release Rate for period (uCi/sec):
Total Error(): 25.08 1.44E-03 1.87E-04 0.00E+00 0.OOE+00 1.06E-05 7.40E-02 9.63E-03 9.18E-03 1.18E-03 6.96E-06
- 8. 95E-07 8.97E-06
- 1. 84E+00 2.37E-01 2.28E-04 2.90E-05
- 0. OOE+00 0.OOE+00 6.33E-06 7.78E-02
- 9. 89E-03 4.41E-05 5.61E-06
- 0. OOE+00 0.OOE+00 1.03E-05 4.92E-02 6.25E-03 NOTE:
Values reported as zero are determined to be below the Lower Limit of Detection (LLD).
III-4
TABLE III.4 GASEOUS EFFLUENTS--GROUND LEVEL RELEASES JANUARY THROUGH DECEMBER 2002 Batch Mode Nuclides(Ci) 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter Fission & Activation Gases AR-41 KR-85 KR-85M KR-87 KR-88 XE-131M XE-133 XE-133M XE-135 XE-135M Totals for Period:
Iodines I-131 I-132 I-133 I-135 Totals for Period:
J 2.36E-01 1.49E+01 4.45E-02 0.OOE+00 3.67E-02
- 4. 11E+00
- 2. 18E+02 1.65E+00 7.57E-01
- 0. OOE+00 2.40E+02 0.00E+00 0.OOE+00 0.OOE+00 0.0OE+00 0.OOE+00 1.60E-01 8.97E+01 4.15E-02 1.61E-03 2.41E-02 3.93E+01 1.76E+03
- 1. 84E+01 6.79E+00
- 3. 98E-03 2.47E-01
- 5. 99E+00 2.04E-03
- 0. OOE+00 1.02E-03 8.42E-02 1.96E+00 2.64E-02 6.19E-02 0.OOE+00 2.40E-01 1.52E+00 2.75E-03 1.73E-04 1.68E-03 1.12E-02 2.34E+00 3.36E-02 8.77E-02 0.OOE+00 4.24E+00
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00 1.91E+03 8.38E+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Pariculates
-J CO-58 Totals for Period:
- 0. OOE+00
- 0. OOE+00 7.40E-02 0. OOE+00
- 1. 84E+00
- 0. OOE+00
- 7. 78E-02
- 0. OOE+00
- 4. 92E-02 NOTE:
Values reported as zero are determined to be below the Lower Limit of Detection (LLD).
III-5
TABLE II1.5 GASEOUS EFFLUENTS--GROUND LEVEL RELEASES JANUARY THROUGH DECEMBER 2002 Continuous Mode Nuclides(Ci)
Fission & Activation Gases AR-41 KR-85 KR-85M KR-87 KR-88 XE-131M XE-133 XE-133M XE-135 XE-135M Totals for Period:
Iodines I-131 I-132 I-133 I-135 Totals for Period:
1st Quarter 2nd Quarter 3rd Quarter 4th Quarter
- 0. OOE+00
- 0. OOE+00 0. OOE+00
- 0. OOE+00
- 0. OOE+00 0. OOE+00
- 1. 69E+01 o.OOE+00 3.76E-01
- 0. OOE+00
- 1. 73E+01 3.37E-04 8.80E-05 6.59E-04 3.56E-04 1.44E-03
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00 0.OOE+00
- 0. OOE+00 3.16E+00 7.03E+01 0.00E+00 1.47E-01
- 0. 00E+00 7.36E+01 8.41E-03 1.99E-04 5.74E-04 0.OOE+00
- 9. 18E-03
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00 0. OOE+00
- 0. OOE+00 0.OOE+00 0.OOE+00
- 0. OOE+00 1.29E-01 0.OOE+00 1.29E-01 2.12E-04 0.OOE+00 1.63E-05 0.OOE+00 2.28E-04
- 0. OOE+00
- 0. OOE+00 0.OOE+00 0.OOE+00
- 0. OOE+00 0.OOE+00 0.OOE+00
- 0. OOE+00 5.15E-02 0. OOE+00 5.15E-02
- 9. 74E-06
- 0. OOE+00 3.44E-05 0. OOE+00 4.41E-05 Particulates CO-58 Totals for Period:
0.OOE+00 6.96E-06
- 0. OOE+00 0.OOE+00
- 1. 06E-05
- 0. OOE+00 8.97E-06
- 0. OOE+00 6.22E-06
- 0. OOE+00 1.OOE-05 0.OOE+00 NOTE:
Values reported as zero are determined to be below the Lower Limit of Detection (LLD).
III-6
TABLE III.6 LIQUID EFFLUENTS--SUMMATION OF ALL RELEASES JANUARY THROUGH DECEMBER 2002 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter A. Fission & Activation Products Total Release (No Tritium, Gas, Alpha) (Ci):
1.27E-02 2.86E-01 8.58E-02 3.54E-02 Avg Diluted Concentration (uCi/mi):
3.72E-11 1.13E-09 2.40E-10 1.04E-10 10 CFR 20, App. B Limit 1.OOE-06 uCi/ml Percent of Limit (%):
3.72E-03 1.13E-01 2.40E-02 1.04E-02 Total Error (%):
25.29 B. Tritium Total Release (Ci):
8.19E+01 1.42E+02 1.92E+01 4.99E+01 Avg Diluted Concentration (uCi/ml):
2.40E-07 5.60E-07 5.37E-08 1.47E-07 10 CFR 20, App.
B Limit 1.OOE-03 uCl/ml Percent of Limit (%):
2.40E-02 5.60E-02 5.37E-03 1.47E-02 Total Error (%):
25.08 C. Dissolved & Entrained Gases Total Release (Ci):
3.20E-02
- 6. 37E-02
- 2. 68E-05
- 1. 96E-04 Avg Diluted Concentration (uCi/ml):
4.69E-05 1.26E-04 3.75E-08 2.88E-07 Total Error (%):
28.50 D. Gross Alpha Radioactivity Total Release (Ci):
3.1OE-03 3.22E-03 3.48E-03 7.75E-04 Total Error (%):
25.08 E. Volume of Waste Released Prior to Dilution (Liters):
4.91E+07 3.81E+07 4.97E+07 4.69E+07 F. Volume of Dilution Water This Period (Liters):
3.42E+11 2.53E+11 3.57E+11 3.39E+11 NOTE: Values reported as zero are determined to be below the Lower Limit of Detection (LLD).
III-7
TABLE III.7 LIQUID EFFLUENTS JANUARY THROUGH DECEMBER 2002 Batch Mode Nuclides(Ci)
Fission & Activation Cases AG-110M AM-241 AS-76 BA-139 BA-140 BE-7 BR-76 CD-109 CE-139 CE-141 CE-144 CO-57 CO-58 C0-60 CR-51 CS-134 CS-136 CS-137 FE-55 FE-59 HF-181 I-131 I-132 I-133 LA-140 LA-141 MN-54 MO-99 NB-95 NP-239 PR-144 RB-88 RH-103M RH-105 RU-103 SB-122 SB-124 SB-125 SB-126 SE-75 SN-113 SN-117M SR-90 TA-182 TC-99M TE-129 TE-129M TE-132 Y-90 ZR-95 Totals for Period:
1st Quarter 1.42E-04 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 6.81E-05 8.62E-05 2.12E-04 1.38E-03 9.87E-07 1.82E-03 1.41E-03 O.OOE+00 O.OOE+00 4.19E-04 O.OOE+00 1.02E-05 O.OOE+00 O.OOE+00 2.15E-06 O.OOE+00 2.20E-05 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 1.53E-05 7.13E-03 O.OOE+00 6.57E-06 O.OOE+00 O.OOE+00 5.86E-06 6.57E-07 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 5.86E-06 O.OOE+00 1.27E-02 2nd Quarter 5.82E-03 1.89E-05 3.41E-05 3.12E-05 2.27E-04 4.06E-05 1.72E-05 2.37E-04 5.47E-06 2.62E-04 6.61E-04 2.02E-05 2.06E-02 3.54E-03 1.5SE-02 6.OOE-03 5.96E-05 7.44E-03 1.41E-02 3.84E-04 4.35E-0S 5.OSE-02 2.98E-03 3.88E-04 1.24E-03 3.14E-04 5.97E-04 3.19E-04 4.15E-03 1.09E-04 6.61E-04 9.19E-05 1.16E-04 4.53E-06 4.67E-04 7.11E-05 7.98E-03 1.O1E-01 1.18E-03 O.OOE+00 8.59E-05 1.O1E-04 5.63E-05 2.74E-06 3.19E-04 6.09E-03 2.73E-02 2.95E-03 5.63E-05 1.90E-03 2.86E-01 3rd Quarter 4th Quarter 7.18E-03 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00
- 0. OOE+00 O.OOE+00 O.OOE+00 5.02E-05 1.24E-03 1.31E-04 2.83E-02 5.97E-03 5.58E-03 2.04E-03 O.OOE+00 2.59E-03 0.OOE+00 2.OOE-04 1.51E-04 4.11E-04 O.OOE+00 0.OOE+00 8.42E-05 O.OOE+00 9.68E-04 O.OOE+00 9.34E-03 O.OOE+00 1.24E-03
- 0. OOE+00 O.OOE+00 O.OOE+00 2.54E-04
- 0. OOE+00 5.37E-04 1.48E-02
- 0. OOE+00 4.11E-05 1.78E-04 O.OOE+00 O.OOE+00
- 9. 06E-06 0.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 3.45E-03
- 0. OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00
- 0. OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 2.98E-04 1.19E-04 1.66E-02 3.13E-03 5.02E-04 3.55E-04 O.OOE+00 5.46E-04 9.19E-04 2.85E-06
- 2. 96E-06 2.27E-05 O.OOE+00 O.OOE+00 3.25E-05
- 0. OOE+00 2.74E-04 O.OOE+00 3.OSE-03
- 0. OOE+00 2.98E-04 O.OOE+00
- 0. OOE+00 O.OOE+00 2.72E-05 O.OOE+00 6.70E-05 4.37E-03 O.OOE+00 2.35E-05 4.44E-05 O.OOE+00
- 0. OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 4.60E-03 1.20E-03 8.58E-02 3.54E-02 Dissolved & Entrained Cases AR-41 KR-BS XE-131M XE-133 XE-133M XE-135 Totals for Period:
O.OOE+00 1.11E-03
- 4. 88E-04 3.03E-02 9.67E-05 8.21E-06 3.20E-02 5.23E-06 O.OOE+00 1.76E-03 6.10E-02 5.37E-04 3.96E-04 6.37E-02 O.OOE+0O
- 0. OOE+00 O.OOE+00 2.68E-05 O.OOE+00 O.OOE+00 2.68E-05 O.OOE+00 O.OOE+00 O.OOE+00
- 1. 96E-04 O.OOE+00 O.OOE+00
- 1. 96E-04 Tritium and Gross Alpha ALPHA H-3 1.39E-04 8.19E+01 2.49E-03 1.42E+02 5.51E-04 1.92E+01 1.19E-04 4.99E+01 NOTE:
Values reported as zero are determiner U be below the Lower Limit of Detection (LLD) values.
TABLE III.8 LIQUID EFFLUENTS JANUARY THROUGH DECEMBER 2002 Continuous Mode Nuclides(Ci)
Fission & Activation Products I-131 Totals for Period:
1st Quarter 2nd Quarter 3rd Quarter 4th Quarter 0.OOE+00 2.15E-06 0.OOE+00 2.15E-06
- 0. OOE+00 0.OOE+00
- 0. OOE+00
- 0. 00E+00 Dissolved & Entrained Gases Totals for Period:
0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 Tritium and Gross Alpha ALPHA H-3 2.96E-03
- 0. 00E+00 7.31E-04
- 0. OOE+00
- 2. 93E-03
- 0. OOE+00
- 6. 56E-04 0.OOE+00 NOTE:
Values reported as zero are determined to be below Detection (LLD).
the Lower Limit of III-9
SECTION IV DOSE FROM GASEOUS EFFLUENTS Technical Specification 5.9.4a GASPAR II OUTPUT January 1, 2002 - December 31, 2002 IV-1
Radioactive Effluent Releases - First, Second, Third and Fourth Quarters 2002 GASEOUS EFFLUENTS Radioactive gaseous releases for the reporting period totaled 2.26E+03 Curies of inert gas. The gross gaseous activity release rates were 3.35E+02 ItCi/sec for the first quarter, 2.56E+02 IiCi/sec for the second quarter, 1.08E+00 gCi/sec for the third quarter, and 5.46E-01 jtCi/sec for the fourth quarter.
Radioactive halogens and Particulates with half-lives greater that eight days released during the reporting period totaled 1.09E-02 Curies. The halogen release rates were 1.87E-04 gCi/sec for the first quarter, 1.18E-03 IiCi/sec for the second quarter, 2.90E-05 [tCi/sec for the third quarter, and 5.61 E-06 jCi/sec for the fourth quarter. The release rates for Particulates with half-lives greater than eight days were O.OOE+00 p.Ci/sec for the first quarter, 8.95E-07 giCi/sec for the second quarter, O.OOE+00 jiCi/sec for the third quarter and 0.OOE+00 p.Ci/sec for the fourth quarter.
Radioactive tritium released during the reporting period totaled 2.04E+00 Curies. Gross alpha radioactivity released during the reporting period totaled 3.62E-05 Curies.
IV-2
POTENTIAL DOSES TO INDIVIDUALS AND POPULATIONS A.
Potential Annual Doses to Individuals from Gaseous Releases Total body, skin, and organ doses from ground releases were calculated in mRem to an average adult, teenager, child, and infant using the annual configuration of the GASPAR II program. Results to each receptor are shown in Tables IV-A-1 through IV-A-40. Also, the doses to the same groups, Table IV-B-1, in units of mrad, due to gamma and beta radiation carried by air, were computed using GASPAR II. In its annual configuration, GASPAR II assumes that all release rates are entered in curies per year (Ci/yr).
The inputs to GASPAR II for the annual period from January 1, 2002 through December 31, 2002 were as follows:
(1)
All gaseous effluents (2)
Entrained gases (Ar-41, Xe-131M, Xe-133M, Xe-1 33, Xe-135M, Xe-135, Kr-85M, Kr-87, and Kr-88) from liquid effluents.
(3)
Annual X/Qs at the actual receptor locations, which are corrected for open terrain and plume depletion, are calculated according to Regulatory Guideline 1.1 11. Also included are annual deposition rates corrected for the open terrain factor.
(4)
The production, intake and grazing fractions were as follows: 1.0 for leafy vegetables grown in garden of interest, 0.76 for produce grown in garden of interest, 0.5 for the pasture grazing season of the milk animal, 1.0 for pasture grazing season of the meat animal, and 8 g/m3 for the air water (humidity) concentrations.
(5)
All dose factors, transport times from receptor to individual, and usage factors are defined by Regulatory Guide 1.109 and NUREG-0172.
(6)
Site specific information, within a five-mile radius of the plant, on types of receptors located in each sector was used. That is, if a cow was not present in a sector, then the milk pathway for that sector was not considered. If it was present, then the actual sector distance was used.
IV-3
These inputs introduce a most conservative approach for the following reasons:
(1)
The open terrain and deposition corrections increase annual XIQs by a factor ranging between 1.0 and 4.0 (2)
The production, intake, and grazing fractions, as defined in the input definition statement, represent the environment in an extremely conservative manner.
B.
Potential Semiannual Doses to Population from Gaseous Releases The GASPAR II program in its annual configuration was also used to calculate the ALARA integrated population dose summary for the total body, skin, and organ doses in man-rem for all individuals within a 50-mile radius. The population-integrated dose is the summation of the dose received by all individuals and has units of man-thyroid-rem when applied to the summation of thyroid doses. The same inputs were used as in the individual case with the addition of the following:
(1)
A total population of 853,274 (based on the 2000 census) was used to define the sector segments within a 50-mile radius of the plant.
(2)
Production of milk, meat, and vegetation is based on 1973 annual data for Nebraska as recommended by the Nuclear Regulatory Commission for use in GASPAR II.
IV-4
TABLE IV-A-1 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
1 RES AT 4.57 MILES N ANNUALBETAAIRDOSE = 8.35E-03 MILLRADS ANNUALGAMMAAIRDOSE = 2.53E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+_________-+_________-+__________+__________+__________+_________-+
PLUME
- 1.47E-03 : 1.47E-03 : 1.47E-03 : 1.47E-03 : 1.47E-03 : 1.47E-03 : 1.56E-03 : 4.78E-03
-________+______-___+__________+_________-+________-_+________-_+________-_+_______-__+________-_+
GROUND
- 7.39E-07 : 7.39E-07 : 7.39E-07 : 7.39E-07 : 7.39E-07 : 7.39E-07 : 7.39E-07 : 8.95E-07
_______-_+__________+__________+__________+-_________+__________+__________+__________+__________+
INHAL ADULT 5.71E-06 5.33E-06 7.38E-07 6.18E-06 6.94E-06 3.48E-04 5.14E-06 5.12E-06
-________+______-___+_________-+_________-+________-_+________-_+________-_+________-_+________-_+
TEEN
- 5.93E-06 : 5.39E-06 : 1.04E-06 : 6.62E-06 : 7.66E-06 : 4.27E-04 : 5.19E-06 : 5.17E-06
-________+______-___+_______-__+_______-__+________-_+_______-__+________-_+________-_+________-_+
CHILD
- 5.36E-06 : 4.67E-06 : 1.41E-06 : 5.99E-06 : 6.90E-06 : 4.74E-04 : 4.58E-06 : 4.56E-06
-______-_+_____-____+________-_+________-_+________-_+________-_+________-_+_________-+_________-+
INFANT : 3.20E-06 : 2.66E-06 : 1.11E-06 : 3.94E-06 : 4.16E-06 : 4.32E-04 : 2.64E-06 : 2.63E-06
-________+______-___+_________-+__________+_________-+_______-__+_______-__+_______-__+________-_+
IV-5
(
(
(
(
QQK K K K K K K ( C y K C Q C K K_ (
K C C C K C C C C K K K_ ( K K C K K K K C K
( ( (C C C
( C
( C ( C
( (
( ( C ( ( ( ( ( ( C ( ( ( ( ( ( (\\ ( ( ( ( ( ( ( (,(
( ( (
TABLE IV-A-2 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
2 RES AT 1.93 MILES NNE ANNUALBETAAIRDOSE = 4.39E-02 MILLRADS ANNUALGAMMAAIRDOSE = 1.35E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+_____-____+________-_+_________-+__________+__________+__________+__________+_________-+
PLUME
- 7.87E-03 : 7.87E-03 : 7.87E-03 : 7.87E-03 : 7.87E-03 : 7.87E-03 : 8.31E-03 : 2.53E-02
-________+_____-____+________-_+________-_+_________-+________-_+________-_+_________-+_________-+
GROUND
- 4.43E-06 : 4.43E-06 : 4.43E-06 : 4.43E-06 : 4.43E-06 : 4.43E-06 : 4.43E-06 : 5.37E-06
_________+__________+__________+__________+__________+__________+__________+__________+__________+
INHAL ADULT 2.93E-05 2.72E-05 3.98E-06 3.18E-05 3.59E-05 1.86E-03 2.62E-05 2.61E-05
-_______+__________+__________+__________+__________+__________+__________+___--_______-+--+__-__+
TEEN
- 3.04E-05 : 2.75E-05 : 5.59E-06 : 3.42E-05 : 3.98E-05 : 2.29E-03 : 2.64E-05 : 2.63E-05
-________+______-___+__________+________
-+________-_+________-_+________-_+________-_+________-_+
CHILD
- 2.75E-05 : 2.38E-05 : 7.59E-06 : 3.09E-05 : 3.58E-05 : 2.54E-03 : 2.34E-05 : 2.32E-05
-________+______-___+________-_+________-_+_________-+________-_+________-_+________-_+________-_+
INFANT : 1.64E-05 : 1.36E-05 : 5.99E-06 : 2.05E-05 : 2.17E-05 : 2.32E-03 : 1.34E-05 : 1.34E-05
-________+_____-____+________-_+_______-_+_____
__-_+________-_+________-_+________-_+________-_+
IV-6
TABLE IV-A-3 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
3 RES AT 1.52 MILES NE ANNUAL BETAAIRDOSE = 4.99E-02 MILLRADS ANNUAL GAMMA AIRDOSE = 1.53E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+_________-+_________-+__________+__________+__________+_________-+
PLUME
- 8.91E-03 : 8.91E-03 : 8.91E-03 : 8.91E-03 : 8.91E-03 : 8.91E-03 : 9.40E-03 : 2.87E-02
-________+_____-____+_________-+________-_+________-_+________-_+_________-_+_____---_+-_________+
GROUND
- 4.41E-06 : 4.41E-06 : 4.41E-06 : 4.41E-06 : 4.41E-06 : 4.41E-06 : 4.41E-06 : 5.34E-06
_________+__________+__________+__________+__________+__________+__________+__________+__________+
INHAL ADULT 3.35E-05 3.11E-05 4.56E-06 3.63E-05 4.10E-05 2.13E-03 2.99E-05 2.98E-05
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
TEEN
- 3.48E-05 : 3.15E-05 : 6.41E-06 : 3.91E-05 : 4.55E-05 : 2.62E-03 : 3.02E-05 : 3.01E-05
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
CHILD
- 3.15E-05 : 2.72E-05 : 8.70E-06 : 3.54E-05 : 4.10E-05 : 2.92E-03 : 2.67E-05 : 2.66E-05
-________+______-___+______-___+_________-+________-_+________-_+________-_+________-_+________-_+
INFANT : 1.88E-05 : 1.55E-05 : 6.86E-06 : 2.34E-05 : 2.48E-05 : 2.66E-03 : 1.54E-05 : 1.53E-05
-________+_____-____+_________-+_________-+________-_+________-_+_______-__+________-_+________-_+
IV-7
( ( Q < < ( (~ ( (~ ( Q ( ( Q ( (. C ( (~ ( ( ( (~ (~ ( C (
.(
C
( (
C C
(
. C. ( C ( ( Q C (
( C ( ( C ( C C (C( ( C C
( ( C C ( (Cf (A C C C C
C C C C C C C C(
( ( (
(
(A
( (
TABLE IV-A-4 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
4 RES AT 4.79 MILES ENE ANNUALBETAAIR DOSE = 3.77E-03 MILLRADS ANNUALGAMMAAIRDOSE = 1.15E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+________-_+________-_+________-_+_________-+_________-+________-_+
PLUME
- 6.68E-04 : 6.68E-04 : 6.68E-04 : 6.68E-04 : 6.68E-04 : 6.68E-04 : 7.06E-04 : 2.16E-03
-________+______-___+_________-+________-_+________-_+________-_+________-_+________-_+________-_+
GROUND
- 1.87E-07 : 1.87E-07 : 1.87E-07 : 1.87E-07 : 1.87E-07 : 1.87E-07 : 1.87E-07 : 2.26E-07
_________+__________+__________+_______--_+_________-+__________+__________+__________+__________+
INHAL ADULT 2.55E-06 2.38E-06 3.33E-07 2.76E-06 3.10E-06 1.57E-04 2.29E-06 2.28E-06
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
TEEN
- 2.65E-06 : 2.40E-06 : 4.68E-07 : 2.96E-06 : 3.43E-06 : 1.92E-04 : 2.31E-06 : 2.30E-06
-________+______-___+________-_+_________-+_________-+________-_+________-_+________-_+________-_+
CHILD
- 2.39E-06 : 2.08E-06 : 6.36E-07 : 2.68E-06 : 3.09E-06 : 2.14E-04 : 2.04E-06 : 2.03E-06
-________+______-___+________-_+_________-+________-_+_________-+__________+-_________+_________-+
INFANT : 1.43E-06 : 1.19E-06 : 5.02E-07 : 1.76E-06 : 1.86E-06 : 1.95E-04 : 1.18E-06 : 1.17E-06
-________+_____-____+________-_+________-+________--+________-_+________-_+________-_+________-_+
IV-8
TABLE IV-A-5 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
5 RES AT 4.67 MILES E ANNUALBETA AIR DOSE = 5.68E-03 MILLRADS ANNUALGAMMAAIRDOSE = 1.73E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+ __
_ ___-+_________-+__________+__________+__________+__________+______--____+____--_
+
PLUME
- 1.01E-03 : 1.01E-03 : 1.01E-03 : 1.01E-03 : 1.01E-03 : 1.01E-03 : 1.06E-03 : 3.25E-03
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
GROUND
- 2.33E-07 : 2.33E-07 : 2.33E-07 : 2.33E-07 : 2.33E-07 : 2.33E-07 : 2.33E-07 : 2.82E-07
_________+__________+-_________+__________+__________+__________+__________+__________+__________+
INHAL ADULT 3.85E-06 3.59E-06 5.01E-07 4.16E-06 4.68E-06 2.36E-04 3.46E-06 3.45E-06
-________+__________+__________+__________+__________+__________+__________+_---+-______+-+___-__+
TEEN
- 4.OOE-06 : 3.63E-06 : 7.0SE-07 : 4.46E-06 : 5.17E-06 : 2.89E-04 : 3.49E-06 : 3.48E-06
-________+__________+__________+_________+__________+__________+__________+__--________+-________+
CHILD
- 3.61E-06 : 3.14E-06 : 9.57E-07 : 4.04E-06 : 4.66E-06 : 3.22E-04 : 3.08E-06 : 3.07E-06
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
INFANT : 2.15E-06 : 1.79E-06 : 7.55E-07 : 2.66E-06 : 2.81E-06 : 2.93E-04 : 1.78E-06 : 1.77E-06
-________+__________+__________+__________+__________+__________+__________+_--+-________-+___-__+
IV-9 C K K K Y K K C C K K K C K K K K K K K ( K K C K Q K K K K K K K C K K K K K K K K K
C ( ( C
( ( ( C (4
c
( c (c (tC,(
C C (C C
( CC C C C
(7 TABLE IV-A-6 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
6 RES AT 4.22 MILES ESE ANNUALBETAAIR DOSE = 9.14E-03 MILLRADS ANNUALGAMMAAIRDOSE = 2.77E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+__ _ ___--+_________-+__________+__________+__________+__________+______--____+____--_
+
PLUME
- 1.61E-03 : 1.61E-03 : 1.61E-03 : 1.61E-03 : 1.61E-03 : 1.61E-03 : 1.71E-03 : 5.23E-03
-________+______-___+_________-+_________-+____-_____+__________+__________+__________+_________-+
GROUND
- 4.48E-07 : 4.48E-07 : 4.48E-07 : 4.48E-07 : 4.48E-07 : 4.48E-07 : 4.48E-07 : 5.42E-07 INHAL ADULT 6.24E-06 5.82E-06 8.16E-07 6.76E-06 7.59E-06 3.84E-04 5.61E-06 5.59E-06
-________+______-___+_________-+______-___+_________-+________-_+________-_+________-_+________-_+
TEEN
- 6.48E-06 : 5.88E-06 : 1.15E-06 : 7.24E-06 : 8.39E-06 : 4.71E-04 : 5.67E-06 : 5.64E-06
-________+______-___+_________-+_________-+________-_+________-_+________-_+________-_+________-_+
CHILD
- 5.86E-06 : 5.09E-06 : 1.56E-06 : 6.55E-06 : 7.56E-06 : 5.24E-04 : 5.00E-06 : 4.98E-06
-________+______-___+_________-+_____
___-+_
_____-+_______-__+________-_+________-_+________-_+
INFANT : 3.50E-06 : 2.91E-06 : 1.23E-06 : 4.32E-06 : 4.56E-06 : 4.77E-04 : 2.88E-06 : 2.86E-06
-________+______-___+_________-+_________-+________-_+_______-__+________-_+_________-+________-_+
IV-10
TABLE IV-A-7 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
7 RES AT 1.67 MILES SE ANNUAL BETAAIRDOSE = 7.37E-02 MILLRADS ANNUALGAMMAAIRDOSE = 2.26E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+________-_+_________-+________-_+__________+__________+_________-+
PLUME
- 1.32E-02 : 1.32E-02 : 1.32E-02 : 1.32E-02 : 1.32E-02 : 1.32E-02 : 1.39E-02 : 4.24E-02
_________+__________+__________+__________+__________+__________+__________+__________+__________+
GROUND
- 8.05E-06 : 8.05E-06 : 8.05E-06 : 8.05E-06 : 8.05E-06 : 8.05E-06 : 8.05E-06 : 9.76E-06 INHAL ADULT 4.91E-05 4.57E-05 6.69E-06 5.34E-05 6.03E-05 3.13E-03 4.39E-05 4.38E-05
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
TEEN
- 5.11E-05
- 4.62E-05 : 9.40E-06 : 5.74E-05 : 6.68E-05 : 3.85E-03
- 4.44E-05
- 4.42E-05
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
CHILD
- 4.62E-05 : 4.OOE-05 : 1.28E-05 : 5.19E-05 : 6.02E-05 : 4.28E-03 : 3.92E-05 : 3.90E-05
-________+__________+__________+__________+__________+__________+__________+_--+-________-+___-__+
INFANT : 2.76E-05 : 2.28E-05 : 1.01E-05 : 3.44E-05 : 3.64E-05 : 3.90E-03 : 2.26E-05 : 2.24E-05 IV-11 C K K C C C & C ( (, ( ( ( ( t C C K C ( (~ ( ( K ( t ( ( ( C ( K C C K ( C C ( C ( ( (
( ( C C ( C ( ( (i(
( C (/(
( (C ( (,(
C C C C C ( ('(
CC ( ( ( ( (,C, TABLE IV-A-8 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
8 RES AT 0.94 MILES SSE ANNUAL BETAAIR DOSE = 2.61E-01 MILLRADS ANNUALGAMMAAIRDOSE = 8.07E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+_____-____+_________-+________-_+_________-+_________-+_________-+_________-+_________-+
PLUME
- 4.71E-02 : 4.71E-02 : 4.71E-02 : 4.71E-02 : 4.71E-02 : 4.71E-02 : 4.97E-02 : 1.51E-01
-________+_____-____+_________-+_________-+________-_+________-_+________-_+________-_+________-_+
GROUND
- 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 4.63E-05
-________+__________+__________+__________+__________+__________+__________+_---+-______-+____-__+
INHAL ADULT 1.73E-04 1.61E-04 2.40E-05 1.88E-04 2.13E-04 1.12E-02 1.54E-04 1.54E-04
-________+ __________+_____
____+____
+_
____+_____
____+__________+___--_______-+--+
+
TEEN
- 1.80E-04 : 1.63E-04 : 3.38E-05 : 2.03E-04 : 2.36E-04 : 1.38E-02 : 1.56E-04 : 1.55E-04
-________+ __________+___
__+
__+_
__+___
______+__________+_____--_____-+---+
+
CHILD
- 1.63E-04 : 1.40E-04 : 4.59E-05 : 1.83E-04 : 2.13E-04 : 1.53E-02 : 1.38E-04 : 1.37E-04
-________+ __________+__________+
+
+
_______+__
_______+_____--_____--+--+
+
INFANT : 9.73E-05 : 8.01E-05 : 3.62E-05 : 1.22E-04 : 1.29E-04 : 1.40E-02 : 7.93E-05 : 7.88E-05
-________+_____-____
+____
___-__+__
____-_+_
-______+___
-______+__________+__________+_________-+
IV-12
TABLE IV-A-9 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
9 RES AT 0.74 MILES S ANNUALBETAAIRDOSE = 3.24E-01 MILLRADS ANNUALGAMMAAIRDOSE = 1.OOE-01 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+__________+-
+___
_+
__-----+
_+_--___
_+
PLUME
- 5.85E-02 : 5.85E-02 : 5.85E-02 : 5.85E-02 : 5.85E-02 : 5.85E-02 : 6.18E-02 : 1.88E-01
-________+__________+-
+___
_+
__-----+
_+_--___
_+
GROUND
- 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 4.63E-05
-________+__________+--+
+_
+
+
+
__--+-+_____+__--_
+
INHAL ADULT 2.15E-04 2.00E-04 3.01E-05 2.34E-04 2.65E-04 1.40E-02 1.92E-04 1.91E-04
+-
+-------------------+-
+
+--
TEEN
- 2.24E-04 : 2.02E-04 : 4.23E-05 : 2.52E-04 : 2.94E-04 : 1.73E-02 : 1.94E-04 : 1.93E-04
+-
+-------------------+-
+
+
+--
CHILD
- 2.02E-04 : 1.75E-04 : 5.74E-05 : 2.28E-04 : 2.66E-04 : 1.92E-02 : 1.71E-04 : 1.70E-04
+-
+------------------
+
+
+---
INFANT : 1.21E-04 : 9.96E-05 : 4.53E-05 : 1.52E-04 : 1.61E-04 : 1.75E-02 : 9.85E-05 : 9.79E-05
+---IV-13----+-
+
-+
+
IV-13
( (~ C C I Q K K Q K K K K C K C
( C.
( C.
( K C K K C K C K C C K K C K C C C C C C
(.
( ((((
(C( (14' f44 ( (r(e(((Cl(t-l(
(4
(((C( (((((
fC
((
(<Cj
( (.( (:Q}
TABLE IV-A-10 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
10 RES AT 0.60 MILES SSW ANNUALBETAAIRDOSE = 3.64E-01 MILLRADS ANNUALGAMMAAIRDOSE = 1.13E-01 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+_________-+________-_+________-_+________-_+________-_+________-_+
PLUME
- 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.93E-02 : 2.10E-01
_________+__________+__________+_______--_+_______-__+______-___+__________+__________+__________+
GROUND
- 2.87E-05 : 2.87E-05 : 2.87E-05 : 2.87E-05 : 2.87E-05 : 2.87E-05 : 2.87E-05 : 3.47E-05 INHAL ADULT 2.41E-04 2.24E-04 3.38E-05 2.63E-04 2.98E-04 1.58E-02 2.15E-04 2.14E-04
-________+__________+__________+__________+_________+_________+__________+__--________+-_________+
TEEN
- 2.51E-04 : 2.27E-04 : 4.76E-05 : 2.83E-04 : 3.31E-04 : 1.94E-02 : 2.17E-04 : 2.16E-04
-________+______-___+_________-+________-_+________-_+________-_+________-_+________-_+________-_+
CHILD
- 2.27E-04 : 1.96E-04 : 6.46E-05 : 2.56E-04 : 2.98E-04 : 2.16E-02 : 1.92E-04 : 1.91E-04
-________+______-___+________-_+
_______-_+_______
-_+_________-+__________+__________+_________-+
INFANT : 1.36E-04 : 1.12E-04 : 5.10E-05 : 1.70E-04 : 1.80E-04 : 1.97E-02 : 1.11E-04 : 1.10E-04
-________+_____-____+________-_+_________-+_______-_+_______-__+_________-+_________-+________-_+
IV-14
TABLE IV-A-11 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
11 RES AT 0.73 MILES SW ANNUALBETAAIR DOSE = 2.22E-01 MILLRADS ANNUALGAMMAAIRDOSE = 6.85E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+___
___-__+________-_
+__________+__________+__________+__________+_____---____-+__-
+
PLUME
- 4.OOE-02 : 4.OOE-02 : 4.OOE-02 : 4.OOE-02 : 4.OOE-02 : 4.OOE-02 : 4.22E-02 : 1.28E-01 GROUND
- 1.43E-05 : 1.43E-05 : 1.43E-05 : 1.43E-05 : 1.43E-05 : 1.43E-05 : 1.43E-05 : 1.74E-05
_________+__________+__________+__________+__________+__________+__________+__________+__________+
INHAL ADULT 1.47E-04 1.36E-04 2.05E-05 1.60E-04 1.81E-04 9.57E-03 1.31E-04 1.30E-04
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
TEEN
- 1.53E-04 : 1.38E-04 : 2.88E-05 : 1.72E-04 : 2.01E-04 : 1.18E-02 : 1.32E-04 : 1.32E-04
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
CHILD
- 1.38E-04 : 1.19E-04 : 3.91E-05 : 1.56E-04 : 1.81E-04 : 1.31E-02 : 1.17E-04 : 1.16E-04
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
INFANT : 8.27E-05 : 6.80E-05 : 3.08E-05 : 1.03E-04 : 1.10E-04 : 1.l9E-02 : 6.73E-05 : 6.68E-05
-________+__________+__________+__________+__________+__________+__________+_--+-________-+___-__+
IV-15
( C C C C ( C K C C C ( C C C C C C C C ( ( C C C C C C C C C C C C C C C C C C C C C
( ( ( (1/2(
( ( ( (7(
((#('((
('C C (:CKYJC'
( ('C (((
U/C~('C ( C (QQ(~
C ( (,(:(,
TABLE IV-A-12 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
12 RES AT 1.06 MILES WSW ANNUALBETAAIR DOSE = 8.71E-02 MILLRADS ANNUALGAMMA_AIR_DOSE = 2.69E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+__________+__________+__________+_________+__________+__________+__--________+-________+
PLUME
- 1.57E-02 : 1.57E-02 : 1.57E-02 : 1.57E-02 : 1.57E-02 : 1.57E-02 : 1.66E-02 : 5.03E-02
-________+__________+__________+__________+___
______+_________+__________+__--________+-________+
GROUND
- 6.05E-06 : 6.05E-06 : 6.05E-06 : 6.05E-06 : 6.05E-06 : 6.05E-06 : 6.05E-06 : 7.33E-06
-________+______-___+_________-+________-_+_
______-+________-_+________-_+________-_+________-_+
INHAL ADULT 5.76E-05 5.36E-05 7.92E-06 6.26E-05 7.08E-05 3.70E-03 5.14E-05 5.12E-05
-________+_____-____+_________-+_________-+
____-+_
______-_+_______-__+________-_+________-_+
TEEN
- 5.99E-05 : 5.42E-05 : 1.11E-05 : 6.74E-05 : 7.85E-05 : 4.55E-03 : 5.20E-05 : 5.17E-05
_________+__________+__________+__________+_________-+__________+__________+__________+__________+
CHILD
- 5.42E-05 : 4.68E-05 : 1.51E-05 : 6.10E-05 : 7.08E-05 : 5.06E-03 : 4.59E-05 : 4.56E-05 INFANT : 3.24E-05 : 2.67E-05 : 1.19E-05 : 4.04E-05 : 4.28E-05 : 4.61E-03 : 2.64E-05 : 2.63E-05
-________+______-___+________-_+________-_+__
_____-_+__
______-+________-_+________-_+________-_+
IV-16
TABLE IV-A-13 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
13 RES AT 1.20 MILES W ANNUALBETAAIRDOSE = 7.05E-02 MILLRADS ANNUALGAMMAAIRDOSE = 2.16E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+________-_+________-_+________-_+_________-+_________-+________-_+
PLUME
- 1.26E-02 : 1.26E-02 : 1.26E-02 : 1.26E-02 : 1.26E-02 : 1.26E-02 : 1.33E-02 : 4.06E-02
-________+______-___+_________-+_________-+________-_+_______-__+________-_+________-_+________-_+
GROUND
- 4.58E-06 : 4.58E-06 : 4.58E-06 : 4.58E-06 : 4.58E-06 : 4.58E-06 : 4.58E-06 : 5.55E-06
_________+__________+__________+__________+__________+__________+__________+__________+__________+
INHAL ADULT 4.71E-05 4.38E-05 6.45E-06 5.12E-05 5.78E-05 3.02E-03 4.21E-05 4.19E-05
-________+______-___+________-_+________-_+________-_+________-_+__________+_________-+________-_+
TEEN
- 4.90E-05 : 4.43E-05 : 9.07E-06 : 5.50E-0S : 6.41E-05 : 3.71E-03 : 4.25E-05 : 4.23E-05
-________+______-___+__________+_________-+________-_+_______-__+________-_+________-_+________-_+
CHILD
- 4.43E-05 : 3.83E-05 : 1.23E-05 : 4.98E-05 : 5.78E-05 : 4.13E-03 : 3.75E-05 : 3.73E-05
_________+__________+__________+__________+__________+__________+__________+__________+__________+
INFANT : 2.65E-05 : 2.18E-05 : 9.72E-06 : 3.30E-05 : 3.49E-05 : 3.76E-03 : 2.16E-05 : 2.15E-05 IV-17 (t ('
(N C C (~ t
(. (N (N (, (
C C
( (
. C C C (N t C ( ( C ( C C ( C C C C C C C C C C C C C
(I (C
('( CC((((R
( ((C (C
C C C C(
7(
C
(.(
( ( (
(;CCJt
( ('C ( (4
((( 'C ((
TABLE IV-A-14 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
14 RES AT 2.26 MILES WNW ANNUALBETAAIR DOSE = 3.68E-02 MILLRADS ANNUALGAMMAAIRDOSE = 1.13E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+_________-+_________-+________-_+________-_+________-_+________-_+
PLUME
- 6.59E-03 : 6.59E-03 : 6.59E-03 : 6.59E-03 : 6.59E-03 : 6.59E-03 : 6.96E-03 : 2.12E-02
_________+__________+__________+__________+__________+__________+__________+__________+__________+
GROUND
- 1.90E-06 : 1.90E-06 : 1.90E-06 : 1.90E-06 : 1.90E-06 : 1.90E-06 : 1.90E-06 : 2.30E-06 INHAL ADULT 2.45E-05 2.29E-05 3.32E-06 2.67E-05 3.01E-05 1.55E-03 2.20E-05 2.19E-05
-________+______-_
_+__
-+
-+
-_-+
-______+_________-+________-_+________-_+
TEEN 2.55E-05 : 2.31E-05 : 4.67E-06 : 2.86E-05 : 3.33E-05 : 1.91E-03 : 2.22E-05 : 2.21E-05
-________+______-___+__________+_________-+________-_+________-_+________-_+________-_+________-_+
CHILD
- 2.31E-05 : 2.00E-05 : 6.34E-06 : 2.59E-05 : 3.OOE-05 : 2.12E-03 : 1.96E-05 : 1.95E-05
-________+_____-____+_________-+_______--_+_____-_-+__
____-+_______-__+________-_+________-_+
INFANT : 1.38E-05 : 1.14E-05 : 5.OOE-06 : 1.71E-05 : 1.81E-05 : 1.94E-03 : 1.13E-05 : 1.12E-05
-________+_____-____+________-_+____
-+
______--+_____
__-_+________-_+________-_+________-_+
IV-18
TABLE IV-A-15 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
15 RES AT 2.40 MILES NW ANNUAL BETA AIR DOSE = 3.45E-02 MILLRADS ANNUALGAMMAAIRDOSE = 1.06E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+_____-____+________-_+_________-+_________-+_________-+__________+__________+_________-+
PLUME
- 6.16E-03 : 6.16E-03 : 6.16E-03 : 6.16E-03 : 6.16E-03 : 6.16E-03 : 6.51E-03 : 1.98E-02
-________+______-___+_________-+_________-+_________-+-_________+_________-+________-_+________-_+
GROUND
- 2.37E-06 : 2.37E-06 : 2.37E-06 : 2.37E-06 : 2.37E-06 : 2.37E-06 : 2.37E-06 : 2.87E-06
_________+__________+__________+__________+__________+__________+__________+__________+__________+
INHAL ADULT 2.30E-05 2.14E-05 3.12E-06 2.50E-05 2.82E-05 1.46E-03 2.06E-05 2.05E-05
-________+______-___+_________-+_________-+________-_+________-_+_______-__+________-_+________-_+
TEEN
- 2.39E-05 : 2.16E-05 : 4.38E-06 : 2.68E-05 : 3.12E-05 : 1.79E-03 : 2.08E-05 : 2.07E-05
-_______+__________+__________+__________+__________+__________+__________+__--________+-________+
CHILD
- 2.16E-05 : 1.87E-05 : 5.95E-06 : 2.43E-05 : 2.81E-05 : 1.99E-03 : 1.83E-05 : 1.83E-05
-________+__________+__________+__________+__________+__________+__________+_---+-______-+____-__+
INFANT : 1.29E-05 : 1.07E-05 : 4.69E-06 : 1.61E-05 : 1.70E-05 : 1.82E-03 : 1.06E-05 : 1.05E-05
_________+__________+_-________+__________+__________+__________+__________+__________+__________+
IV-l9 C C & ( (~ C C (. C C C C
( C C (
. C C C (~ C C (. C C C C ( C C C C C C C C C Q C C C.
TABLE IV-A-16 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
16 RES AT 2.08 MILES NNW ANNUALBETAAIRDOSE = 4.12E-02 MILLRADS ANNUALGAMMAAIRDOSE = 1.26E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-_+_- _____--_+__________+____
+__
__+
+__-----
+
+
-+_
+
PLUME
- 7.34E-03 : 7.34E-03 : 7.34E-03 : 7.34E-03 : 7.34E-03 : 7.34E-03 : 7.75E-03 : 2.37E-02
______-__+_-________+_________-+_________-+_______-__+________-_+________-_+_______-__+________-_+
GROUND
- 4.55E-06 : 4.55E-06 : 4.55E-06 : 4.55E-06 : 4.55E-06 : 4.55E-06 : 4.55E-06 : 5.52E-06
_________+__________+__________+__________+__________+__________+__________+__________+__________+
INHAL ADULT 2.77E-05 2.58E-05 3.73E-06 3.OOE-05 3.39E-05 1.75E-03 2.48E-05 2.47E-05
_________+______-___+_________-+_________-+_________-+________-_+________-_+________-_+________-_+
TEEN 2.88E-05 : 2.60E-05 : 5.24E-06 : 3.23E-05 : 3.75E-05 : 2.15E-03 : 2.50E-05 : 2.49E-05
______-__+_-________+_________-+_________-+________-_+________-_+________-_+_______-__+________-_+
CHILD
- 2.60E-05 : 2.25E-05 : 7.11E-06 : 2.92E-05 : 3.38E-05 : 2.39E-03 : 2.21E-05 : 2.20E-05
______-__+_-________+_________-+_________-+_______-
_+________-_+________-_+________-_+________-_+
INFANT : 1.55E-05 : 1.29E-05 : 5.61E-06 : 1.93E-05 : 2.04E-05 : 2.17E-03 : 1.27E-05 : 1.27E-05
______-_+-
-+--
+-
-+
IV-20
TABLE IV-A-17 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
17 VEG AT 3.29 MILES NE ANNUALBETAAIRDOSE = 7.77E-03 MILLRADS ANNUALGAMMAAIRDOSE = 2.37E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-_-_+_________-+_________-+_________-+________-_+________-_+________-_+________-_+
PLUME
- 1.38E-03 : 1.38E-03 : 1.38E-03 : 1.38E-03 : 1.38E-03 : 1.38E-03 : 1.46E-03 : 4.46E-03
_________+__________+__________+__________+__________+__________+__________+__________+__________+
GROUND
- 5.65E-07 : 5.65E-07 : 5.65E-07 : 5.65E-07 : 5.65E-07 : 5.65E-07 : 5.65E-07 : 6.84E-07 VEGET ADULT 1.43E-05 1.12E-05 7.11E-06 1.86E-05 2.59E-05 3.34E-03 8.44E-06 8.44E-06
-________+__________+__________+_________+__________+__________+__________+__--________+-________+
TEEN
- 1.74E-05 : 1.26E-05 : 1.03E-05
- 2.40E-05 : 3.44E-05 : 4.20E-03
- 9.65E-06
- 9.65E-06
_________+__________+__________+__________+-_________+__________+__________+__________+__________+
CHILD
- 2.85E-05 : 1.72E-05 : 2.36E-05 : 3.87E-05 : 5.40E-05 : 7.86E-03 : 1.50E-05 : 1.50E-05 IV-21 C C C C C C C C C. C C C C C C C C C C C C K C C C C C C C C C C C C C C C C ( C C C
( K( ( C (OC
( C('( K' C
(
C(
'Q (:(
(,( ( ( f
( ( C(,( C r,:( )( )(,
C iC K
(
K i(
,(
TABLE IV-A-18 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
18 VEG AT 4.67 MILES E ANNUALBETAAIRDOSE = 5.68E-03 MILLRADS ANNUALGAMMAAIRDOSE = 1.73E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+__
_ ___--+_________-+__________+__________+__________+__________+______--____+____--_
+
PLUME
- 1.01E-03 : 1.01E-03 : 1.01E-03 : 1.01E-03 : 1.01E-03 : 1.01E-03 : 1.06E-03 : 3.25E-03
-________+______-___+_________-+________-_+_________-+________-_+_________-+________-_+________-_+
GROUND
- 2.33E-07 : 2.33E-07 : 2.33E-07 : 2.33E-07 : 2.33E-07 : 2.33E-07 : 2.33E-07 : 2.82E-07
_________+__________+__________+__________+__________+__________+__________+__________+__________+
VEGET ADULT 8.66E-06 7.39E-06 2.94E-06 1.05E-05 1.35E-05 1.38E-03 6.24E-06 6.24E-06
-________+______-___+_________-+________-_+________-_+________-_+________-_+________-_+________-_+
TEEN
- 1.03E-05
- 8.35E-06 : 4.24E-06
- 1.31E-05 : 1.74E-05 : 1.74E-03 : 7.14E-06 : 7.14E-06
-________+______-___+__________+_________-+________-_+________-_+________-_+________-_+________-_+
CHILD
- 1.67E-05 : 1.20E-05 : 9.75E-06 : 2.09E-05 : 2.72E-05 : 3.25E-03 : 1.11E-05 : 1.11E-05
-________+______-___+_________-+________-_+_________-+_________-+_________-+__________+_________-+
IV-22
TABLE IV-A-19 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
19 VEG AT 1.74 MILES SE ANNUALBETAAIRDOSE = 6.89E-02 MILLRADS ANNUALGAMMAAIRDOSE = 2.11E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+ __
___-+
__________+ __________+__________+__________+__________+______--____+____--_
_ +
PLUME
- 1.23E-02 : 1.23E-02 : 1.23E-02 : 1.23E-02 : 1.23E-02 : 1.23E-02 : 1.30E-02 : 3.97E-02
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
GROUND
- 7.42E-06 : 7.42E-06 : 7.42E-06 : 7.42E-06 : 7.42E-06 : 7.42E-06 : 7.42E-06 : 8.99E-06
_________+__________+__________+__________+__________+__________+__________+__________+__________+
VEGET ADULT 1.51E-04 1.11E-04 9.33E-05 2.08E-04 3.03E-04 4.38E-02 7.42E-05 7.42E-05
-________+__________+__________+__________+__________+__________+__________+_---+-______-+____-__+
TEEN
- 1.86E-04 : 1.23E-04 : 1.35E-04 : 2.74E-04 : 4.10E-04 : 5.51E-02 : 8.49E-05 : 8.49E-05
-________+__________+__________+__________+__________+__________+__________+_---+-______-+____-__+
CHILD
- 3.09E-04 : 1.60E-04 : 3.10E-04 : 4.43E-04 : 6.43E-04 : 1.03E-01 : 1.32E-04 : 1.32E-04
-________+__________+__________+__________+__________+__________+__________+_---________+-+___-__+
IV-23 C ( ( ( ( ( C ( ( C ( ( C ( C C C C C C ( C C (~ ( ( C C C ( C C C ( C C C (
C
TABLE IV-A-20 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
20 VEG AT 0.94 MILES SSE ANNUALBETA AIR DOSE = 2.61E-01 MILLRADS ANNUALGAMMAAIRDOSE = 8.07E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
_______-+__________+__________+__________+__________+__________+__________+__--________+-________+
PLUME
- 4.71E-02 : 4.71E-02 : 4.71E-02 : 4.71E-02 : 4.71E-02 : 4.71E-02 : 4.97E-02 : 1.51E-01
_______-+__________+__________+__________+__________+__________+__________+__--________+-________+
GROUND
- 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 4.63E-05
_______-+__________+__________+__________+__________+__________+__________+__--________+-________+
VEGET ADULT 6.72E-04 4.65E-04 4.80E-04 9.65E-04 1.46E-03 2.25E-01 2.78E-04 2.78E-04
_______-+__________+__________+__________+__________+__________+__________+__--________+-________+
TEEN
- 8.40E-04 : 5.15E-04 : 6.93E-04 : 1.29E-03 : 1.99E-03 : 2.83E-01 : 3.18E-04 : 3.18E-04
_________+-_________+_______-__+________-_+_________-+_________-+________-_+________-_+________-_+
CHILD
- 1.41E-03 : 6.40E-04 : 1.59E-03 : 2.10E-03 : 3.12E-03 : 5.30E-01 : 4.95E-04 : 4.95E-04
______-__+-_________+________-_+_______-__+_________-+_________-+__________+__________+_________-+
IV-24
TABLE IV-A-21 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
21 VEG AT 0.74 MILES S ANNUALBETAAIRDOSE = 3.24E-01 MILLRADS ANNUALGAMMAAIRDOSE = 1.OOE-01 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+_________-+__________+__________+__________+__________+_________-+
PLUME
- 5.85E-02 : 5.85E-02 : 5.85E-02 : 5.85E-02 : 5.85E-02 : 5.85E-02 : 6.18E-02 : 1.88E-01
-________+__________+__________+__________+__________+__________+__________+_--+-________-+___-__+
GROUND
- 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 3.82E-05 : 4.63E-05
_________+__________+__________+__________+__________+__________+__________+__________+__________+
VEGET ADULT 7.40E-04 5.32E-04 4.80E-04 1.03E-03 1.52E-03 2.25E-01 3.46E-04 3.46E-04
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
TEEN
- 9.17E-04 : 5.93E-04 : 6.93E-04 : 1.37E-03 : 2.07E-03 : 2.83E-01 : 3.96E-04 : 3.96E-04
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
CHILD
- 1.53E-03 : 7.60E-04 : 1.59E-03 : 2.22E-03 : 3.24E-03 : 5.30E-01 : 6.14E-04 : 6.14E-04
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
IV-25 C C C C C C C C C C C C C ( C C C C C C C C C C C C C Q C ( C C ( C C C C C C C C C C
(4 C; *( (,O('(t(((
( 'Q(.
C(4?'( '(QCo (KKKl)((
(( (C Cc
C tC-8 iCt (K'(O)(
4(O' TABLE IV-A-22 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
22 VEG AT 0.60 MILES SSW ANNUALBETAAIRDOSE = 3.64E-01 MILLRADS ANNUALGAMMAAIRDOSE = 1.13E-01 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+__ _ ___--+_________-+__________+__________+__________+__________+______--____+____--_
+
PLUME
- 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.93E-02 : 2.10E-01
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
GROUND
- 2.87E-05 : 2.87E-05 : 2.87E-0S : 2.87E-05 : 2.87E-05 : 2.87E-05 : 2.87E-05 : 3.47E-05
-________+__________+__________+__________+__________+__________+__________+_---+-______-+____-__+
VEGET ADULT 6.83E-04 5.28E-04 3.60E-04 9.03E-04 1.27E-03 1.69E-01 3.88E-04 3.88E-04
-________+_____-____+_________-+_________-+________-_+________-_+________-_+________-_+________-_+
TEEN
- 8.35E-04 : 5:92E-04 : 5.20E-04
- 1.17E-03
- 1.70E-03
- 2.13E-01 : 4.44E-04
- 4.44E-04
-________+______-___+__________+_________-+________-_+________-_+________-_+________-_+________-_+
CHILD
- 1.37E-03 : 7.99E-04 : 1.19E-03 : 1.89E-03 : 2.66E-03 : 3.98E-01 : 6.89E-04 : 6.89E-04
-________+_____-____+________-_+_
_____-_+__
_--+___
___-_+_________-+________-_+-_________+
IV-26
TABLE IV-A-23 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
23 VEG AT 1.31 MILES SW ANNUALBETAAIRDOSE = 5.03E-02 MILLRADS ANNUALGAMMAAIRDOSE = 1.55E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+________-_+_________-+_________-+__________+-_________+_________-+________-_+
PLUME
- 9.01E-03 : 9.01E-03 : 9.01E-03 : 9.01E-03 : 9.01E-03 : 9.01E-03 : 9.51E-03 : 2.90E-02
-________+_____-____+________-_+_________-+__________+-_________+__________+_________-+________-_+
GROUND
- 3.17E-06 : 3.17E-06 : 3.17E-06 : 3.17E-06 : 3.17E-06 : 3.17E-06 : 3.17E-06 : 3.84E-06
_________+__________+__________+__________+__________+__________+__________+__________+__________+
VEGET ADULT 8.67E-05 6.95E-05 3.98E-05 1.11E-04 1.52E-04 1.87E-02 5.40E-05 5.40E-05
-________+______-___+__________+_________-+________-_+________-_+________-_+________-_+________-_+
TEEN
- 1.05E-04 : 7.81E-05 : 5.75E-05 : 1.42E-04 : 2.OOE-04 : 2.35E-02 : 6.18E-05 : 6.18E-05
-________+_____-____+________-_+_________-+__________+-_________+__________+_________-+________-_+
CHILD
- 1.72E-04 : 1.08E-04 : 1.32E-04 : 2.29E-04 : 3.14E-04 : 4.40E-02 : 9.59E-05 : 9.59E-05
-________+______-___+________-_+________-_+_________-+__________+__________+__________+_________-+
IV-27 C C C C C C C C C C C C C C C C C C ( C C C ( ( ( ( ( C C ( Q ( C C C C C ( C C
('C ('C (;,.'~( O('f C) C o cc( cc' (2(((
t(KK()(C' ( f ( <
(,C)(
(
((Q((t(
i((
(
TABLE IV-A-24 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
24 VEG AT 1.21 MILES WSW ANNUALBETAAIRDOSE = 5.74E-02 MILLRADS ANNUALGAMMAAIRDOSE = 1.77E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+ __
_ ___--+__________+ __________+__________+__________+__________+______--____+____--_
+
PLUME
- 1.03E-02 : 1.03E-02 : 1.03E-02 : 1.03E-02 : 1.03E-02 : 1.03E-02 : 1.09E-02 : 3.31E-02
-________+______-___+_________-+_________-+________-_+________-_+________-_+_________-+________-_+
GROUND
- 4.12E-06 : 4.12E-06 : 4.12E-06 : 4.12E-06 : 4.12E-06 : 4.12E-06 : 4.12E-06 : 4.99E-06
-________+______-___+_________-+________-_+________-_+________-_+________-_+________-_+________-_+
VEGET ADULT 1.04E-04 8.17E-05 5.18E-05 1.36E-04 1.89E-04 2.43E-02 6.16E-05 6.16E-05
-________+______-___+__________+_________-+________-_+________-_+________-_+________-_+________-_+
TEEN
- 1.27E-04 : 9.17E-05 : 7.47E-05 : 1.75E-04 : 2.51E-04 : 3.06E-02 : 7.04E-05 : 7.04E-05
-________+_____-____+________-_+________-_+________-_+_________-+________-_+_________-+_________-+
CHILD
- 2.08E-04 : 1.25E-04 : 1.72E-04 : 2.82E-04 : 3.93E-04 : 5.72E-02 : 1.09E-04 : 1.09E-04
-________+______-___+_________-+________-_+________-_+________-_+________-_+________-_+________-_+
IV-28
TABLE IV-A-25 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
25 VEG AT 1.20 MILES W ANNUALBETAAIRDOSE = 7.05E-02 MILLRADS ANNUALGAMMAAIRDOSE = 2.16E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+________-_+________-_+_________-+_________-+__________+_________-+
PLUME
- 1.26E-02 : 1.26E-02 : 1.26E-02 : 1.26E-02 : 1.26E-02 : 1.26E-02 : 1.33E-02 : 4.06E-02
-________+______-___+________-_+________-_+_________-+________-_+_________-+_________-+________-_+
GROUND
- 4.58E-06 : 4.58E-06 : 4.58E-06 : 4.58E-06 : 4.58E-06 : 4.58E-06 : 4.58E-06 : 5.55E-06
_________+__________+__________+__________+_-________+__________+__________+__________+__________+
VEGET ADULT 1.23E-04 9.83E-05 5.76E-05 1.58E-04 2.17E-04 2.71E-02 7.59E-05 7.59E-05
-________+______-___+________-_+________-_+_________-+_________-+__________+-_________+_________-+
TEEN
- 1.49E-04 : 1.1OE-04 : 8.32E-05 : 2.03E-04 : 2.87E-04 : 3.41E-02 : 8.68E-05 : 8.68E-05
-________+_____-____+_________-+_________-+________-_+________-_+________-_+________-_+________-_+
CHILD
- 2.44E-04 : 1.52E-04 : 1.91E-04 : 3.27E-04 : 4.50E-04 : 6.37E-02 : 1.35E-04 : 1.35E-04
-________+______-___+_________-+_________-+________-_+________-_+________-_+________-_+________-_+
IV-29 Q Q & ( Q ( ( ( Q ( ( Q ( ( &
& (
(. ( & Q ( ( ( (.
( C ( C ( C C C C C ( ( ( ( (
(,(
('C Q C.(.(;( *(4 (C
(((
I,
(-jCQ C(fIwfl8(h('
>(Q.(E
(,CQ(
( (A( ( fC
('
TABLE IV-A-26 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
26 VEG AT 2.97 MILES WNW ANNUALBETAAIRDOSE = 1.78E-02 MILLRADS ANNUALGAMMAAIRDOSE = 5.45E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+_________-+________-_+________-_+________-_+________-_+________-_+
PLUME
- 3.17E-03 : 3.17E-03 : 3.17E-03 : 3.17E-03 : 3.17E-03 : 3.17E-03 : 3.35E-03 : 1.02E-02
-________+_____-____+_________-+_________-+________-_+________-_+________-_+________-_+________-_+
GROUND
- 8.46E-07 : 8.46E-07 : 8.46E-07 : 8.46E-07 : 8.46E-07 : 8.46E-07 : 8.46E-07 : 1.02E-06
_________+__________+__________+__________+__________+__________+__________+__________+__________+
VEGET ADULT 2.82E-05 2.35E-05 1.07E-05 3.47E-05 4.55E-05 5.01E-03 1.94E-05 1.94E-05
-________+_____-____+_________-+_________-+________-_+________-_+________-_+________-_+________-_+
TEEN
- 3.38E-05 : 2.66E-05 : 1.54E-05 : 4.38E-05 : 5.93E-05 : 6.31E-03 : 2.22E-05 : 2.22E-05
-________+_____-____+________-_+________-_+________-_+________-_+________-_+_________-+_________-+
CHILD
- 5.47E-05 : 3.77E-05 : 3.54E-05 : 7.01E-05 : 9.29E-05 : 1.18E-02 : 3.45E-05 : 3.45E-05
-________+_____-____ +_________-+__________+__________+________
_+_- -
+----------
+-_________ +
IV-30
TABLE IV-A-27 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
27 VEG AT 2.40 MILES NW ANNUAL BETAAIRDOSE = 3.45E-02 MILLRADS ANNUALGAMMAAIRDOSE = 1.06E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+ __
___-+
__________+ __________+__________+__________+__________+______--____+____--_
+
PLUME
- 6.16E-03 : 6.16E-03 : 6.16E-03 : 6.16E-03 : 6.16E-03 : 6.16E-03 : 6.51E-03 : 1.98E-02 GROUND
- 2.37E-06 : 2.37E-06 : 2.37E-06 : 2.37E-06 : 2.37E-06 : 2.37E-06 : 2.37E-06 : 2.87E-06
_________+__________+___-______+__________+__________+__________+__________+__________+__________+
VEGET ADULT 6.16E-05 4.87E-05 2.98E-05 7.98E-05 1.10E-04 1.40E-02 3.71E-05 3.71E-05
-________+__________+__________+__________+__________+__________+__________+_--+-________-+___-__+
TEEN
- 7.48E-05 : 5.47E-05 : 4.30E-05 : 1.03E-04 : 1.46E-04 : 1.76E-02 : 4.25E-05 : 4.25E-05
_________+__________+__________+__________+__________+__________+__________+__________+__________+
CHILD
- 1.23E-04 : 7.50E-05 : 9.88E-05 : 1.65E-04 : 2.29E-04 : 3.29E-02 : 6.59E-05 : 6.59E-05 IV-31 C C C C C C C ( K C ( C C C C C (1 C C ( C C C C C C C K ( C C C C C C C C C C C C C C
0CC( C (oC'Q0(e Cu CR C (C
(' ('(\\CC Cc
( ( (
C(
(
'(I"(
, C( ((
C
/
TABLE IV-A-28 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
28 VEG AT 4.01 MILES NNW ANNUALBETAAIRDOSE = 9.93E-03 MILLRADS ANNUALGAMMAAIRDOSE = 3.02E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+ __
+ __________+ __________+__________+__________+__________+______--____+____--_
+
PLUME
- 1.76E-03 : 1.76E-03 : 1.76E-03 : 1.76E-03 : 1.76E-03 : 1.76E-03 : 1.85E-03 : 5.69E-03
-________+______-___+_________-+________-_+________-_+_________-+________-_+_________-+_________-+
GROUND
- 8.97E-07 : 8.97E-07 : 8.97E-07 : 8.97E-07 : 8.97E-07 : 8.97E-07 : 8.97E-07 : 1.09E-06
-________+______-___+__________+_________-+________-_+________-_+________-_+________-_+________-_+
VEGET ADULT 2.03E-05 1.54E-05 1.13E-05 2.72E-05 3.88E-05 5.32E-03 1.10E-05 1.10E-05
-________+_____-____+________-_+________-+________-_+________-_+________-_+_________-+________-_+
TEEN
- 2.49E-05 : 1.72E-05 : 1.64E-05 : 3.55E-05
- 5.20E-05
- 6.70E-03
- 1.25E-05 : 1.25E-05
-________+______-___+__________+_________-+________-_+________-_+________-_+________-_+________-_+
CHILD
- 4.10E-05 : 2.29E-05 : 3.76E-05 : 5.73E-05 : 8.16E-05 : 1.25E-02 : 1.95E-05 : 1.95E-05
-________+_____-____+________-_+_______--+________-_+________-_+________-_+________-_+________-_+
IV-32
TABLE IV-A-29 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
29 BEEF AT 4.72 MILES NNE ANNUALBETAAIRDOSE = 6.86E-03 MILLRADS ANNUALGAMMAAIRDOSE = 2.09E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+-_________+_________-+_________-+_______-__+_______-__+________-_+________-_+
PLUME
- 1.22E-03 : 1.22E-03 : 1.22E-03 : 1.22E-03 : 1.22E-03 : 1.22E-03 : 1.29E-03 : 3.94E-03
_________+-_________+_______-__+________-_+________-_+________-_+________-_+________-_+________-_+
GROUND
- 5.14E-07 : 5.14E-07 : 5.14E-07 : 5.14E-07 : 5.14E-07 : 5.14E-07 : 5.14E-07 : 6.23E-07
_________+__________+__________+__________+__________+__________+__________+__________+__________+
MEAT ADULT 1.32E-06 1.21E-06 2.92E-07 1.50E-06 1.80E-06 1.38E-04 1.08E-06 1.08E-06
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
TEEN
- 8.28E-07
- 7.22E-07
- 2.43E-07
- 9.84E-07
- 1.23E-06
- 9.98E-05
- 6.43E-07 : 6.43E-07
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
CHILD
- 1.04E-06
- 8.25E-07
- 4.50E-07
- 1.23E-06
- 1.52E-06
- 1.50E-04 : 7.79E-07
- 7.79E-07
-________+_____-____+________-_+_________-+________-_+_______-__+________-_+________-_+________-_+
IV-33 (Q
y
((( ( (((
(~(( (
K
(
C
(
Q
(. ( (~ C
( (K' k v CC C
( (Q(
(C C C
(8)rC'C '(
CK)(. -X;Q(, ' C ( C C '(,(Q( Q,(
iCJ (1 (
I(C' I( ( (Q'C(
(OI O f)CtC;t '( ( ( ( (A(X TABLE IV-A-30 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
30 BEEF AT 4.91 MILES E ANNUALBETAAIRDOSE = 5.28E-03 MILLRADS ANNUALGAMMAAIRDOSE = 1.60E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+__ _ ___--+_________-+__________+__________+__________+__________+______--____+____--_
+
PLUME
- 9.35E-04 : 9.35E-04 : 9.35E-04 : 9.35E-04 : 9.35E-04 : 9.35E-04 : 9.87E-04 : 3.03E-03
-________+______-___+__________+_________-+________-_+________-_+________-_+________-_+________-_+
GROUND
- 2.17E-07 : 2.17E-07 : 2.17E-07 : 2.17E-07 : 2.17E-07 : 2.17E-07 : 2.17E-07 : 2.63E-07
-________+__________+__________+_________
+__
____+__________+__________+___--_______---+____-__+
MEAT ADULT 9.39E-07 8.93E-07 1.23E-07 1.01E-06 1.14E-06 5.86E-05 8.37E-07 8.37E-07
-________+__________+__________+__________+__-______+__________+__________+__--________+-________+
TEEN
- 5.76E-07 : 5.32E-07 : 1.02E-07 : 6.42E-07 : 7.46E-07 : 4.24E-05 : 4.99E-07 : 4.99E-07
-________+______-___+__________+_________-+________-_+________-_+________-_+________-_+________-_+
CHILD
- 7.14E-07 : 6.23E-07 : 1.90E-07 : 7.96E-07 : 9.18E-07 : 6.38E-05 : 6.04E-07 : 6.04E-07
-________+_____-____+________-_+_________-+_______-_+________-_+________-_+_________-+________-_+
IV-34
TABLE IV-A-31 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
31 BEEF AT 4.59 MILES SE ANNUALBETAAIR DOSE = 8.35E-03 MILLRADS ANNUALGAMMAAIRDOSE = 2.53E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+_______-__+________-_+_________-+__________+_________-+_________-+
PLUME
- 1.47E-03 : 1.47E-03 : 1.47E-03 : 1.47E-03 : 1.47E-03 : 1.47E-03 : 1.56E-03 : 4.78E-03
-________+______-___+_________-+-_________+_________-+________-_+________-_+________-_+________-_+
GROUND
- 6.47E-07 : 6.47E-07 : 6.47E-07 : 6.47E-07 : 6.47E-07 : 6.47E-07 : 6.47E-07 : 7.83E-07
_________+__________+__________+__________+__________+__________+__________+__________+__________+
MEAT ADULT 1.64E-06 1.50E-06 3.68E-07 1.86E-06 2.24E-06 1.74E-04 1.33E-06 1.33E-06
-________+______-___+__________+_________-+________-_+_______-__+_______-__+________-_+________-_+
TEEN
- 1.03E-06 : 8.94E-07 : 3.06E-07
- 1.22E-06 : 1.53E-06 : 1.26E-04
- 7.95E-07 : 7.95E-07
-________+______-___+_________-+_________-+________-_+_______-__+________-_+________-_+________-_+
CHILD
- 1.29E-06 : 1.02E-06 : 5.67E-07
- 1.53E-06 : 1.90E-06
- 1.89E-04
- 9.63E-07 : 9.63E-07
-________+______-___+________-_+_______-__+________-_+_______-__+________-_+________-_+________-_+
IV-35 C(~
Ct C ( ( ( (' ( ( ( C C C ( (~ C C ( ( ( C ( ( ( C (. ( ( ( C ( ( ( ( C ( C4 ( (
('4(T CCi c<\\(c~scc'c (.U&C(^
CX'>CC(^(
( (.QQ((f~ (KC Cl
( (*Q('C'( ('(
f ( Ci( e TABLE IV-A-32 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
32 BEEF AT 1.82 MILES SSE ANNUALBETAAIRDOSE = 5.50E-02 MILLRADS ANNUALGAMMAAIRDOSE = 1.69E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+ __
+ __________+ __________+__________+__________+__________+______--____+____--_
+
PLUME 9.87E-03 : 9.87E-03 : 9.87E-03 : 9.87E-03 : 9.87E-03 : 9.87E-03 1.04E-02 : 3.17E-02
-________+______-___+__________+_________-+________-_+________-_+________-_+________-_+________-_+
GROUND
- 7.60E-06 : 7.60E-06 : 7.60E-06 : 7.60E-06 : 7.60E-06 : 7.60E-06 : 7.60E-06 : 9.21E-06 MEAT ADULT 1.21E-05 1.04E-05 4.30E-06 1.47E-05 1.90E-05 2.02E-03 8.49E-06 8.49E-06
-________+______-___+__________+_________-+________-_+________-_+________-_+________-_+________-_+
TEEN
- 7.77E-06 : 6.22E-06 : 3.57E-06 : 1.01E-05 : 1.37E-05 : 1.47E-03 : 5.06E-06 : 5.06E-06
-________+______-___+__________+_________-+__
_____-_+________-_+________-_+________-_+________-_+
CHILD
- 9.96E-06 : 6.81E-06 : 6.63E-06 : 1.28E-05 : 1.71E-05 : 2.21E-03 : 6.13E-06 : 6.13E-06
-________+______-___+_________-+__________+_________-+________-_+________-_+________-_+________-_+
IV-36
TABLE IV-A-33 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
33 BEEF AT 2.60 MILES S ANNUALBETAAIRDOSE = 1.42E-02 MILLRADS ANNUALGAMMAAIRDOSE = 4.40E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+
___-+
__________+ __________+______
___+__________+__________+______--____+____--_
+
PLUME
- 2.57E-03 : 2.57E-03 : 2.57E-03 : 2.57E-03 : 2.57E-03 : 2.57E-03 : 2.71E-03 : 8.24E-03
-________+_________+__________+__________+__________+__________+__________+__--________+-________+
GROUND
- 1.45E-06 : 1.45E-06 : 1.45E-06 : 1.45E-06 : 1.45E-06 : 1.45E-06 : 1.45E-06 : 1.76E-06
_________+_____-____+__________+__________+__________+__________+__________+__________+__________+
MEAT ADULT 2.86E-06 2.55E-06 8.19E-07 3.36E-06 4.19E-06 3.86E-04 2.18E-06 2.18E-06
-________+______-___+__________+_________-+________-_+________-_+_______-__+________-_+________-_+
TEEN
- 1.82E-06 : 1.52E-06
- 6.80E-07 : 2.26E-06
- 2.94E-06
- 2.79E-04
- 1.30E-06
- 1.30E-06
-________+______-___+__________+_________-+________-_+________-_+________-_+________-_+________-_+
CHILD
- 2.31E-06
- 1.70E-06
- 1.26E-06
- 2.85E-06
- 3.66E-06
- 4.21E-04
- 1.58E-06
- 1.58E-06
-________+______-___+________-_+________-_+_________-+________-_+________-_+________-_+________-_+
IV-37
( C l, ( ( ( ( ( ( ( C C C C t C ( (C ( ( ( C ( K (
C (C
( C ( ( C C ( (. C & ( C ( C K.
( ( f(C ( ((
C,
(.&(((
( C(.
( V.
c
( ( (.(
(
(C(
(
('(
('(
TABLE IV-A-34 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
34 BEEF AT 0.60 MILES SSW ANNUALBETAAIRDOSE = 3.64E-01 MILLRADS ANNUALGAMMAAIRDOSE = 1.13E-01 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+ __
___-+
__________+ __________+__________+__________+__________+______--____+____--_
+
PLUME
- 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.93E-02 : 2.10E-01
_________+__________+__________+__________+__________+__________+__________+__________+__________+
GROUND
- 2.87E-05 : 2.87E-05 : 2.87E-05 : 2.87E-05 : 2.87E-05 : 2.81E-05 : 2.87E-05 : 3.47E-05 MEAT I
ADULT
- 6.92E-05 6.31E-05 1.62E-05 7.90E-05 9.55E-05 7.65E-03 5.58E-05 5.58E-05
-________+__________+__________+_____
____+_________+__________+__________+__--________+-________+
TEEN
- 4.35E-05 : 3.76E-05 : 1.35E-05 : 5.21E-05 : 6.57E-05
- 5.53E-03
- 3.32E-05 : 3.32E-05
-________+_____-____+________-_+________-+_______-__+________-_+________-_+________-_+________-_+
CHILD
- 5.47E-05 : 4.28E-05 : 2.50E-05 : 6.54E-05 : 8.15E-05 : 8.34E-03 : 4.03E-05 : 4.03E-05
-________+_____-____+_________-+______-_-_+___
__-__+________-_+__________+__________+_________-+
IV-38
TABLE IV-A-35 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
35 BEEF AT 0.73 MILES SW ANNUALBETAAIR DOSE = 2.22E-01 MILLRADS ANNUAL_GAMMAAIRDOSE = 6.85E-02 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
_________+__________+__________+__________+__________+__________+__________+__________+__________+
PLUME
- 4.OOE-02 : 4.OOE-02 : 4.OOE-02 : 4.OOE-02 : 4.OOE-02 : 4.OOE-02 : 4.22E-02 : 1.28E-01:
GROUND
- 1.43E-05 : 1.43E-05 : 1.43E-05 : 1.43E-05 : 1.43E-05 : 1.43E-05 : 1.43E-05 : 1.74E-05
_-_______+__________+__________+__________+__________+__________+__________+__________+__________+
MEAT ADULT 4.07E-05 3.76E-05 8.10E-06 4.56E-05 5.38E-05 3.83E-03 3.40E-05 3.40E-05
-________+__________+__________+__________+__________+__________+__________+_---________+-+___-__+
TEEN
- 2.53E-05 : 2.24E-05 : 6.73E-06 : 2.97E-05 : 3.64E-05 : 2.77E-03 : 2.02E-05 : 2.02E-05
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
CHILD
- 3.17E-05 : 2.58E-05 : 1.25E-05 : 3.71E-05 : 4.51E-05 : 4.17E-03 : 2.45E-05 : 2.45E-05
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
IV-39 K (, ( ( ( ( ( ( ( C ( ( ( ( K ( ( (. C ( ( C ( ( ( C. C ( C ( ( C C ( K( C K
( (
( (. C
( C C C ( C C;t (KY }(
( (
C C C (
' (C ( (
-C; C (, ( C C CS C (W<(
$ C C ('
Ct C C.(
TABLE IV-A-36 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
36 BEEF AT 2.42 MILES WSW ANNUAL BETAAIRDOSE = 1.07E-02 MILLRADS ANNUAL_GAMMAAIRDOSE = 3.26E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+__
_ ___-+_________-+__________+__________+__________+__________+______--____+____--_
+
PLUME
- 1.90E-03 : 1.90E-03 : 1.90E-03 : 1.90E-03 : 1.90E-03 : 1.90E-03 : 2.OOE-03 : 6.15E-03
-________+______-___+_________-+_________-+________-_+_________-+_________-+_________-+________-_+
GROUND
- 6.67E-07 : 6.67E-07 : 6.67E-07 : 6.67E-07 : 6.67E-07 : 6.67E-07 : 6.67E-07 : 8.08E-07
-________+______-___+________-_+_______-__+_______-__+________-_+________-_+________-_+________-_+
MEAT ADULT 2.01E-06 1.87E-06 3.79E-07 2.24E-06 2.63E-06 1.79E-04 1.70E-06 1.70E-06
-________+______-___+_________-+-__
______+_________-+________-_+_______-__+________-_+________-_+
TEEN
- 1.25E-06 : 1.11E-06 : 3.15E-07 : 1.45E-06
- 1.77E-06
- 1.30E-04
- 1.01E-06 : 1.O1E-06
-________+______-___+__________+_________-+________-_+________-_+________-_+_______-__+________-_+
CHILD
- 1.56E-06 : 1.29E-06 : 5.84E-07 : 1.81E-06 : 2.19E-06 : 1.95E-04 : 1.23E-06 : 1.23E-06
-________+______-___+_________-+_________-+_________-+________-_+________-_+________-_+________-_+
IV-40
TABLE IV-A-37 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
37 BEEF AT 3.25 MILES W ANNUALBETAAIRDOSE = 6.50E-03 MILLRADS ANNUALGAMMAAIRDOSE = 1.98E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+__________+_________-+________-_+________-_+_________-+________-_+
PLUME
- 1.16E-03 : 1.16E-03 : 1.16E-03 : 1.16E-03 : 1.16E-03 : 1.16E-03 : 1.22E-03 : 3.73E-03
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
GROUND
- 3.44E-07 : 3.44E-07 : 3.44E-07 : 3.44E-07 : 3.44E-07 : 3.44E-07 : 3.44E-07 : 4.17E-07
_________+__________+__________+__________+__________+__________+__________+__________+__________+
MEAT ADULT 1.18E-06 1.11E-06 1.95E-07 1.30E-06 1.50E-06 9.25E-05 1.02E-06 1.02E-06
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
TEEN
- 7.30E-07 : 6.60E-07 : 1.62E-07 : 8.35E-07 : 9.98E-07 : 6.69E-05 : 6.07E-07 : 6.07E-07
-________+__________+__________+__________+__________+__________+__________+_---________+-+___-__+
CHILD
- 9.09E-07 : 7.66E-07 : 3.01E-07 : 1.04E-06 : 1.23E-06 : 1.O1E-04 : 7.35E-07 : 7.35E-07
-________+__________+__________+__________+__________+__________+__________+_---________-+____-__+
IV-41 Q~ ( c Q y (< Q Q K K C C
(
y (
( C C C C '( C C C C C C C C C ( (
(.
'~. K K C K K K C
C C ( C C CK C (C C C C C (.6 C C ('C ( C ( ('(
C C.( (C C C Ch ( C)( ( K8 C (C
C
( C C V TABLE IV-A-38 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
38 BEEF AT 2.74 MILES WNW ANNUALBETAAIRDOSE = 2.18E-02 MILLRADS ANNUALGAMMAAIRDOSE = 6.66E-03 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-__+_________-+__________+__________+__________+__________+_____--+-____-+_--____+
PLUME
- 3.88E-03 : 3.88E-03 : 3.88E-03 : 3.88E-03 : 3.88E-03 : 3.88E-03 : 4.10E-03 : 1.25E-02
-________+_____-____+________-_+________-_+_________-+_________-+________-_+________-_+________-_+
GROUND
- 1.07E-06 : 1.07E-06 : 1.07E-06 : 1.07E-06 : 1.07E-06 : 1.07E-06 : 1.07E-06 : 1.29E-06
-________+______-___+________-_+________-_+_________-+-_________+__________+_________-+________-_+
MEAT ADULT 3.90E-06 3.67E-06 6.06E-07 4.26E-06 4.88E-06 2.87E-04 3.40E-06 3.40E-06
-________+_____-____+________-_+________-_+_______-__+________-_+_________-+_________-+_________-+
TEEN
- 2.41E-06 : 2.19E-06
- 5.03E-07
- 2.73E-06 : 3.24E-06 : 2.08E-04 : 2.02E-06 : 2.02E-06
-________+______-___+__________+_________-+________-_+________-_+_________-+________-_+________-_+
CHILD
- 2.99E-06 : 2.55E-06 : 9.33E-07 : 3.39E-06 : 3.99E-06 : 3.13E-04 : 2.45E-06 : 2.45E-06
-________+______-___+_________-+________-_+________-_+________-_+________-_+________-_+________-_+
IV-42
TABLE IV-A-39 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS SPECIAL LOCATION NO.
39 GOAT AT 0.60 MILES SSW ANNUALBETAAIRDOSE = 3.64E-01 MILLRADS ANNUALGAMMAAIRDOSE = 1.13E-01 MILLRADS PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
-________+______-___+_________-+_________-+_________-+_________-+__________+_________-+________-_+
PLUME
- 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.57E-02 : 6.93E-02 : 2.10E-01
________-+__________+__________+__________+__________+__________+__________+__________+__________+
GROUND
- 2.87E-05 : 2.87E-05 : 2.87E-05 : 2.87E-05 : 2.87E-05 : 2.87E-05 : 2.87E-05 : 3.47E-05 GOATMILK :
ADULT
- 7.07E-04 4.71E-04 5.37E-04 1.04E-03 1.58E-03 2.52E-01 2.67E-04 2.67E-04
-________+__________+__________+__________+__________+__________+__________+_--+-________-+___-__+
TEEN
- 1.08E-03 : 6.19E-04 : 9.74E-04 : 1.71E-03 : 2.70E-03 : 3.98E-01 : 3.48E-04 : 3.48E-04
-________+__________+_________+__________+__________+__________+__________+__--________+-________+
CHILD
- 1.90E-03 : 7.64E-04 : 2.36E-03 : 2.93E-03 : 4.46E-03 : 7.86E-01 : 5.51E-04 : 5.51E-04
+ __________+__________+-_______- _+__________+_
______+__________+___--+-______--+
+
INFANT : 3.39E-03 : 1.05E-03 : 4.93E-03 : 6.65E-03 : 7.63E-03 : 1.91E+00 : 8.36E-04 : 8.36E-04
-_______+__________+__________+__________+__________+__________+__________+__--________+-________+
IV-43 K K K K y K K K
K K K K K K K K K K K K K K K K K K K K K K K (
< K K.
K K K (K
( ( ( ( C ( ( ( ( ( ( C ( ( ( ( ( ( ( (
C C C C C ( C ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( (
TABLE IV-B-1 FORT CALHOUN 1 DOSE CONTRIBUTIONS FROM GASEOUS EFFLUENTS UNRESTRICTED AREA BOUNDARY REQUIRED BY TECHNICAL SPECIFICATION 5.9.4.a.
ANNUAL FOR JANUARY 1, 2002 TO DECEMBER 31, 2002 MAXIMUM SITE BOUNDARY GAMMA AIR DOSE -
MAXIMUM SITE BOUNDARY BETA AIR DOSE -
2.20E-01 MILLRADS 7.12E-01 MILLRADS IV-44
TABLE IV-C-1 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS ALARA ANNUAL INTEGRATED POPULATION DOSE
SUMMARY
(PERSON-REM)
PATHWAY T.BODY GI-TRACT BONE LIVER KIDNEY THYROID LUNG SKIN
_____-___+_-___-____+_________-+_________-+________-_+________-_+_______-__+________-_+________-_+
PLUME 1.08E-01 1.08E-01 1.08E-01 1.08E-01 1.08E-01 1.08E-01 1.16E-01 4.33E-01 98.60%
98.77%
99.59%
98.40%
98.09%
39.72%
98.94%
99.71%
_________+-_________+_______-__+________-_+________-_+________-_+_______-__+________-_+________-_+
GROUND 3.41E-05 3.41E-05 3.41E-05 3.41E-05 3.41E-05 3.41E-05 3.41E-05 4.13E-05 0.03%
0.03%
0.03%
0.03%
0.03%
0.01%
0.03%
0.01%
_________+______-___+_________-+_________-+________-_+________-_+_______-__+________-_+________-_+
INHAL 5.97E-04 5.51E-04 8.87E-05 6.48E-04 7.29E-04 3.78E-02 5.34E-04 5.33E-04 0.55%
0.51%
0.08%
0.59%
0.66%
13.95%
0.45%
0.12%
_________+-_________+_______-__+______-___+________-_+________-_+_______-__+________-_+________-_+
VEGET 4.72E-04 4.71E-04 5.84E-06 4.75E-04 4.80E-04 2.80E-03 4.68E-04 4.68E-04 0.43%
0.43%
0.01%
0.43%
0.44%
1.03%
0.40%
0.11%
_________+-_________+_______-__+________-_+_________-+-_________+__________+_________-+________-_+
COW MILK 3.OOE-04 1.65E-04 2.89E-04 4.51E-04 6.87E-04 1.12E-01 1.04E-04 1.04E-04 0.27%
0.15%
0.27%
0.41%
0.63%
41.43%
0.09%
0.02%
_________+-_________+_______-__+________-_+_______-__+________-_+________-_+________-_+________-_+
MEAT 1.24E-04 1.14E-04 2.42E-05 1.37E-04 1.60E-04 1.04E-02 1.06E-04 1.06E-04 0.11%
0.10%
0.02%
0.13%
0.15%
3.85%
0.09%
0.02%
____-__--+__________+__________+__________+__________+__________+_________+__--________+-________+
- TOTAL*
- 1.09E-01 : 1.09E-01 : 1.08E-01 : 1.09E-01 : 1.10E-01 : 2.71E-01 : 1.17E-01 : 4.35E-01
_______--+__________+__________+_________+__________+__________+__________+__--________+-________+
IV-45 K (~ C
(,
K K K K K K K K (
C C (~
K K C C K K C C K K K K QQ K
K K
SECTION V DOSE FROM LIQUID EFFLUENTS LADTAP II OUTPUT Technical Specification 5.9.4a January 1, 2002 - December 31, 2002 V-1
Radioactive Effluent Releases - First, Second, Third, and Fourth Quarters 2002 LIQUID EFFLUENTS During the reporting period, a total of 4.20E-01 Curies of radioactive liquid materials less tritium, dissolved noble gases, and alpha was released to the Missouri River at an average concentration of 3.78E-10 gCi/mL. This represents 1.51 E-01% of the limits specified in Appendix B to 10 CFR 20 (1.OE-06 pCi/mL for unrestricted areas),
293 Curies of tritium were discharged at an average diluted concentration of 2.50E-07 gCi/mL or 1.OOE-01 % of ECL (1.OE-03 gCi/mL). Gross alpha radioactivity released during the reporting period total 1.06E-02 Curies.
Dilution water during the period amounted to 1.29E+12 liters, while radioactive liquid waste volume was 1.84E+08 liters.
V-2
A.
Potential Annual Doses to Individuals from Liquid Releases Total body, skin, and organ mRem for liquid releases were calculated for all significant liquid pathways using the annual configuration of the LADTAP II program.
The inputs to LADTAP II for the annual period from January 1, 2002 through December 31, 2002 were as follows:
(1)
All liquid effluents were as described in Section IV except for entrained noble gases (Ar-41, Xe-131M, Xe-1 33M, Xe-1 33, Xe-1 35M, Xe-1 35, Kr-85M, Kr-87, and Kr-88)
(2)
An average plant discharge rate of 733.0 cubic feet per second (CFS) was utilized for 2002. The average discharge rate during releases was 678.0 cubic feet per second (CFS).
(3)
Dilution factors (inverse of the mixing ratios) were computed based on Regulatory Guide 1.113 (equation 7 in Section 2.a. 1 of Appendix A) for a one dimensional transport model.
(4)
Drinking water transport times of 6.6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> to the Omaha intake and 7.0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> to the Council Bluffs intake for the ALARA doses were used. A transport time of 0.0 was used from the plant to the discharge site.
(5)
A shorewidth factor of 0.2 was used.
(6)
All dose factors, transport times from receptor to individual, and usage factors are defined by Regulatory Guide 1.109 and NUREG-0172.
The discharge site was chosen to present the most conservative estimate of mRem dose for an average adult, teenager, child, and infant. A conservative approach is also presented by the assumption that Omaha and Council Bluffs receive all drinking water from the Missouri River.
B.
Potential Annual Doses to Population from Liquid Releases The LADTAP II program in its annual configuration was also used to calculate to total body and organ doses for the population of 853,274 within a 50-mile radius of the plant (based on the 2000 census). The same input was used as in the individual cases with the addition of the following:
V-3
(1)
Dilution factors and transport times for the pathways of sport fish, commercial fish, recreation and biota were calculated based on a distance of two miles downstream as approximately the distance to the nearest recreation facility - DeSoto National Wildlife Preserve.
(2)
The total fish harvest for both sport and commercial purposes was calculated using an average commercial fish catch for Nebraska.
V4
L AAA DDDD TTTTT AAA PPPP L
A A
D D
T A
A P
P L
A A
D D
T A
A P
P L
AAAAA D D
T AAAAA PPPP L
A A
D D
T A
A P
LLLLL A A DDDD T
A A
P IIIII IIIII I
I I
I I
I I
I IIIII IIIII EVALUATION OF RADIATION DOSES FROM RELEASES OF RADIACTIVITY IN NUCLEAR POWER PLANTS LIQUID EFFLUENTS REVISION DATE:
PNL VAX - OCTOBER 1985 FORT CALHOUN ANNUAL 2002, DOSE PROJECTIONS RADIOLOGICAL ASSESSMENT BRANCH DIVISION OF SYSTEMS INTEGRATION U. S. NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C.
DATE OF RUN:
24-FEB-03 V-S C K ( C C C Q C Q C C K ( C Y C C C C C C C ( Q C
(C( C 0CC (C(C CC( C C (('C
(<CC ((
((CC C(
CC( C C C C C (K( ( (C'~
A D U L T D OS E S PATHWAY FISH DRINKING SHORELINE SWIMMING BOATING TOTAL FISH DRINKING SHORELINE SWIMMING BOATING SKIN 7.53E-05 7.53E-05 BONE 1.58E-02 1.16E-04 6.51E-OS 1.46E-06 7.29E-07 1.60E-02 LIVER 2.68E-02 8.12E-04 6.51E-05 1.46E-06 7.29E-07 2.77E-02 DOSE__ (MREM TOTAL BODY 1.97E-02 7.81E-04 6.51E-05 1.46E-06 7.29E-07 2.06E-02 PER YEAR INTAKE)
THYROID 6.79E-03 4.33E-03 6.51E-05 1.46E-06 7.29E-07 1.12E-02 KIDNEY 1.14E-02 7.90E-04 6.51E-05 1.46E-06 7.29E-07 1.22E-02 LUNG 2.99E-03 7.02E-04 6.51E-05 1.46E-06 7.29E-07 3.76E-03 GI-LLI 5.26E-02 1.03E-03 6.51E-05 1.46E-06 7.29E-07 5.37E-02 LUNG GI - LLI USAGE (KG/YRHR/YR) 21.0 730.0 12.0 12.0 12.0 DILUTION TIME(HR) 7.3 24.00 30.8 18.60 7-1 0.00 SHOREWIDTH FACTOR=0.2 7.3 7.3 0.00 0.00 T E E N A G E R D O S E S PATHWAY FISH DRINKING SHORELINE SWIMMING BOATING TOTAL SKIN 4.21E-04 4.21E-04 BONE 1.67E-02 1.09E-04 3.63E-04 8.14E-06 4.07E-06 1.71E-02 LIVER 2.75E-02 6.03E-04 3.63E-04 8.14E-06 4.07E-06 2.85E-02
_DOSE__ (MREM TOTAL BODY 1.13E-02 5.39E-04 3.63E-04 8.14E-06 4.07E-06 1.22E-02 PER YEAR INTAKE)
THYROID 6.35E-03 3.61E-03 3.63E-04 8.14E-06 4.07E-06 1.03E-02 KIDNEY LUNG GI-LLI KIDNEY 1.17E-02 5.8 SE-04 3.63E-04 8.14E-06 4.07E-06 1.27E-02 LUNG 3.50E-03 5.03E-04 3.63E-04 8.14E-06 4.07E-06 4.38E-03 GI-LLI 3.75E-02 7.14E-04 3.63E-04 8.14E-06 4.07E-06 3.86E-02 FISH DRINKING SHORELINE SWIMMING BOATING USAGE (KG/YRHR/YR) 16.0 510.0 67.0 67.0 67.0 DILUTION 7.3 30.8 7.3 7.3 7.3 TIME (HR) 24.00 18.60 0.00 0.00 0.00 SHOREWIDTH FACTOR=0.2 V-6
C H1 I L D D O S E S PATHWAY FISH DRINKING SHORELINE SWIMMING BOATING TOTAL SKIN 8.79E-05 8 79E-05 BONE 2.07E-02
- 3. 09E-04
- 7. 59E-05 1.70E-06
- 8. 51E-07 2.11E-02 LIVER 2.40E-02 1.17E-03 7.59E-05 1.70E-06
- 8. 51E-07 2.53E-02 DOSE__ (MREM TOTAL BODY 4.49E-03 1.OOE-03 7.59E-05 1.70E-06 8.51E-07 5.57E-03 PER YEAR INTAKE)
THYROID 6.60E-03 8.41E-03 7.59E-05 1.70E-06 8.51E-07 1 51E-02 KIDNEY 1.01E-02 1.13E-03 7.59E-05 1.70E-06 8.51E-07 1.13E-02 LUNG
- 2. 76E-03 9.63E-04
- 7. 59E-05 1.70E-06
- 8. 51E-07 3.80E-03 GI-LLI 1.36E-02
- 1. 13E-03 7.59E-05 1.70E-06 8.51E-07 1.48E-02 FISH DRINKING SHORELINE SWIMMING BOATING USAGE (KG/YR,HR/YR) 6.9 510.0 14.0 14.0 14.0 DILUTION 7.3 30.8 7.3 7.3 7.3 TIME (HR) 24.00 18.60 0.00 0.00 0.00 SHOREWIDTH FACTOR=0.2 I N F A N T D O S E S PATHWAY FISH DRINKING SHORELINE TOTAL SKIN
- 0. OOE+00
- 0. OOE+00 BONE
- 0. OOE+00 3.25E-04 0.OOE+00 3.25E-04 LIVER 0.OOE+00 1.22E-03 0.OOE+00 1.22E-03 DOSE__ (MREM TOTAL BODY 0.OOE+00 9.76E-04 0.OOE+00 9.76E-04 PER YEAR INTAKE)
THYROID 0.OOE+00 1.27E-02 0.00E+00 1.27E-02 KIDNEY
- 0. OOE+00
- 1. 14E-03 0.OOE+00
- 1. 14E-03 LUNG
- 0. OOE+00
- 9. 53E-04
- 0. OOE+00
- 9. 53E-04 GI-LLI 0.00E+00 1.03E-03 0.OOE+00 1.03E-03 FISH DRINKING USAGE (KG/YR,HR/YR) 0.0 330.0 DILUTION 7.3 30.8 TIME (HR) 24.00 18.60 SHOREWIDTH FACTOR=0.2 V-7
(
(
(
(
Q C
(
(
Q
( ( (
(
C
( ( ( ( ( ( ( ( ( ( ( ( ( ( ( Q C
. ( ( ( ( C ( ( ( (
C C C
((CC CC (
((
CC,(< (
QC.
(
CCC C
(C (I C CC C ( (C C (C (SQ, LOCATION IS PATHWAY FISH DRINKING SHORELINE SWIMMING BOATING TOTAL SITE DISCHG.
A D U L T D O S E S SKIN
- 5. SOE-04 5.50E-04 BONE 1.15E-01 3.58E-03 4.75E-04 1.06E-05 5.32E-06 1.20E-01 LIVER 1.95E-01 2.50E-02 4.75E-04 1.06E-05 5.32E-06 2.21E-01 DOSE__ (MREM TOTAL BODY 1.44E-01 2.41E-02 4.75E-04 1.06E-05 5.32E-06 1.69E-01 PER YEAR INTAKE)
THYROID 4.96E-02 1.36E-01 4.75E-04 1.06E-05 5.32E-06 1.86E-01 GI - LLI KIDNEY 8.30E-02 2.44E-02 4.75E-04 1.06E-05 5.32E-06 1.08E-01 LUNG 2.18E-02 2.16E-02 4.75E-04 1.06E-05 5.32E-06 4.39E-02 GI-LLI 3.84E-01 3.16E-02 4.75E-04 1.06E-05 5.32E-06 4.16E-01 FISH DRINKING SHORELINE SWIMMING BOATING USAGE (KG/YRHR/YR) 21.0 730.0 12.0 12.0 12.0 DILUTION 1.0 1.0 1.0 1.0 1.0 TIME (HR) 24.00 12.00 0.00 0.00 0.00 SHOREWIDTH FACTOR'0.2 T E E N A G E R D O S E S PATHWAY FISH DRINKING SHORELINE SWIMMING BOATING TOTAL SKIN
- 3. 07E-03 3.07E-03 BONE 1.22E-01 3.37E-03 2.65E-03 5.94E-05
- 2. 97E-05 1.28E-01 LIVER 2.01E-01 1.86E-02 2.65E-03 5.94E-05 2.97E-05 2.22E-01 DOSE__ (MREM TOTAL BODY 8.23E-02 1.66E-02 2.65E-03 5.94E-05 2.97E-05 1.02E-01 PER YEAR INTAKE)
THYROID 4.63E-02 1.13E-01 2.65E-03 5.94E-05 2.97E-05 1.63E-01 KIDNEY 8.56E-02 1.80E-02 2.65E-03 5.94E-05 2.97E-05 1.06E-Ol LUNG 2.56E-02 1.55E-02 2.65E-03 5.94E-05 2.97E-05 4.38E-02 GI-LLI 2.74E-01 2.20E-02 2.65E-03 5.94E-05 2.97E-05 2.99E-01 LUNG GI-LLI FISH DRINKING SHORELINE SWIMMING BOATING USAGE (KG/YRHR/YR) 16.0 510.0 67.0 67.0 67.0 DILUTION 1.0 1.0 1.0 1.0 TIME (HR) 24.00 12.00 0.00 0.00 0.00 SHOREWIDTH FACTOR=0.2 V-8
LOCATION IS SITE DISCHG.
C H I L D D O S E S PATHWAY FISH DRINKING SHORELINE SWIMMING BOATING TOTAL SKIN 6.41E-04 6.41E-04 BONE 1.51E-01 9.54E-03 5.54E-04 1.24E-05 6.21E-06 1.61E-01 LIVER 1.75E-01
- 3. 61E-02
- 5. 54E-04 1.24E-05 6.21E-06 2.12E-01
_DOSE_ (MREM PER YEAR INTAKE)
TOTAL BODY THYROID 3.28E-02 4.81E-02 3.09E-02 2.65E-01 5.54E-04 5.54E-04 1.24E-05 1.24E-05 6.21E-06 6.21E-06 6.42E-02 3.13E-01 KIDNEY 7.34E-02 3. 50E-02 5.54E-04 1.24E-05 6.21E-06 1.09E-01 LUNG 2.02E-02
- 2. 97E-02
- 5. 54E-04 1.24E-05 6.21E-06
- 5. 04E-02 GI-LLI 9.93E-02 3.48E-02
- 5. 54E-04 1.24E-05 6.21E-06 1.35E-01 FISH DRINKING SHORELINE SWIMMING BOATING USAGE (KG/YR,HR/YR) 6.9 510.0 14.0 14.0 14.0 DILUTION 1.0 1.0 1.0 1.0 1.0 TIME (HR) 24.00 12.00 0.00 0.00 0.00 SHOREWIDTH FACTOR=0.2 I N F A N T D O S E S PATHWAY FISH DRINKING SHORELINE TOTAL SKIN 0.OOE+00 0.OOE+00 BONE 0.OOE+00 1 OOE-02 0.00E+00 1.00E-02 LIVER
- 0. OOE+00 3.77E-02
- 0. OOE+00
- 3. 77E-02 DOSE-_ (MREM PER TOTAL BODY 0.00E+00 3.01E-02 0.OOE+00 3.01E-02 YEAR INTAKE)
THYROID 0.00E+00 3.99E-01 0.OOE+00 3.99E-01 KIDNEY 0.OOE+00 3.51E-02 0.OOE+00 3.51E-02 LUNG 0.OOE+00
- 2. 93E-02 0.OOE+00 2.93E-02 GI-LLI
- 0. OOE+00 3.18E-02
- 0. OOE+00
- 3. 18E-02 FISH DRINKING USAGE (KG/YR,HR/YR) 0.0 330.0 DILUTION 1.0 1 0 TIME (HR) 24.00 12 00 SHOREWIDTH FACTOR=0.2 V-9 (QC QY ( Q ( C' QQ C' C ( YQ( ((C
(>( ( C(C QCtC
(
((i((
( (
It(
(K.(
( ( C C,(C ( ( (C
((((
((t(
()
FISH CONSUMPTION POPULATION DOSES PERSON-REM SPORT HARVEST PATHWAY FISH FISH FISH FISH AGE GROUP ADULT TEENAGER CHILD TOTAL
DOSE USAGE BONE LIVER TOTAL BODY 6.108+04 4.55E-02 7.74E-02 5.71E-02 7.12E+03 7.35E-03 1.22E-02 4.99E-03 4.93E+03 1.46E-02 1.71E-02 3.17E-03 7.30E+04 6.75E-02 1.07E-01 6.52E-02 (PERSON-REM)-------------------------
THYROID KIDNEY LUNG GI-LLI L.20E-02 3.19E-02 8.65E-03 1.35E-01 1.71E-03 5.042-03 1.55E-03 1.48E-02 2.86E-03 6.92E-03 1.97E-03 8.61E-03 L.65E-02 4.39E-02 1.22E-02 1.59E-01 LOCATION DILUTION CATCH TIME(HR)-INCLUDES FOOD PROCESSING TIME OF 1.68E+02 HR 7.30E+00 7.30E+04 1.69E+02 POPULATION=1.24E+04 AVERAGE INDIVIDUAL CONSUMPTION (KG/YR)
ADULT=6.90E+00 TEEN-5.20E+00 CHILD=2.20E+00 COMMERCIAL HARVE PATHWAY FISH FISH FISH FISH AGE GROUP ADULT TEENAGER CHILD TOTAL
'ST
DOSE (PERSON-REM)-------------------------
USAGE BONE LIVER TOTAL BODY THYROID KIDNEY LUNG GI-LLI 4.18E+06 5.16E-03 8.78E-03 6.48E-03 1.07E-03 3.58E-03 9.82E-04 1.45E-02 4.88E+05 8.34E-04 1.38E-03 5.66E-04 1.53E-04 5.65E-04 1.77E-04 1.59E-03 3.38E+05 1.66E-03 1.94E-03 3.60E-04 2.56E-04 7.75E-04 2.23E-04 9.24E-04 5.01E+06 7.66E-03 1.21E-02 7.40E-03 1.47E-03 4.92E-03 1.38E-03 1.70E-02 LOCATION DILUTION CATCH TIME(HR)-INCLUDES FOOD PROCESSING TIME OF 2.40E+02 HR 7.30E+00 7.30E+04 2.41E+02 POPULATION=8.53E+05 AVERAGE INDIVIDUAL CONSUMPTION (KG/YR)
ADULT=6.90E+00 TEEN=5.20E+00 CHILD=2.20E+00 V-10
POPULATION WATER CONSUMPTION DOSES SUPPLIER-OMAHA PATHWAY AGE GROUP DRINKING ADULT DRINKING TEENAGER DRINKING CHILD DRINKING TOTAL POPULATION=5.29E+05 USAGE 1.39E+08
- 1. 51E+07 2.48E+07 1.79E+08 DILUTION=3 DOSE (PERSON-REM) -------------
BONE LIVER TOTAL BODY THYROID KIDNEY LUNG GI-LLI 2.20E-02 1.54E-O1 1.49E-01 7.95E-01 1.50E-01 1.34E-01 1.95E-01 3.22E-03 1.79E-02 1.60E-02 1.03E-01 1.73E-02 1.49E-02 2.11E-02 1.49E-02 5.69E-02 4.86E-02 3.93E-01 5.49E-02 4.68E-02 5.46E-02 4.01E-02 2.29E-01 2.13E-01 1.29E+00 2.22E-01 1.95E-01 2.70E-01
.08E+01 TRANSIT TIME=3.06E+01 11R (INCLUDING 24 HR FOR TREATMENT FA'CILITY)
AVERAGE INDIVIDUAL CONSUMPTION (L/YR)
ADULT=3.70E+02 TEEN=2.60E+02 CHILD=2.60E+02 SUPPLIER-COUNCIL BLUFFS PATHWAY AGE GROUP DRINKING ADULT DRINKING TEENAGER DRINKING CHILD DRINKING TOTAL POPULATION=8.70E+04 USAGE
- 2. 29E+07 2.49E+06
- 4. 07E+06
- 2. 94E+07 DILUTION=3 DOSE (PERSON-REM) -------------
BONE LIVER TOTAL BODY THYROID KIDNEY LUNG GI-LLI 3.55E-03 2.50E-02 2.40E-02 1.29E-01 2.43E-02 2.16E-02 3.15E-02 5.21E-04 2.89E-03 2.59E-03 1.67E-02 2.80E-03 2.41E-03 3.42E-03 2.41E-03 9.20E-03 7.87E-03 6.35E-02 8.89E-03 7.57E-03 8.84E-03 6.49E-03 3.71E-02 3.45E-02 2.09E-01 3.60E-02 3.16E-02 4.38E-02
.13E+01 TRANSIT TIME=3.10E+01 HR (INCLUDING 24 HR FOR TREATMENT FA,CILlTY)
AVERAGE INDIVIDUAL CONSUMPTION (L/YR)
ADULT=3.70E+02 TEEN=2.60E+02 CHILD=2.60E+02
--- CUMULATIVE TOTAL ---
PATHWAY AGE GROUP USAGE BONE LIVER TOTAL BODY THYROID KIDNEY LUNG GI-LLI DRINKING CUMUL TOTAL 2.08E+08 4.66E-02 2.66E-01 2.48E-01 1.50E+00 2.58E-01 2.27E-01 3.14E-01 NEPA DOSES _
NOTE- -TOTAL NEPA DOSE INCLUDES SPORT CATCH PATHWAY FISH FISH FISH FISH AGE GROUP ADULT TEENAGER CHILD TOTAL DOSE (PERSON-REM) -------------
USAGE BONE LIVER TOTAL BODY THYROID KIDNEY LUNG GI-LLI 1.22E+05 9.09E-02 1.55E-01 1.14E-01 2.13E-02 6.33E-02 1.73E-02 2.63E-01 1.42E+04 1.47E-02 2.43E-02 9.97E-03 3.06E-03 1.OOE-02 3.10E-03 2.87E-02 9.85E+03 2.92E-02 3.41E-02 6.33E-03 5.11E-03 1.37E-02 3.93E-03 1.67E-02 1.46E+05 1.35E-01 2.13E-01 1.30E-01 2.95E-02 8.71E-02 2.43E-02 3.08E-01
________HYDROSPHERE TRITIUM DOSE_____
AVERAGE INDIVIDUAL WATER CONSUMPTION-3.0 L/DAY PATHWAY AGE GROUP USAGE BONE LIVER TOTAL BODY THYROID KIDNEY LUNG GI-LLI WATER TOTAL 2.86E+ll 0.OOE+00 2.23E-03 2.23E-03 2.23E-03 2.23E-03 2.23E-03 2.23E-03 v-11
( Q ( ( k. ( ( ( C C C C C ( C C C ( ( C C ( ( C C C ( C C K C C ( C C C C C C (
('(
(,((
((
((,
(
()(
~()(
)(
J
(
(;
(
(
(
PUT(
IO( DO( S(
(
)
- RECREATION POPULATION DOSES I
LOCATION-DOWN STREAM SWIMMING DILUTION= 7.30E+00 PATHWAY AGE GROUP SHORELINE TOTAL POPUL TRANSIT TIME-6.70E-01 HR SWF- 0.2 DOSE (PERSON-REM)
USAGE SKIN TOTAL BODY THYROID 4.10E+07 2.57E-01 2.22E-01 2.22E-01 LOCATION-DOWN STREAM SWIMMING DILUTION= 7.30E+00 PATHWAY AGE GROUP SWIMMING TOTAL POPUL TRANSIT TIME= 6.70E-01 HR DOSE (PERSON-REM)
USAGE SKIN TOTAL BODY THYROID 4.10E+07 4.95E-03 4.95E-03 LOCATION-DOWN STREAM BOATING DILUTION= 7.30E+00 TRANSIT TIME-6.70E-01 HR DOSE (PERSON-REM)
USAGE SKIN TOTAL BODY THYROID 4.10E+07 2.48E-03 2.48E-03 PATHWAY BOATING AGE GROUP TOTAL POPUL DOSE TO BIOTA MRADS PER YEAR BIOTA FISH INVERTEBRATE ALGAE MUSKRAT RACCOON HERON DUCK DILUTION=
INTERNAL 2.07E+00 4.94E+00 2.42E+00 2.60E+00 1.14E+00 1.35E+01 2.28E+00 1.OOE+00 EXTERNAL 1.74E+00 3.48E+00 7.77E-03 1.16E+00 8.67E-01 1.1E+00 1.74E+00 TRANSIT TIME= 0.OOE+00 HR TOTAL 3.81E+00 8.41E+00 2.43E+00 3.76E+00 2.01E+00 1.46E+01 4.02E+00 V-12
SECTION VI RADIOACTIVE EFFLUENT RELEASES - SOLID RADIOACTIVE WASTE Technical Specifications 5.9.4a, 5.17d and 5.18d January 1, 2002 - December 31, 2002 VI-1
III. RADIOACTIVE EFFLUENT RELEASES-SOLID RADIOACTIVE WASTE EFFLUENT AND WASTE DISPOSAL REPORT January 1, 2002 through December 31, 2002 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS A. SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (NOT IRRADIATED)
- 1. Type of Waste
- a. Spent resins, filter sludges, evaporator bottoms, etc.
Month Shipped Number of Shipments Volume Curie Est.Total Cu.Meter Content
% Error January February March April May June July August September October November December 0
0 0
I 0
0 0
I 0
I 0
0 O.OOE + 00 O.OOE + 00 O.OOE +00 3.40E + 00 O.OOE + 00 O.OOE + 00 O.OOE +00 3.86E + 00 O.OOE + 00 3.40E + 00 O.OOE + 00 O.OOE + 00 O.OOE +00 O.OOE +00 O.OOE + 00 4.72E + 02 O.OOE + 00 O.OOE + 00 O.OOE + 00 5.09E+01 O.OOE + 00 4.29E+02 O.OOE + 00 O.OOE + 00 N/A N/A N/A 20 N/A N/A N/A 20 N/A 20 N/A N/A Total (Type a) 3 1.07E+01 9.52E+02 20
- b. Dry compressable, contaminated equipment, etc.
January February March April May June July August September October November December 0
1 1
1 3
7 5
7 6
0 0
3 O.OOE + 00 8.OOE-02 2.50E-01 1.40E-01 1.50E-01 3.02E + 00 1.65E+00 4.29E + 00 1.68E + 00 O.OOE + 00 O.OOE + 00 1.33E+00 O.OOE + 00 1.10E-02 2.18E-03 8.58E-02 8.16E-02 1.1 3E-01 1.31 E-01 3.31 E-02 2.67E-01 O.OOE + 00 O.OOE + 00 3.58E-02 N/A 20 20 20 20 20 20 20 20 N/A N/A 20 Total (Type b) 34 1.26E+01 7.60E-01 20 Vl-2
- c. Irradiated components and other categories January February March April May June July August September October November December 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A Total (Type c) 0 0
N/A
- d. Other January February March April May June July August September October November December 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A NIA N/A Total (Type d) 0 0
N/A VI-3
B. ESTIMATE OF MAJOR NUCLIDE COMPOSITION (BY Type of Waste)
- 1. Percentage of Curies from Represented Isotopes Isotope Percent Curies
- a.
Cs-1 34 Cs-1 37 H-3 Ni-63 Sb-125
- b.
Cs-137 Nb-95 Cr-51 Cs-1 34 Co-58 Zr-95 RU-106 CO-60 Ni-63 Fe-55 1-131 Ce-144
- c.
N/A
- d.
N/A 46.5%
46.1%
2.0%
1.9%
1.7%
20.2%
19.8%
9.7%
9.5%
7.7%
6.8%
6.6%
6.2%
3.2%
2.9%
2.6%
1.2%
N/A N/A 4.43E + 02 4.39E + 02 1.94E + 01 1.82E + 01 1.61 E + 01 1.53E-01 1.50E-01 7.37E-02 7.24E-02 5.82E-02 5.20E-02 5.01 E-02 4.72E-02 2.45E-02 2.22E-02 1.96E-02 9.36E-03 All other nuclides constitute less than 1%
All other nuclides constitute less than 1%
N/A N/A C. SOLID WASTE (DISPOSITION)
Number of Shipments 4
33 Transportation Mode Closed Sole Use Vehicle Closed Sole Use Vehicle Destination Barnwell,S.C.
Clive Utah.
D. IRRADIATED FUEL SHIPMENTS (DISPOSITION)
Number of Shipments NtA Transportation Mode N/A Destination N/A VI4
SECTION VII ATTACHMENT 1 ODCM and PCP revisions for the period January 1, 2002 through December 31, 2002 in accordance with Technical Specification 5.17d and 5.18d, the radioactive effluent release report shall include any revisions to the Offsite Dose Calculation Manual (ODCM) and the Process Control Program (PCP).
1 revision(s) made to the Offsite Dose Calculation Manual (ODCM).
0 revision(s) made to the Process Control Program (PCP).
January 1, 2002 - December 31, 2002 VII-1
WP8 Fort Calhoun Station Unit No. 1 CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL
Title:
OFF-SITE DOSE CALCULATION MANUAL (ODCM)
FC-68 Number:
Reason for Change:
Requestor:
Preparer:
Correction (a):
EC 29304 Correct errors, update to reflect land use survey.
J. Shipman J. Shipman Page 18 (09-05-02)
ISSUED:
09-03-02 3:00 pm R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 1 OF 132 TABLE OF CONTENTS PART I
- 1. DEFINITIONS.......................
6
- 2.
INSTRUMENTATION.......................
9 2.1 Radioactive Liquid Effluent Instrumentation 9
2.1.1 Limiting Condition for Operation.9 2.1.2 Surveillance Requirements.9 2.2 Radioactive Gaseous Effluent Instrumentation 13 2.2.1 Limiting Condition for Operation.13 2.2.2 Surveillance Requirements.13
- 3. RADIOACTIVE EFFLUENTS.......................
19 3.1 Radioactive Liquid Effluents 19 3.1.1 Concentration.19 3.1.2 Dose from Radioactive Liquid Effluents.21 3.1.3 Liquid Radwaste Treatment.22 3.1.4 Liquid Holdup Tanks.23 3.2 Radioactive Gaseous Effluents 24 3.2.1 Concentration.24 3.2.2 Dose - Noble Gases.28 3.2.3 Dose - Iodine-131, Radioactive Material in Particulate Form with Half-Lives Greater than 8 Days (Other than Noble Gases) and Tritium.29 3.2.4 Gaseous Radwaste Treatment.30 3.3 Uranium Fuel Cycle 32 3.3.1 Total Dose-Uranium Fuel Cycle.32
- 4. RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (REMP).....
33 4.1 Monitoring Program 33 4.1.1 Limiting Condition for Operation 33 4.1.2 Surveillance Requirements.34 4.2 Land Use Survey 43 4.2.1 Limiting Condition for Operation.43 4.2.2 Surveillance Requirements 44 4.3 Interlaboratory Comparison Program 44 4.3.1 Limiting Condition for Operation.44 4.3.2 Surveillance Requirements.44
- 5. ADMINISTRATIVE CONTROLS.......................
44 5.1 Responsibilities 44 5.1.1 FCS Chemistry Department.44 5.1.2 FCS Operations Department.44 5.2 Radioactive Effluent Reporting Requirements 45 5.2.1 Annual Radioactive Effluent Release Report.45 5.2.2 Annual Radiological Environmental Operating Report.46 5.2.3 Special Report.47 5.2.4 EPA 40 CFR Part 190 Reporting Requirements.47 R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 2 OF 132 TABLE OF CONTENTS PART I 5.3 Change Mechanism................................................
48 5.4 Meteorological Data................................................
48 5.5 References.......................
49
- 6. BASIS 50 6.1 Instrumentation 50 6.1.1 Radioactive Liquid Effluent Instrumentation.......
................. 50 6.1.2 Radioactive Gaseous Effluent Instrumentation......
............... 50 6.2 Radioactive Effluents................................................
51 6.2.1 Radioactive Liquid Effluents....................................
51 6.2.2 Radioactive Gaseous Effluents..........
....................... 53 6.3 Radiological Environmental Monitoring...................................
58 6.3.1 Monitoring Program..........................................
58 6.3.2 Land Use Survey............................................
58 6.3.3 Interlaboratory Comparison Program........
..................... 58 R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 3 OF 132 LIST OF TABLES PART I Table 1.2 - Frequency Notation.7 7
Table 1.3 - Radiological Effluent Controls Program Technical Specification Implementation.. 8 Table 2.1.1 - Radioactive Liquid Effluent Monitoring Instrumentation.10 Table 2.1.2 - Radioactive Liquid Effluent Monitoring Instrumentation Surveillance Requirements 12 Table 2.2.1 - Radioactive Gaseous Effluent Monitoring Instrumentation.14 Table 2.2.2 - Radioactive Gaseous Effluent Monitoring Instrumentation Surveillance Requirements.18 Table 3.1 - Radioactive Liquid Effluent Sampling And Analysis.20 Table 3.2 - Radioactive Airborne Effluent Sampling And Analysis.25 Table 3.3 - Sampler Deposition/transportation Correction Factors.27 Table 4.1 - Radiological Environmental Monitoring Program.35 Table 4.2 - Radiological Environmental Sampling Locations And Media.37 Table 4.3 - Detection Capabilities For Environmental Sample Analysis Lower Limit of Detection (LLD).41 Table 4.4 - Reporting Levels for Radioactivity Concentrations in Environmental Samples 42 LIST OF FIGURES PART I Figure 1 - Environmental Radiological Sampling Points.4 40 NJ R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 4 OF 132 TABLE OF CONTENTS PART II
- 1. EFFLUENT MONITOR SETPOINTS.........................................
60 1.1 Liquid Effluents.60 1.1.1 Liquid Effluent Radiation Monitors.61 1.2 Airborne Effluents 65 1.2.1 Airborne Effluent Radiation Monitors.66 1.3 Simultaneous Release Pathways 72 1.3.1 Liquid Release Pathways.72 1.3.2 Airborne Release Pathway.74
- 2. EFFLUENT CONCENTRATIONS.........................................
82 2.1 Liquid Effluent Concentrations.........................................
82 2.2 Airborne Effluent Concentrations.......................................
83
- 3. RADIOACTIVE EFFLUENT DOSE CALCULATIONS
............................ 84 3.1 Liquid Effluent Dose Calculations 84 3.1.1 Doses from Liquid Effluent Pathways.85 3.2 Airborne Effluent Dose Calculations 88 3.2.1 Noble Gas.88 3.2.2 Radioiodine, Tritium, and Particulates.90 3.2.3 Concentrations of Radionuclides in Foods and Vegetation from Atmospheric Releases.92 3.2.4 Parameters for Calculating Radionuclide Concentration in Cow and Goat Milk.95 3.2.5 Parameters for Calculating Radionuclide Concentration in Cow Meat, excluding Tritium.96 3.2.6 Parameters for Calculating Tritium Concentrations in Vegetation.96 3.2.7 Annual Dose from Atmospherically Released Radionuclides in Foods... 97
- 4. LOWER LIMIT OF DETECTION (LLD)..............................
99 R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 5 OF 132 LIST OF TABLES PART II Table 1 - Allocation Factors for Simultaneous Releases.............................
76 Table 2 - Dose Factors for Exposure to a Semi-Infinite Cloud of Noble Gases....
....... 100
\\8 Table 3 - Bioaccumulation Factors.............................................
101 Table 4 - Highest Potential Exposure Pathways for Estimating Dose.................. 102 Table 5 - Stable Element Transfer Data.
103 Table 6 - Recommended Values for Uap to Be Used for the Maximum Exposed Individual in Lieu of Site Specific Data....................................................
104 Table 7 - Animal Consumption Rates...........................................
104 Table 8 - External Dose Factors for Standing on Contaminated Ground................
105 Table 9 - Inhalation Dose Factors for Adult......................................
107 Table 1 0 - Inhalation Dose Factors for Teenager..................................
110 Table 1 1 - Inhalation Dose Factors for Child..........
........................... 113 Table 12 - Inhalation Dose Factors for Infant.....................................
116 Table 13 - Ingestion Dose Factors for Adult......................................
119 Table 14 - Ingestion Dose Factors for Teenager..................................
122 Table 15 - Ingestion Dose Factors for Child..........
............................ 125 Table 16-Ingestion Dose Factors for Infant..........
........................... 128
\\j Table 17 - Recommended Values for Other Parameters............................
131 LIST OF FIGURES PART II Figure 1 - Exclusion and Site Boundary Map......................................
77 Figure 2 - Liquid Radioactive Discharge Pathways...............
.................. 78 Figure 3 - Liquid Radioactive Waste Disposal System............
................... 79 Figure 4 - Airborne Effluent Discharge Pathways...................................
80 Figure 5 - Airborne Radioactive Waste Disposal System.............................
81 R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 6 OF 132 OFF-SITE DOSE CALCULATION MANUAL (ODCM)
- 1. DEFINITIONS Effluent Concentration Limit(ECL)
Radionuclide limits listed in 10 CFR Part 20, Appendix B, Table 2, Column 1.
Channel Check A qualitative determination of acceptable operability by observation of channel behavior during normal plant operation. This determination shall, where feasible, include comparison of the channel with other independent channels measuring the same variable.
Channel Function Test Injection of a simulated signal into the channel to verify that it is operable, including any alarm and/or trip initiating action.
Member(s) of the Public Member(s) of the Public means any individual except when that individual is receiving occupational dose.
Operable - Operability A system, subsystem, train, component or device shall be OPERABLE or have OPERABILITY when it is capable of performing its specified function(s). Implicit in this definition shall be the assumption that all necessary attendant instrumentation, controls, normal and emergency electrical power sources, cooling or seal water, lubrication, or other auxiliary equipment that are required for the system, subsystem, train, component, or device to perform its function(s) are also capable of performing their related support function(s).
Purge-Purgina A means for the removal and replacement of gases within the containment building.
Source Check Verification of channel response when the channel sensor is exposed to a radioactive source.
R12
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE CH-ODCM-0001 PAGE 7 OF 132
- 1. DEFINITIONS (continued)
Ventinq A means for the reduction of pressure greater than atmospheric within the containment structure.
Unrestricted Area Means an area, access to which is neither limited or controlled by licensee.
Water Effluent Concentration (WEC)
Radionuclide limits listed in 10 CFR Part 20, Appendix B, Table 2, Column 2.
Table 1.2 - Frequency Notation The surveillance intervals are defined as follows:
NOTATION TITLE FREQUENCY S
Shift At least once per shift D
Daily At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> W
Weekly At least once per 7 days BW Biweekly At least once per 14 days M
Monthly At least once per 31 days Q
Quarterly At least once per 92 days SA Semiannual At least once per 184 days A
Annually At least once per 366 days R
Refueling At least once per 18 months P
Prior to Prior to each release R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 8 OF 132 Table 1.3 - Radiological Effluent Controls Program Technical Specification Implementation Technical Specification ODCM Implementing Step 5.16.1.a 2.1.1, 2.2.1 5.16.1.b 3.1.1 5.16.1.c Table 3.1, Table 3.2 5.16.1.d 3.1.2 5.16.1.e 3.1.2.B.1, 3.2.2.B.1 5.16.1.f 3.1.3.1, 3.2.4.1 5.16.1.g 3.2.1 5.16.1.h 3.2.2 5.16.1.i 3.2.3 5.16.1.j 3.3.1 5.16.2.a 4.1.1 5.16.2.b 4.2.1 5.1 6.2.c 4.3.1 5.17 5.3, 5.2.1.d 5.18 5.2.1.d R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 9 OF 132
- 2. INSTRUMENTATION 2.1 Radioactive Liquid Effluent Instrumentation 2.1.1 Limiting Condition for Operation A_/
A.
The radioactive liquid effluent monitoring instrumentation channels shown in Table 2.1.1 shall be OPERABLE with their alarm/trip setpoints set to ensure that the limits of Specification 3.1.1 are not exceeded.
The alarm/trip setpoints of these channels shall be determined in accordance with Section II of the Off-site Dose Calculation Manual.
APPLICABILITY: At all times ACTION:
- 1)
With a radioactive liquid effluent monitoring instrumentation channel alarm/trip setpoint less conservative than required by the above specification, immediately suspend the releases of radioactive liquid effluents monitored by the affected channel or declare the channel inoperable.
- 2) With less than the minimum number of radioactive liquid effluent monitoring instrumentation channels operable, take the action shown in Table 2.1.1. Restore inoperable effluent monitoring instrumentation to OPERABLE status within 30 days and, if unsuccessful, explain in the next Annual Radiological Effluent Release Report why this inoperability was not corrected in a timely manner. The reporting requirement is limited to the following instrumentation that monitors effluent streams: RM-055, RM-054A, and RM-054B.
2.1.2 Surveillance Requirements A.
Each radioactive liquid effluent monitoring instrumentation channel shall be demonstrated OPERABLE by performance of the CHANNEL CHECK, SOURCE CHECK, CALIBRATION, and CHANNEL FUNCTIONAL TEST at the frequencies shown in Table 2.1.2.
R12 J
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE CH-ODCM-0001 PAGE 10 OF 132 Table 2.1.1 - Radioactive Liquid Effluent Monitoring Instrumentation MINIMUM CHANNELS OPERABLE ACTION INSTRUMENT
- 1. Radioactivity Monitors Providing Alarm and Automatic Termination of Release.
- a. Liquid Radwaste Effluent Line (RM-055)
- b. Steam Generator Blowdown Effluent Line (RM-054 A and B) 1 1 1 1, 5 2, 5
- 2. Flow Rate Measurement Devices
- a. Liquid Radwaste Effluent Line 1
3 3
- b. Steam Generator Blowdown Effluent Line 1
- 3. Radioactivity Recorders
- a. Liquid Radwaste Effluent Line 1
4 4
- b. Steam Generator Blowdown Effluent Line 1
1 If one of the two radiation monitors is inoperable, the activity of both blowdown lines shall be monitored by the operable monitor within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of the declaration of inoperability by the Shift Manager, or the action steps of ACTION 2, Table 2.1.1 should be performed on the Steam Generator that is not being monitored.
I R12
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE CH-ODCM-0001 PAGE 11 OF 132 Table 2.1.1 (continued)
Table Notation ACTION 1 With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided that prior to initiating a release:
- 1. At least two independent samples are analyzed in accordance with applicable chemistry procedures.
- 2. At least two qualified individuals independently verify the release rate calculations.
ACTION 2 With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided that grab samples are analyzed for principal gamma emitters at a sensitivity of 5.OE-07 pCi/gram:
J
- 1. At least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> when the specific activity of the secondary coolant is greater than 0.01 pCi/gram dose equivalent 1-131.
- 2.
At least daily when the specific activity of the secondary coolant is less than or equal to 0.01 pCi/gram equivalent 1-131. Otherwise, suspend release of radioactive effluents via this pathway.
11
ACTION 3 ACTION 4 ACTION 5 With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided the flow rate is determined at least once per four hours during the actual release.
With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided the radioactivity is recorded manually at least once per four hours during the actual release.
During the performance of source checks the effluent radiation monitor is unable to respond, hence is considered inoperable. Effluent releases may continue uninterrupted during the performance of source checks provided the operator is stationed at the monitor during the check. If the effluent radiation monitor fails the source check, carryout the action(s) of the ODCM for the inoperable monitor or terminate the effluent release.
J.
R12
'U~
( C C C C C C C ( C C C C C C C C, C C
(~ C(, C C C C C C C, ( ( (*)(
C C' C C ( C C C C FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL CH-ODCM-0001 PAGE 12 OF 132 REFERENCE USE Table 2.1.2 - Radioactive Liquid Effluent Monitoring Instrumentation Surveillance Requirements C H NN I
INSTRUMENT CHANNEL CHECK CHANNEL CALIBRATION IFUNCTION TEST SOURCE CHECK 2 PRIOR TO RELEASE t
- 1. Radioactivity Monitors Providing Alarm and Automatic Isolation
- a. RM-054A/054B I
l Q
Q P
- b. RM-055
- 2. Flowrate Monitors
- a. Steam Generator Blowdown
-t D
2 2
Visual Flowcheck Daily A Source Check must be completed within 24 hrs prior to release.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 13 OF 132 2.2 Radioactive Gaseous Effluent Instrumentation 2.2.1 Limiting Condition for Operation A. The radioactive gaseous effluent monitoring instrumentation channels shown in Table 2.2.1 shall be OPERABLE with their alarm/trip setpoints set to ensure that the limits of Specification 3.2.1 are not exceeded.
The alarm/trip setpoints of these channels shall be determined in accordance with Section II of the Off-site Dose Calculation Manual.
APPLICABILITY: At all times ACTION:
- 1)
With a radioactive gaseous effluent monitoring instrumentation channel alarm/trip setpoint less conservative than required by the above specification, immediately suspend the releases of radioactive gaseous effluents monitored by the affected channel or declare the channel inoperable.
- 2)
With less than the minimum number of radioactive gaseous effluent monitoring instrumentation channels operable, take the action shown in Table 2.2.1. Restore inoperable effluent monitoring instrumentation to OPERABLE status within 30 days and, if unsuccessful, explain in the next Annual Radiological Effluent Release Report why this inoperability was not corrected in a timely manner. The reporting requirement is limited to the following instrumentation that monitors effluent streams: RM-057, RM-043, RM-062, RM-063, and RM-052.
2.2.2 Surveillance Requirements A.
Each radioactive gaseous effluent monitoring instrumentation channel shall be demonstrated OPERABLE by performance of the CHANNEL CHECK, SOURCE CHECK, CALIBRATION, and CHANNEL FUNCTIONAL TEST at the frequencies shown in Table 2.2.2.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 14 OF 132 Table 2.2.1 - Radioactive Gaseous Effluent Monitoring Instrumentation MINIMUM CHANNELS INSTRUMENT OPERABLE ACTION
- 1. Auxiliary Bldg. Exhaust Stack (RM-052, RM-062)
- a. Noble Gas 1
1, 9,11
- b. Iodine and Particulate 1
2,9,11
- 2. Laboratory and Radwaste Processing Building Stack (RM-043)
- a. Noble Gas 1
3,9
- b. Iodine and Particulate 1
4, 9
- 3. Condenser Off Gas (RM-057)
- a. Noble Gas 1
5,9
- 4. Containment Purge Line (RM-050/51)
- a. Noble Gas 1
1, 6,9, 11,12
- b. Iodine and Particulate 1
2,9, 11,12
- 5. Containment Pressure Relief Line (RM-050/51)
- a. Noble Gas 1
1, 9,11
- b. Iodine and Particulate 1
2,9,11
- 6. Containment Penetrations M72 and M74 (Integrated Leak Rate Test Depressurization Vent Path)
N/A 10 R12
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE Table 2.2.1 (continued)
INSTRUMENT
- 7.
Flow Rate Measurement Devices
- a. Waste Gas Discharge Header
- b. Auxiliary Building Stack
- c. Laboratory and Radwaste Processing Building Stack
- d. Containment Purge Line
- e. Containment Pressure Relief Line Annubar D/P
- 8. Radioactivity Chart Recorders
- a. Auxiliary Building Exhaust Stack CH-ODCM-0001 PAGE 15 OF 132 MINIMUM CHANNELS OPERABLE ACTION 7
7 7
7 7
8 Ii/
'U U
U U
1-i 1-
'U I
V V
U
'U U
U U
U U
UJ U
U R12
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE CH-ODCM-0001 PAGE 16 OF 132 Table 2.2.1 (continued)
TABLE NOTATION ACTION 1 ACTION 2 ACTION 3 ACTION 4 ACTION 5 ACTION 6 ACTION 7 If the Auxiliary Building Exhaust Stack Noble Gas Monitor is inoperable, releases from the containment pressure relief line and the containment purge line are to be secured in the most expeditious manner. Ventilation of the auxiliary building via the Auxiliary Building Exhaust Stack may continue provided grab samples are taken once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> (+25% maximum extension) and analyzed for principal gamma emitters. (See Table 3.2)
If the Auxiliary Building Exhaust Stack Iodine and Particulate Sampler is inoperable, ventilation of the Auxiliary Building and releases from the gaseous waste discharge header, containment pressure relief line or the containment purge line may continue through the Auxiliary Building Exhaust Stack provided sample collection in accordance with Table 3.2 using auxiliary sample collection equipment is initiated within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of the declaration of inoperability by the Shift Manager.
If the Noble Gas Monitor is inoperable, ventilation of the LRWPB may continue via the LRWPB stack provided grab samples will be taken once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> (+ 25% maximum extension) and analyzed for principal gamma emitters. (See Table 3.2)
If the Iodine and Particulate Sampler is inoperable, ventilation of the LRWPB may continue via the LRWPB Stack provided sample collection using auxiliary sample collection equipment is initiated within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of the declaration of inoperability, by the Shift Manager, in accordance with Table 3.2.
During power operation, when the condenser air ejector is in service, the condenser off gas discharge shall be monitored for gross radioactivity. If this monitor is inoperable, grab samples shall be taken once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> (+25%
maximum extension) and analyzed for principal gamma emitters. (See Table 3.2)
The release of airborne effluents from the Containment purge line will be secured if a noble gas monitor is unavailable to monitor the containment building atmosphere.
With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided the flowrate is estimated or recorded manually at least once per four hours during the actual release.
I I
R12
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE CH-ODCM-0001 PAGE 17 OF 132 Table 2.2.1 (continued)
TABLE NOTATION ACTION 8 ACTION 9 ACTION 10 ACTION 11 ACTION 12 With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided the radioactivity level is recorded manually at least once per four hours during the actual release.
During the performance of source checks the effluent radiation monitor is unable to respond, hence is considered inoperable. Effluent releases may continue uninterrupted during the performance of source checks provided the operator is stationed at the monitor during the check. If the effluent radiation monitor fails the source check, carryout the Action(s) of the ODCM for the inoperable monitor or terminate the effluent release.
Automatic release termination capability is not required provided manual isolation can be accomplished in accordance with the requirements of SS-ST-ILRT-0001.
During the ventilation of airborne effluents from the Auxiliary Building Stack at least one Auxiliary Building Exhaust fan shall be in operation.
IF containment purges are made without processing through at least one of the Containment Air Cooling and Filtering Units, and it is confirmed that one half of the annual dose objective listed in Section 3.2.2 will be exceeded during the calender quarter, a special report shall be submitted to the NRC as defined in Section 3.2.4 R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 18 OF 132 Table 2.2.2 - Radioactive Gaseous Effluent Monitoring Instrumentation Surveillance Requirements CHANNEL SOURCE INSTRUMENT CHANNEL CALIBRATION FUNCTION CHECK 2 PRIOR CHECK TEST TO RELEASE
- 1. Radioactivity Monitors Providing Alarm and Automatic Isolation
- a. RM-043 D
R Q
- b. RM-057 D
R Q
- c. RM-062 D
R Q
P
- d. RM-052' D
R Q
P
- 2. Flowrate Monitors
- a. RM-043 Sampler D
R
- b. RM-062 Sampler D
R
- c. RM-052 Sampler D
R
- d. Auxiliary Bldg Exhaust D
R Stack
- e. Laboratory and Radwaste Process Bldg Exhaust D
R Stack
_ Operations Check Air Flow Calibration
- 3. Environmental Monitors
- a. RM-035 M
A
- b. RM-036 M
A
- c. RM-037 M
A
- d. RM-038 M
A
- e. RM-040 M
A
- f. RM-025 M
A
- g. RM-026 M
A
- h. RM-027 M
A I
1 Required when RM-052 is sampling the Auxiliary Building Exhaust Stack.
2 A Source Check must be completed within 24 hrs prior to release.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 19 OF 132
- 3. RADIOACTIVE EFFLUENTS 3.1 Radioactive Liquid Effluents 3.1.1 Concentration A.
Limiting Condition for Operation
- 1)
The release rate of radioactive material in liquid effluents shall be controlled such that the instantaneous concentrations for radionuclides, other than dissolved or entrained noble gases, do not exceed the values specified in 10 CFR Part 20 for liquid effluents at site discharge. To support plant operations, Supervisor-System Chemistry may increase this limit up to the limit specified in Technical Specifications 5.16.1.b. For dissolved or I
entrained noble gases, the concentration shall be limited to 2.OE-04 pCi/ml, total activity.
- 2)
Technical Specification 5.16.1.b establishes the administrative control limit on concentration of radioactive material, other than dissolved or entrained noble gases, released in liquid effluents to unrestricted areas conforming to ten times 10 CFR Part 20.1001-20.2401, Appendix B, Table 2, Column 2. For dissolved or entrained noble gases, the concentration shall be limited to 2.OE-04 pCi/ml total activity.
APPLICABILITY: At all times U
ACTION:
a)
When the concentration of radioactive material released at site discharge exceeds the above limits, appropriate corrective actions shall be taken immediately to restore concentrations J
within the above limits.
B. Surveillance Requirements
- 1)
Radioactive liquid waste shall be sampled and analyzed according to the sampling and analysis program in Table 3.1.
- 2)
The results of the radioactivity analysis shall be used with the calculational methods in Part II of the ODCM to assure that the concentration at the point of release is maintained within the limits of Technical Specification 5.16.1.b.
- 3)
Records shall be maintained of the radioactive concentrations and volume before dilution of each batch of liquid effluent released and of the average dilution flow and length of time over which each discharge occurred. Analytical results shall be submitted to the Commission in accordance with Part I, Section 5.
U R12 U
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE CH-ODCM-0001 PAGE 20 OF 132 Table 3.1 - Radioactive Liquid Effluent Sampling And Analysis A. Monitor & Hotel Waste Tanks Releases B.
Sampling Frequency Type of Activity Analysis Lower Limit of Detection (LLD) (pCi/ml)_'
Each Batch Principal Gamma Emitters 2 5.OE-07 Each Batch 1-131 1.0E-06 Monthly from One Dissolved Noble Gases Batch (Gamma Emitters) 1.OE-05 Monthly Composite 4 H-3 1.OE-05 Monthly Composite 4 Gross Alpha 1.OE-07 Quarterly Composite 4 Sr-89, Sr-90 5.OE-08 Quarterly Composite 4 Fe-55 1.OE-06 Steam Generator Blowdown Sampling Frequency Type of Activity Analysis Lower Limit of Detection l
(LLD) (pCi/ml)
Weekly Composite 4 Principal Gamma Emitters 2 5.0E-07 Weekly Composite 4 1-131 3 1.0E-06 Monthly Dissolved Noble Gases (Gamma Emitters) 1.OE-05 Monthly Composite 4 H-3 1.OE-05 Monthly Composite 4 Gross Alpha 1.OE-07 Quarterly Composite 4 Sr-89, Sr-90 5.OE-08 Quarterly Composite "
Fe-55 1.0E-06 NOTES:
1 LLD is defined in Part II of the ODCM.
2 The principal gamma emitters for which the LLD specification applies exclusively are the following radionuclides: Mn-54, Fe-59, Co-58, Co-60, Zn-65, Mo-99, Cs-134, Cs-137, and Ce-141. Ce-144 shall also be measured, but with a LLD of 5.OE-06.
3 A weekly grab sample and analyses program including gamma isotopic identification will be initiated for the turbine building sump effluent when the steam generator blowdown water composite analysis indicates the 1-131 concentration is greater than 1.0E-06 pCi/ml.
4 To be representative of the average quantities and concentrations of radioactive materials in liquid effluents, samples should be collected in proportion to the rate of flow of the effluent stream. Prior to analyses, all samples taken for the composite should be mixed in order for the composite sample to be representative of the average effluent release.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 21 OF 132 3.1.2 Dose from Radioactive Liquid Effluents A.
Limiting Condition for Operation
- 1) The dose or dose commitment to an individual in unrestricted areas from radioactive materials in liquid effluents during any calendar year shall not exceed 3 millirems to the total body and 10 millirems to any organ.
- 2) The dose or dose commitment to an individual in unrestricted areas from radioactive materials in liquid effluents during any calendar quarter shall not exceed 1.5 millirems to the total body and 5 millirems to any organ.
APPLICABILITY: At all times ACTION:
a) The radiation dose contributions from radioactive materials in liquid effluents released at site discharge shall be determined, in accordance with the methodology and parameters in Part II of the ODCM, on a quarterly basis. If the dose contribution, due to the cumulative release of liquid effluents averaged over a calendar quarter, exceeds one-half of the annual design objectives, the following course of actions shall be taken:
- 1) Make an investigation to identify the causes for such releases.
- 2) Define and initiate a program of action to reduce such releases to the design levels.
- 3) Submit a special report, pursuant to Technical Specification 5.16, within 30 days from the end of the quarter during which the release(s) occurred, identifying the causes and describing the proposed program of action to reduce such releases to the design levels.
B. Surveillance Requirements
'Uo
- 1) Cumulative dose contributions from liquid effluents for the current calender quarter and the current calendar year shall be determined K
in accordance with the methodology and parameters in Part II of the ODCM at least once per quarter.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 22 OF 132 3.1.3 Liquid Radwaste Treatment A.
Limiting Condition for Operation
- 1) The Liquid Radwaste Treatment System shall be OPERABLE, and appropriate portions of these systems shall be used to reduce the radioactive material in liquid wastes so that one half of the annual dose objective listed in ODCM Specification 3.1.2.A will not be exceeded in a calender quarter.
APPLICABILITY: At all times ACTION:
a) Every effort will be made to process all liquid waste, except from the hotel waste tanks, through the Filtration/Ion Exchange (FIX) system before entering the monitor tanks. If the radioactive liquid waste is discharged without processing and it is confirmed that one half of the annual dose objective will be exceeded during the calender quarter, a special report pursuant to Technical Specification 5.16, shall be prepared and submitted to the Nuclear Regulatory Commission within 30 days of the end of the quarter during which the equipment or subsystem(s) were inoperable. This report shall include the following information:
- 1) Identification of equipment or subsystem(s) not operable and reasons for inoperability.
- 2) Action(s) taken to restore the inoperable equipment to operable status.
- 3) Summary description of action(s) taken to prevent a recurrence.
B. Surveillance Requirements
- 1)
Dose due to liquid releases shall be projected frequently and at least once per quarter, in accordance with the methodology and parameters in Part II of the ODCM, when Liquid Radwaste Treatment Systems are not fully OPERABLE.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 23 OF 132 K
3.1.3B
- 2)
OPERABLE is defined as follows:
A filtration/ion exchange (FIX) system will be utilized for processing liquid radwaste. The system consists of a booster pump, charcoal pretreatment filter, and pressure vessels containing organic/inorganic resins, which can be configured for optimum performance. The effluent from the FIX system is directed to the K
monitor tanks for release.
Waste filters (WD-17A and WD-17B) are used only on those occasions when considered necessary, otherwise the flows from the low activity fluids may bypass the filters. No credit for K) decontamination factors (iodines, Cs, Rb, others) was taken for these filters during the 10 CFR Part 50 Appendix I dose design objective evaluation; therefore, the inoperability of these filters does not affect the dose contributions to any individual in the unrestricted K) areas via liquid pathways. The inoperability of waste filters will not be considered a reportable event in accordance with the Action listed above.
3.1.4 Liquid Holdup Tanks Tanks included in this Specification are those outdoor tanks that are not surrounded by liners, dikes, or walls capable of holding the tanks contents J
and that do not have tank overflows and surrounding area drains connected to the liquid radwaste treatment system.
A.
Limiting Condition for Operation v
- 1) The quantity of radioactive material contained in each unprotected outdoor liquid holdup tank shall not exceed 10 curies, excluding tritium and dissolved or entrained noble gases.
APPLICABILITY: At all times ACTION:
K a) When the quantity of radioactive material in any unprotected outdoor liquid holdup tank exceeds 10 curies, excluding tritium and dissolved or entrained noble gasses, immediately suspend all additions of radioactive material to the tank and within 48 K
hours reduce the tank contents to within the limit.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 24 OF 132 3.1.4 B. Surveillance Requirements
- 1) The quantity of radioactive material contained in each outdoor liquid holdup tank shall be determined to be within the above limit by analyzing a representative sample of the tank's contents at least once per 7 days when radioactive material is being added to the tank.
3.2 Radioactive Gaseous Effluents 3.2.1 Concentration A.
Limiting Condition for Operation
- 1) The release rate of radioactive material in airborne effluents shall be controlled such that the instantaneous concentrations of radionuclides does not exceed the values specified in 10 CFR Part 20 for airborne effluents at the unrestricted area boundary. To support plant operations, Supervisor-System Chemistry may increase this limit up to the limits specified in Technical Specification 5.16.1.g.
- 2) Technical Specification 5.16.1.g establishes the administrative control limit on the concentration resulting from radioactive material, other than noble gases, released in gaseous effluents to unrestricted areas conforming to ten times 10 CFR Part 20.1001-20.2401, Appendix B, Table 2, Column 1. For noble gases, the concentration shall be limited to five times 10 CFR Part 20.1001-20.2401, Appendix B, Table 2, Column 1.
APPLICABILITY: At all times ACTION:
a) When the concentration of radioactive material released to unrestricted areas exceeds the above limits, appropriate corrective actions shall be taken immediately to restore concentrations within the above limits.
B. Surveillance Requirements
- 1) Radioactive gaseous wastes shall be sampled and analyzed according to the sampling and analysis program of Table 3.2. The results of the radioactivity analysis shall be used to assure the limits in 3.2.1.A are not exceeded.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 25 OF 132 Table 3.2 - Radioactive Airborne Effluent Sampling And Analysis A. Gas Decay Tank Releases B.
C.
SampingFreqenc Typ ofActiityAnalsisLower Limit of Detection SampingFreqenc Typ ofActiityAnalsis(LLD) (pCi/mI)1 Prior to each release Principal Gamma Emitters 2 1.OE-04 Containment Purge Releases or Containment Pressure Relief Line Releases 5 n F c T Lower Limit of Detection Sampling Frequency Type of Activity Analysis (LLD) (pCi/ml)'
Prior to each release Principal Gamma Emitters 2 1.OE-04 Prior to each release H-3 1.OE-06 Condenser Off Gas Releases '
Lower Limit of Detection Sampling Frequency Type of Activity Analysis (LLD) (pCi/ml)'
Monthly 3 Tritium (H-3) 1.OE-06 Monthly Principal Gamma Emitters 2 1.OE-04 D. Auxiliary Building Exhaust Stack and Laboratory and Radwaste Building Exhaust Stack 5 n F c T Lower Limit of Detection Sampling Frequency Type of Activity Analysis (LLD) (pCi/ml) 1 Weekly (Charcoal Sample) 1-131 1.OE-12 Weekly (Particulates)
Principal Gamma Emitters 2, 1-131, and Particulates with half-lives >
eight (8) days.
1.OE-1 1 Weekly (Noble Gases)
Principal Gamma Emitters 2 1.OE-4 Monthly Composite 4 Gross Alpha 1.OE-1 1 Quarterly Composite (Particulates)
Sr-89, Sr-90 1.OE-11 R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION.MANUAL REFERENCE USE PAGE 26 OF 132 Table 3.2 (continued)
NOTES:
1 LLD is defined in Part II of the ODCM 2
The principal gamma emitters for which the LLD specification applies exclusively are the following radionuclides: Kr-87, Kr-88, Xe-133, Xe-133m, Xe-135, and Xe-138 for gaseous emissions and Mn-54, Fe-59, Co-58, Co-60, Zn-65, Mo-99, Cs-134, Cs-137, and Ce-141.
Ce-144 for particulate emissions.
3 Required only when steam generator blowdown radioactivity for tritium (Table 3.1, Item B) exceeds 3.OE-03 pCi/milliliter.
4 Frequency requirement may be satisfied using weekly gross alpha results from particulate sampling media.
5 Particulate and Iodine samples shall be corrected for sampler deposition/transportation efficiency by using the approved software programs or by multiplying the activity obtained by the associated sampler multiplication factor (See Table 3.3).
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 27 OF 132 Table 3.3 - Sampler Deposition/transportation Correction Factors PARTICULATE IODINE SAMPLER SAMPLE DF ACTMULT' DF ACTMULT 1 RM-062 AB 0.411 2.433 0.669 1.495 RM-052 2 AB 0.638 1.567 0.653 1.531 RM-052 2 CONT 0.525 1.905 0.688 1.453 RM-051 CONT 0.624 1.603 0.714 1.401 RM-043 LRWPB 0.809 1.236 0.873 1.236 PORTABLE CONT 1.000 1.000 0.950 1.053 ACRONYM DEFINITIONS:
AB - Auxiliary Building Exhaust Stack CONT - Containment Building LRWPB - Laboratory and Rad Waste Processing Building DF - Deposition Factor ACTMULT - Activity multiplication factor to correct for sample loss.
1 ACTMULT factors are automatically determined using the appropriate analysis sequence file for the sample type.
2 Sampler can be used to monitor either the Containment or Auxiliary Building.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 28 OF 132 3.2.2 Dose - Noble Gases A. Limiting Condition for Operation
- 1)
During any calender year: Less than or equal to 10 mrads for gamma radiation and less than or equal to 20 mrads for beta radiation.
- 2)
During any calender quarter: Less than or equal to 5 mrads for gamma radiation and less than or equal to 10 mrads for beta radiation.
APPLICABILITY: At all times ACTION:
a) If the dose contribution, due to the cumulative release of noble gases in airborne effluents averaged over a calendar quarter exceeds one-half of the annual design objectives, the following course of actions shall be taken:
- 1) Make an investigation to identify the cause for such release rates.
- 2) Define and initiate a program of action to reduce such releases to design levels.
- 3) Submit a special report, pursuant to Technical Specification 5.16, within 30 days from the end of the quarter during which the release(s) occurred, identifying the causes and describing the proposed program of action to reduce dose contributions. -
B. Surveillance Requirements
- 1) The radiation dose contributions from radioactive noble gases in airborne effluents shall be determined, in accordance with the methodologies and parameters of Part II of the ODCM, on a quarterly basis.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 29 OF 132 3.2.3 Dose - lodine-131, Radioactive Material in Particulate Form with Half-Lives Greater than 8 Days (Other than Noble Gases) and Tritium A. Limiting Condition for Operation
- 1) The dose to an individual or dose commitment to any organ of an individual in unrestricted areas due to the release of 1-131, Tritium, and radioactive materials in particulate form with half-lives greater than eight days (excluding noble gases) in airborne effluents shall not exceed 7.5 millirems in any calender quarter and 15 millirems from all exposure pathways during any calendar year.
APPLICABILITY: At all times ACTION:
a) If the dose contribution, due to the cumulative release of 1-131, Tritium, and radioactive materials in particulate form with half-lives greater than eight days (excluding noble gases) in airborne effluents averaged over a calendar quarter exceeds one-half of the annual design objectives, the following course of actions shall be taken:
- 1) Make an investigation to identify the cause for such release iJ rates.
- 2) Define and initiate a program of action to reduce such releases to design levels.
- 3) Submit a special report, pursuant to Technical Specification 5.16, within 30 days from the end of the quarter during which the release(s) occurred, identifying the causes and describing the proposed program of action to reduce dose contributions.
B. Surveillance Requirements
- 1) The radiation dose contributions from 1-131, Tritium, and radioactive materials in particulate form with half-lives greater than eight days (excluding noble gases) in airborne effluents shall be determined, in accordance with the methodologies and parameters of Part II of the ODCM, on a quarterly basis.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 30 OF 132 3.2.4 Gaseous Radwaste Treatment A.
Limiting Condition for Operation
- 1) In accordance with Technical specification 5.16.1.f, the Waste Gas System and the Ventilation Exhaust Systems shall be OPERABLE, and appropriate portions of these systems shall be used to reduce the radioactive material in gaseous wastes so that one half of the annual dose objectives listed in ODCM Specifications 3.2.2.A and 3.2.3A will not be exceeded.
APPLICABILITY: At all times ACTION:
a) If radioactive gaseous waste is discharged without treatment and it is confirmed that one half of the annual dose objective will be exceeded during the calender quarter, a special report pursuant to Technical Specification 5.16, shall be prepared and submitted to the Nuclear Regulatory Commission within 30 days of the end of the quarter during which the equipment or subsystem(s) were inoperable. This report shall include the following information:
- 1) Identification of equipment or subsystem(s) not operable and reasons for inoperability.
- 2) Action(s) taken to restore the inoperable equipment to operable status.
- 3) Summary description of action(s) taken to prevent a recurrence.
B. Surveillance Requirements
- 1) Dose due to gaseous releases shall be projected frequently and at least once per quarter, in accordance with the methodology and parameters in Part II of the ODCM, when Waste Gas Systems and Ventilation Exhaust Systems are not fully OPERABLE.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 31 OF 132 3.2.41B
- 2)
OPERABLE is defined as follows:
a) Waste Gas System The waste airborne radioactive material at Fort Calhoun Station is collected in the vent header where the gas compressors take suction, compress the gas and deliver it to one of the four gas decay tanks. The waste airborne radioactive material is treated in these gas decay tanks by holding for radioactive decay prior to final controlled release to the environs. In order to provide conformance with the dose design objectives, gas decay tanks are normally stored for approximately 30 days, with earlier release allowed to support plant operation only, and thus achieve decay of short half-life radioactive materials, e.g., 1-131, Xe-133. If the radioactive airborne wastes from the gas decay tanks are discharged without processing in accordance with the above conditions, and it is confirmed that one half of the annual dose objective will be exceeded during the calendar quarter, a special report shall be submitted to the Commission pursuant to Section 3.2.4A.
b)
Ventilation Exhaust Systems The radioactive effluents from the controlled access area of the auxiliary building are filtered by the HEPA filters in the auxiliary building ventilation system. If the radioactive effluents are discharged without the HEPA filters, a special report shall be submitted to the NRC as defined in Action a) above.
The discharge from the gas decay tanks is routed through charcoal and HEPA filter unit VA-82. No credit was taken for the operation of hydrogen purge filters during the 10 CFR Part 50, Appendix I dose design evaluation and doses through the airborne effluent pathways were well below the design objectives. The unavailability of hydrogen purge filters will not be considered a reportable event.
The containment air is processed through at least one of the redundant containment HEPA and charcoal filters in the Containment Air Cooling and Filtering Units prior to purging. If the containment purges are made without processing through one of the Containment Air Cooling and Filtering Units, and it is confirmed that one half of the annual dose objective will be exceeded during the calender quarter, a special report shall be submitted to the NRC as defined in Action a) above.
R12
'-I
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 32 OF 132 3.3 Uranium Fuel Cycle 3.3.1 Total Dose-Uranium Fuel Cycle A.
Limiting Condition for Operation
- 1)
The dose to any real individual from uranium fuel cycle sources shall be limited to < 25 mrem to the total body or any organ (except the thyroid, which shall be limited to < 75 mrem) during each calendar year.
APPLICABILITY: At all times ACTION:
a)
With the calculated dose from the release of radioactive materials in liquid or gaseous effluents exceeding twice the limits of Specifications 3.1.2.A, 3.2.2.A, or 3.2.3.A, calculations shall be made including direct radiation contribution from the plant and outside storage tanks to determine whether the above limits have been exceeded. If such is the case, in lieu of any other report required by Section 5.2, prepare and submit a Special Report to the Commission pursuant to Technical Specification 5.16 that defines the corrective action to be taken to reduce subsequent releases to prevent recurrence of exceeding the above limits and includes the schedule for achieving conformance with the above limits. This Special Report, as defined in 10 CFR Part 20.2203(a)(4) and 20.2203(b), shall include an analysis that estimates the radiation exposure (dose) to a MEMBER OF THE PUBLIC from uranium fuel cycle sources, including all effluent pathways and direct radiation, for the calender year that includes the release(s) covered by this report. It shall also describe levels of radiation and concentration of radioactive material involved, and the cause of exposure levels or concentrations. If the estimated dose(s) exceeds the above limits, and if the release condition resulting in the violation of 40 CFR Part 190 has not already been corrected, the Special Report shall include a request for a variance in accordance with the provisions of 40 CFR Part 190. Submittal of the report is considered a timely request, and a variance is granted until staff action on the request is complete.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 33 OF 132 3.3.1 B. Surveillance Requirements Cumulative dose contributions from liquid and gaseous effluents shall be determined in accordance with Surveillance requirements 3.1.2B, 3.2.2B and 3.2.31B and in accordance with the methodology and parameters in Part II of the ODCM.
- 4. RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (REMP) 4.1 Monitoring Program 4.1.1 Limiting Condition for Operation A. The Radiological Environmental Monitoring Program shall be conducted as specified in Table 4.1.
APPLICABILITY: At all times ACTION:
- 1) Analytical results of this program and deviations from the sampling schedule shall be reported to the Nuclear Regulatory Commission in the Annual Radiological Environmental Operating Report (Section 5.2).
- 2)
If the level of radioactivity from calculated doses leads to a higher exposure pathway to individuals, this pathway shall be added to the Radiological Environmental Monitoring Program.
- 3)
If the level of radioactivity in an environmental sampling medium exceeds the reporting level specified in Table 4.4, and the activity is attributable to plant operation, a Special Report shall be prepared and submitted to the Nuclear Regulatory Commission within 30 days from the end of the quarter (Section 5.2.3). The detection capabilities of the equipment used for the analysis of environmental samples must meet the requirements of Table 4.3 for Lower Level of Detection (LLD).
- 4)
Radiological environmental sampling locations and the media that is utilized for analysis are presented in Table 4.2. Sampling locations are also illustrated on the map, Figure 1. Details of the emergency TLD locations are contained in surveillance test CH-ST-RV-0009, Environmental Sample Collection - Emergency Planning Zone Dosimeters.
R12
'-I
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 34 OF 132 4.1.1A
- 5)
Deviations from the monitoring program, presented in this section and detailed in Table 4.2, are permitted if specimens are unobtainable due to mitigating circumstances such as hazardous conditions, seasonal unavailability, malfunction of equipment, or if a person discontinues participation in the program, etc. If the equipment malfunctions, corrective actions will be completed as soon as practicable. If a person no longer supplies samples, a replacement will be made if possible. All deviations from the sampling schedule will be described in the Annual Radiological Environmental Operating Report, pursuant to Section 5.2.
4.1.2 Surveillance Requirements A. The Radiological Environmental Monitoring Program (REMP) shall be collected and analyzed in accordance with Tables 4.1, 4.2, and 4.3.
R12
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE CH-ODCM-0001 PAGE 35 OF 132 Table 4.1 - Radiological Environmental Monitoring Program Exposure Pathway Collection Site' Type of Analysis 2 Frequency and/or Sample
- 1. Direct Radiation A. Thirteen TLD indicator stations, Gamma dose Quarterly two control stations, total of 15.
B. An inner-ring of 16 stations, one Gamma dose during Site Replaced in each cardinal sector in the Area and General Annually general area of the unrestricted Emergencies only.
area boundary and within 2.5 miles.
C. An outer-ring of 16 stations, 1 in Gamma dose during Site Replaced each cardinal sector located Area and General Annually outside of the inner-ring, but no Emergencies only.
more distant than approximately 5 miles.
- 2. Air Monitoring A. Indicator Stations Filter for Gross Beta 3 Weekly
- 1. 3 stations in the general area Charcoal for 1-131 Weekly of the unrestricted area boundary Filter for Gamma Isotopic Quarterly composite
- 2. City of Blair of weekly filters
- 3. Desoto Township
- 4. 2 Offsite locations B. One background station
- 3. Water A. Missouri River at nearest Gamma Isotopic, H-3 Monthly downstream drinking water composite for intake.
Gamma Isotopic Analysis B. Missouri River downstream near the mixing zone.
Quarterly composite for H-3 C. Missouri River upstream of Plant Analysis intake (background).
I K-)
K)1
\\K)
I
)_
-)
R12
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE CH-ODCM-0001 PAGE 36 OF 132 Table 4.1 - Radiological Environmental Monitoring Program Exposure Pathway Collection Site 1 Type of Analysis 2 Frequency and/or Sample
- 4. Milk4 A. Nearest milk animal (cow or Gamma Isotopic and 1-131 Semimonthly goat) within 5 miles grazing season (May to October)
B. Milk animal (cow or goat) between 5 miles and 18.75 miles (background).
- 5. Fish A. Four fish samples within vicinity Gamma Isotopic Once per season of Plant discharge.
(May to October)
B. One background sample upstream of Plant discharge.
- 6. Sediment A. One sample from downstream Gamma Isotopic Semiannually area on the station side of the Missouri River.
B. One sample from upstream of Plant Intake (background).
- 7. Vegetables or A. One sample in the highest Gamma Isotopic Once per season Food Products 5 exposure pathway.
(May to October)
B. -One sample from onsite crop field C. One sample outside of 5 miles (background).
I NOTES:
1 See Table 4.3 for required detection limits.
2 The Lower Limit of Detection (LLD) for analysis is defined in the ODCM in accordance with the wording of NUREG-0472, Rev. 3, Draft 7.
3 When a gross beta count indicates radioactivity greater than 1 E-1 2 pCi/ml or 1 pCi/iM3, a gamma spectral analysis will be performed.
4 If milk samples are temporarily not available at a sampling site due to mitigating circumstances, then vegetation (broadleaf, pasture grass, etc.) shall be collected as an alternate sample at the site. If there are no milk producers within the entire 5-mile radius of the plant, then vegetation shall be collected at the offsite location having the highest calculated annual average ground level D/Q. (Reference ODCM Part 2, Table 4
'Highest Potential Exposure Pathways for Estimating Dose")
5 Samples should be collected from garden plots of 500 ft2 or more. (Reference Reg. Guide 4.8 "Environmental Technical Specifications for Nuclear Power Plants," Dec. 1975).
R12
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL CH-ODCM-0001 PAGE 37 OF 132 REFERENCE USE Table 4.2 - Radiological Environmental Sampling Locations And Media Approximate Approximate Sample Approximate Distance from Direction Air Monitoring Vegetables Station Collection Sites Center of (degrees Sector TLD Water Milk Sediment Fish and Food No.
Containment from true Airborne Airborne Products (miles) north)
Particulate Iodine Onsite Station, 1
110-meter weather 0.53 29301MNW P
X X
X tower Onsite Station, 2
adjacent to old plant 0.59 207'/SSW K
X X
X access road Offsite Station, 3
Intersection of Hwy.
0.94 1450/SE G
X X
X 75 and farm access road 4
Blair OPPD office 2.86 305 0/NW Q
X X
X 5
EOF Building, North 14.9 1530/SSE H
X Omaha Power Station 1
6 Fort Calhoun, NE City 5.18 150 0/SSE H
X Hall Fence around intake 7
gate, Desoto Wildlife 2.07 102 0/ESE F
X Refuge Onsite Station, 8
entrance to Plant Site 0.55 191 O/S J
X from Hwy. 75 9
Onsite Station, NW of 0.68 3050/NW Q
X Plant I
II I
I I
I I
R12 C C C C C ( C C C C ( C ( C C C. C C C C ( C C C C C C C C C. C C C. C c C C C C C. C C
(( (,(
r)(,(,(
( )CA.(( '(
(_ M '( ( (,.( (" (J '( ;
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL CH-ODCM-0001 PAGE 38 OF 132 REFERENCE USE Table 4.2 - Radiological Environmental Sampling Locations And Media Approximate Approximate Air Monitoring Sample Distance from Direction Vegetables Station Coximate Center of (degrees Sector TLD Water Milk Sediment Fish and Food No.
Collection Sites Containment from true Airborne Airborne Products (miles) north)
Particulate Iodine Onsite Station, WSW0.142WW MX 10 of Plant 0.61 242°/SW M
X 1
Offsite Station, SE of 1.07 139°/SE G
X P lant Metropolitan Utilities 12 Dist., Florence 14.3 154°tSSE H
X Treatment Plant North Omaha, NE West bank Missouri 13 River, downstream 0.45 1080/ESE F
X X
from Plant discharge Upstream from Intake 14 Bldg, west bank of 0.09 40/N A
X X
river__
16'
^
171 18' 19' 20 Mohr Dairy 9.86 186 0/S J
X 2 X
211
_
=
22 Fish Sampling Area, 0.08 60/N A
X Missouri River (R.M. 645.0)
I R12
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL CH-ODCM-0001 PAGE 39 OF 132 REFERENCE USE Table 4.2 - Radiological Environmental Sampling Locations And Media Approximate Approximate Sample Approximate Distance from Direction Air Monitoring Vegetables Station Collection Sites Center of (degrees Sector TLD Water Milk Sediment Fish and Food No.
Containment from true Airborne Airborne Products (miles) north)
Particulate Iodine 23 Fish Sampling Area, 17.9 3580/N A
X 23 Missouri River (R.M. 666.0) 24' 25' 2 6 1
_ _ _ _v _=X __X 27'
=
=
==
283 Alvin Pechnik Farm 0.94 163 0/SSE H
X X
X X
291 30' 31' 32 Valley Substation #902 19.6 221 0/SW L
X X
X 333 Bansen Farm 0.7 2030/SSW K
2 34'
=
=
35 Onsite Farm Field 0.52 1180/ESE F
X Offsite Station 363 Intersection 0.75 227 0/SW L
X X
X Hwy 75/Co.Rd. P37 373 Offsite Station Desoto 1.57 1440/SE G
X X
X Township NOTES:
(1) Location is currently discontinued and is documented in the table for historical reference only.
(2) When a milk sample is not available at a location, a broad leaf (pasture grass) vegetation sample will be collected at that location as a substitute.
(3) Locations represent highest potential exposure pathways as determined by the biennial Land Use Survey, performed in accordance with Part 1, Section 6.3.2, and are monitored as such.
R12 C C C (C C C
(
(C
(
C (C
(
C C ( (
C
(
C C ( C (
C (
C C (
C
(
C C C C ( (
(
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE Figure 1 - Environmental Radiological Sampling Points*
CH-ODCM-0001 PAGE 40 OF 132 Locations currently discontinued are not illustrated.
R12
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL CH-ODCM-0001 PAGE 41 OF 132 REFERENCE USE Table 4.3 - Detection Capabilities For Environmental Sample Analysis Lower Limit of Detection (LLD) ',2,3 Sample Units l H-3 Mn-54 Fe-59 Co-58, Zn-65 Zr-95 Nb-95 1-131 Cs-134 Cs-137 Ba-140 Beta Co-6O Water pCi/L
=
2.OE+03 1.5E+01 3.OE+01 1.5E+01 3.OE+01 1.5E+01 1.5E+01 1.0E+004 1.5E+01 1.8E+01 1.5E+01 Fish pCi/kg (wet) 1.3E+02 2.6E+02 1.3E+02 2.6E+02 1.3E+02 1.5E+02 Milk pCi/L 1.OE+00 1.5E+01 1.8E+01 1.5E+01 Airborne Particulates or Gases pci/m3
- 1. OE-02 7.0E-02 1.OE-02 1.OE-02 Sediment pCi/kg (dry) 1.5E+02 1.8E+02 Grass or Broad 5
s 5
Leaf Vegetation/
Vegetables or pCi/kg 6.OE+01 6 OE+01 8.OE+01 Food Products (wet) 1 This list does not mean that only these nuclides are to be considered. Other peaks that are identifiable as Plant effluents, together with those of the above nuclides, shall also be analyzed and reported in the Annual Radiological Environmental Operating Report pursuant to Part I, Section 5.2.
2 Required detection capabilities for thermoluminescent dosimeters used for environmental measurements shall be in accordance with the recommendations of Regulatory Guide 4.13.
3 The LLD is defined in Part ll of the ODCM.
4 LLD for drinking water samples. If no drinking water pathway exists, the LLD of gamma isotopic analysis may be used.
5 1-13 1 analysis performed on broadleaf/pasture grass samples when milk is unavailable. Gamma isotopic analysis performed on food products/vegetables.
R12 C C C (
C C C C C C (C C
C C C C C C C (
C C C C C (
C C C (
(
C C (
C C C C C C C
(C, C ( ( C (<C('bQ (<(
C K K'C(
( C,
'(,(,C ",C K K
(
K K
,(
(C -
C ( CC (<C ( (C C (K C K C
((
FORT CALHOUN STATION OFF-SITE DOSE CALCULATION MANUAL CH-ODCM-0001 PAGE 42 OF 132 REFERENCE USE Table 4.4 - Reporting Levels for Radioactivity Concentrations in Environmental Samples 1 Sample Units H-3 Mn-54 Fe-59 Co-58 Co.60 Zn-65 Zr-95 Nb-95 1-131 Cs-134 Cs-137 Ba-140 Water pCi/L 2.OE+04 1.OE+03 4.OE+02 1.OE+03 3.OE+02 3.OE+02 4.OE+02 4.OE+02 2.OE+002 3.OE+01 5.OE+01 2.OE+02 Fish pCi/kg (wet) 3.OE+04 1.OE+04 3.OE+04 1.OE+04 2.OE+04 1.OE+03 2.OE+03 Milk pCi/L 3.OE+00 6.OE+01 7.OE+01 3.OE+02 Airborne Particulates or pCi/m 3
9.OE-01 1.0E+01 2.OE+01 Gases Grass or Broad Leaf Vegetation/
Vegetables or pCi/kg 1.0E+02 1.0E+03 2.OE+03 Food Products (wet) 1 A Non-routine report shall medium and:
be submitted when more than one of the radionuclides listed above are detected in the sampling Concentration 1 Concentration 2
+ Concentration 3 +..* Ž1.0 Reporting Level 1 Reporting Level 2 Reporting Level 3 When radionuclides other than those listed above are detected and are the result of Plant effluents, this report shall be submitted if the potential annual dose to a member of the general public is equal to or greater than the dose objectives of Part I, Section 3.1 and 3.2. This report is not required if the measured level of radioactivity was not the result of Plant effluents; however, in such an event, the condition shall be reported and described in the Annual Radiological Environmental Operating Report.
2 If no drinking water pathway exists, the LLD of gamma isotopic analysis may be used.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 43 OF 132 4.2 Land Use Survey 4.2.1 Limiting Condition for Operation A. A Land Use Survey shall identify the location of the nearest milk animal, nearest meat animal, nearest vegetable garden, and the nearest residence in each of the 16 cardinal sectors within a distance of five miles. The survey shall be conducted under the following conditions:
1 ) Within a one-mile radius from the Plant site, enumeration by door-to-door or equivalent counting techniques.
- 2) Within a Five-mile radius, enumeration may be conducted door-to-door or by using referenced information from county agricultural agents or other reliable sources.
APPLICABILITY: At all times ACTION:
a)
If it is learned from this survey that milk animals, vegetable gardens and resident receptors are present at a location which yields a calculated dose greater than 20% from previously sampled location(s), the new location(s) shall be added to the monitoring program. Milk and vegetable garden sampling location(s) having the lowest calculated dose may then be dropped from the monitoring program at the end of the grazing and/or growing season during which the survey was conducted and the new location added to the monitoring program. Modifications to the air monitoring locations will be made as soon as practicable. The Nuclear Regulatory Commission shall be notified of modifications to the program in the Annual Radiological Environmental Operating Report (Section 5.2).
b) If it is learned from this survey that a pathway for dose to a MEMBER OF THE GENERAL PUBLIC no longer exists, an additional pathway has been identified or site specific factors affecting the dose calculations for a pathway have changed, then this information should be documented in the Land Use Survey and the Annual Radioactive Effluent Release Report. This information can be used to increase the accuracy of the dose models for the Annual Radioactive Effluent Release Report as well as dose estimates performed during the reporting period (i.e., quarterly dose estimates).
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 44 OF 132 4.2.2 Surveillance Requirements A. A land use survey shall be conducted once per 24 months between the dates of June 1 and October 1. The results of the land use survey shall be submitted to the Nuclear Regulatory Commission in the Annual Radiological Environmental Operating Report (Section 5.2).
4.3 Interlaboratory Comparison Program 4.3.1 Limiting Condition for Operation A. Analyses shall be performed on radioactive materials as part of an Interlaboratory Comparison Program that has been approved by the Nuclear Regulatory Commission.
APPLICABILITY: At all times ACTION:
- 1) With analysis not being performed as required above, report the corrective actions taken to prevent a recurrence to the Commission in the Annual Radiological Environmental Operating Report (Section 5.2).
4.3.2 Surveillance Requirements A. The results of these analyses shall be included in the Annual Radiological Environmental Operating Report (Section 5.2).
- 5. ADMINISTRATIVE CONTROLS 5.1 Responsibilities 5.1.1 FCS Chemistry Department is responsible for the implementation and maintenance of the ODCM.
5.1.2 FCS Operations Department is responsible for the compliance with the ODCM in the operation of Fort Calhoun Station.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 45 OF 132 5.2 Radioactive Effluent Reporting Requirements The reporting requirements for radioactive effluents stated in this Section are to provide assurance that the limits set forth in Section I are complied with. These reports will meet the requirements for documentation of radioactive effluents contained in 10 CFR Part 50.36a; Reg. Guide 1.21, Rev. 1; Reg. Guide 4.8, Table 1; and Reg. Guide 1.109, Rev. 1.
5.2.1 Annual Radioactive Effluent Release Report A report covering the operation of the Fort Calhoun Station during the previous calendar year shall be submitted prior to May 1 of each year per the requirements of Technical Specifications 5.9.4.a. and 10 CFR Part 50.
The Radioactive Effluent Release Report shall include:
A.
A summary of the quantities of radioactive liquid and airborne effluents and solid waste released from the plant as outlined in Regulatory Guide 1.21, Revision 1.
B. A summary of the meteorological conditions concurrent with the release of airborne effluents during each quarter as outlined in Regulatory Guide 1.21, Revision 1.
C. An assessment of radiation doses from the radioactive liquid and airborne effluents released from the unit during each calendar quarter as outlined in Regulatory Guide 1.21, Revision 1. The assessment of radiation doses shall be performed in accordance with calculational methodology of the Regulatory Guide 1.109, Revision 1.
D. Changes to the Process Control Program (PCP) or to the Offsite Dose Calculation Manual (ODCM) made during the reporting period. Each change shall be identified by markings in the margin of the affected pages clearly indicating the area of the page that was changed and shall indicate the date the change was implemented.
E. A list and description of abnormal releases from the site to unrestricted areas of radioactive materials in gaseous and liquid effluents made during the reporting period.
F. An explanation of why instrumentation designated in the ODCM Part I, Sections 2.1.1 and 2.2.1 was not restored to OPERABLE status within 30 days.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 46 OF 132 5.2.1 G. A description of any major design changes or modifications made to the Liquid and/or Gaseous Radwaste Treatment Systems or Ventilation Exhaust Systems during the reporting period.
H. An explanation of why the liquid and/or gaseous radwaste treatment systems were not OPERABLE, causing the limits of Specifications 3.1.3.A and 3.2.4.A to be exceeded.
5.2.2 Annual Radiological Environmental Operating Report The Annual Radiological Environmental Operating Report for the previous one year of operation shall be submitted prior to May 1 of each year. This report contains the data gathered from the Radiological Environmental Monitoring Program. The content of the report shall include:
A. Summarized and tabulated results of the radiological environmental sampling/analysis activities following the format of Regulatory Guide 4.8, Table 1. In the event that some results are not available, the report shall be submitted noting and explaining the reasons for the missing results. The missing data shall be submitted as soon as possible in a supplementary report.
B. Interpretations and statistical evaluation of the results, including an assessment of the observed impacts of the plant operation and environment.
C. The results of participation in a NRC approved Interlaboratory Comparison Program.
D. The results of land use survey required by Section 4.2 E. The results of specific activity analysis in which the primary coolant exceeded the limits of Technical Specification 2.1.3.- The following information shall be included:
- 1) Reactor power history starting 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> prior to the first sample in which the limit was exceeded.
- 2)
Results of the last isotopic analysis for radioiodine performed prior to exceeding the limit, results of analysis while limit was exceeded and results of one analysis after the radioiodine activity was reduced to less than the limit. Each result should include date and time of sampling and the radioiodine concentrations.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 47 OF 132 5.2.2E
- 3)
Purification system flow history starting 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> prior to the first sample in which the limit was exceeded.
- 4)
Graph of the 1-131 concentration and one other radioiodine isotope concentration in micro-curies per gram as a function of time for the duration of the specific activity above the steadystate level, AND
- 5) The time duration when the specific activity of the primary coolant exceeded the radioiodine limit.
5.2.3 Special Report If the limits or requirements of Sections 3.1.2A, 3.1.3A, 3.2.2A, 3.2.3A, 3.2.4A, 3.3.1A and/or 4.1.1A.3) are exceeded, a Special Report shall be issued to the Commission, pursuant to Technical Specification 5.16. This
- 1 report shall include:
A.
The results of an investigation to identify the causes for exceeding the specification.
B. Define and initiate a program of action to reduce levels to within the specification limits.
C. The report shall also include an evaluation of any release conditions, environmental factors, or other aspects necessary to explain the condition.
5.2.4 EPA 40 CFR Part 190 Reporting Requirements With the calculated dose from the release of radioactive materials in liquid or gaseous effluents exceeding twice the limits of dose from Specifications 3.1.2.A, 3.2.2.A, or 3.2.3.A, calculations shall be made including direct radiation calculations, to prepare and submit a special report to the Commission within 30 days and limit the subsequent releases such that the dose to any real individual from uranium fuel cycle sources is limited to
< 25 mrem to the total body or any organ (except thyroid, which is limited to
< 75 mrem) over the calendar year. This special report shall include an analysis which demonstrates that radiation exposures to any member of the public from uranium fuel cycle sources (including all effluent pathways and direct radiation) are less than the 40 CFR Part 190 standard. Otherwise, obtain a variance from the Commission to permit releases which exceed the 40 CFR Part 190 standard. The submittal of the report is to be considered a timely request and a variance is granted pending the final action on the variance request from the Commission.
R12 j
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 48 OF 132 5.3 Change Mechanism The ODCM is the controlling document for all radioactive effluent releases. It is defined as a procedure under the guidance of Technical Specification 5.8. It will be revised and reviewed by the Plant Review Committee and approved by the Plant Manager in accordance with Technical Specification 5.17. All changes to the ODCM will be forwarded to the Nuclear Regulatory Commission during the next reporting period for the Annual Radioactive Effluent Release Report in accordance with the requirements of Technical Specification 5.17.
5.4 Meteorological Data The Annual Average X/Q is utilized to determine the concentrations of radionuclides at the unrestricted area boundary. It is also the factor used in conjunction with the parameters and methodologies in Part II to determine unrestricted area dose on a quarterly bases or as needed. It is based on an average of the highest calculated sector X/Q values, using all 16 sectors for each of the three previous year Annual Radioactive Effluent Release Reports, and the XOQDOQ plume trajectory model. An additional 10 percent will be added to the average for unrestricted area dose estimates performed quarterly or as needed for conservatism. When calculating X/Q data for the Annual Radiological Effluent Release Report, if the highest calculated X/Q for the reporting period is observed to be greater than +/-10% of the Annual Average X/Q previously calculated, contact the Supervisor-System Chemistry for further-instructions. This model conforms with the Nuclear Regulatory Commissions Regulatory Guide 1.111.
Real time meteorological data will be utilized in the preparation of the Annual Radioactive Effluent Release Report. This data is used to calculate the joint frequency table, the dispersion coefficients and deposition factors in all 16 sectors.
These are used in the calculation of doses to individuals in unrestricted areas as a result of the operation of Fort Calhoun Station. The models used, GASPAR 2 and LADTAP 2, conform with the Nuclear Regulatory Commissions Reg. Guide 1.109 and 1.21 for the reporting of doses due to routine radioactive effluent releases.
R12
FORT CALHOUN STATION CH-ODCM-0001 OFF-SITE DOSE CALCULATION MANUAL REFERENCE USE PAGE 49 OF 132 5.5 References Regulatory Guide 1.109, Rev. 1 - Calculation of Annual Dose to man from Routine Releases of Reactor Effluents for the purpose of evaluation compliance with 10 CFR Part 50, Appendix I Regulatory Guide 1.111, Rev. 1 - Methods for Estimating Atmospheric Transport and Dispersion of Gaseous Effluents in Routine Releases from Light-Water-Cooled Reactors.
Regulatory Guide 1.113, Rev. 1 - Estimating Aquatic Dispersion of Effluents from Accidental and Routine Releases for the purpose of Implementing Appendix I.
Regulatory Guide 4.8, Environmental Technical Specification for Nuclear Power Plants.
NUREG-0133 - Preparation of Radiological Effluent Technical Specifications for Nuclear Power Plants.
NUREG-0472, Rev. 3 - Draft Radiological Effluent Technical Specifications for PWRs.
Regulatory Guide 1.21, Rev. 1 - Measuring, Evaluating, and Reporting Radioactivity in solid wastes and Releases of Radioactivity Materials in Liquid and Gaseous Effluents from Light-Water-Cooled Nuclear Power Plants.
Code of Federal Regulations, Title 10, Part 20 Code of Federal Regulations, Title 10, Part 50 Code of Federal Regulations, Title 40, Part 190 Fort Calhoun Revised Environmental Report (Unit No. 1)-1972 Fort Calhoun Technical Specifications (Unit No. 1)
Updated Safety Analysis Report AR 12357, Implement Recommendations of Memo FC-0133-92, Part 1, Table 2.2.1 Action 4 s-i
'-I K)
R12