05000482/FIN-2005008-03 | Wolf Creek | 31 December 2005 23:59:59 | Failure to Ensure Redundant Safe Shutdown Systems Located in the Same Fire Area Are Free of Fire Damage | Safe Shutdown Fire Barrier Significance Determination Process Fire Protection Program |
05000482/FIN-2006003-06 | Wolf Creek | 30 June 2006 23:59:59 | Reactor Coolant System (RCS) Pressure Boundary Leakage Due to Small Cracks in Steam Generator Lower Head Bowl Drain Lines | Enforcement Discretion Pressure Boundary Leakage |
05000482/FIN-2007002-02 | Wolf Creek | 30 June 2007 23:59:59 | Use of wrench on manual service water valve handwheel | |
05000482/FIN-2007003-01 | Wolf Creek | 30 June 2007 23:59:59 | Circulating water roof loading exceeds design | |
05000482/FIN-2007003-05 | Wolf Creek | 30 June 2007 23:59:59 | Failure to follow test control procedures to demonstrate operability | |
05000482/FIN-2007005-01 | Wolf Creek | 31 December 2007 23:59:59 | EDG B Governor Failure Effect on Supplied Equipment | |
05000482/FIN-2007006-09 | Wolf Creek | 30 September 2007 23:59:59 | Potential for Damage to TDAFW Pump and ESW System During CST Unavailability | |
05000482/FIN-2008002-01 | Wolf Creek | 31 March 2008 23:59:59 | Failure to implement fire protection impairment control permit requirements and compensatory measures. | Continuous fire watch |
05000482/FIN-2008002-02 | Wolf Creek | 31 March 2008 23:59:59 | Performing prohibited elective maintenance on offsite power during EDG maintenance. | |
05000482/FIN-2008002-03 | Wolf Creek | 31 March 2008 23:59:59 | Containment sump net positive suction head losses. | |
05000482/FIN-2008002-04 | Wolf Creek | 31 March 2008 23:59:59 | Failure to control area as a locked high radiation area. | Locked High Radiation Area Significance Determination Process Substantial potential for overexposure |
05000482/FIN-2008002-05 | Wolf Creek | 31 March 2008 23:59:59 | Failure to follow procedure | Significance Determination Process Substantial potential for overexposure |
05000482/FIN-2008002-06 | Wolf Creek | 31 March 2008 23:59:59 | Failure to establish reasonable expectation of operability. | |
05000482/FIN-2008002-07 | Wolf Creek | 31 March 2008 23:59:59 | Untimely corrective actions for CCP room cooler leads to NOED. | Enforcement Discretion |
05000482/FIN-2008002-08 | Wolf Creek | 31 March 2008 23:59:59 | Transformer trip resulted in an unplanned eractor trip and forced outage. | |
05000482/FIN-2008002-09 | Wolf Creek | 31 March 2008 23:59:59 | Failure to reestablish timely seal cooling for the reactor coolant pumps. | Safe Shutdown |
05000482/FIN-2008002-10 | Wolf Creek | 31 March 2008 23:59:59 | Failure to analyze motor-operated valve circuits. | Safe Shutdown |
05000482/FIN-2008002-11 | Wolf Creek | 31 March 2008 23:59:59 | Licensee-Identified Violation | High Radiation Area Substantial potential for overexposure |
05000482/FIN-2008002-12 | Wolf Creek | 31 March 2008 23:59:59 | Licensee-Identified Violation | |
05000482/FIN-2008002-13 | Wolf Creek | 31 March 2008 23:59:59 | Licensee-Identified Violation | Safe Shutdown |
05000482/FIN-2008003-01 | Wolf Creek | 30 June 2008 23:59:59 | Failure to Implement Transient Combustible Control Permit Requirements for a Propane Tank | Significance Determination Process |
05000482/FIN-2008003-02 | Wolf Creek | 30 June 2008 23:59:59 | Failure to Establish Goals and Monitor for a(1) ECCS Room | |
05000482/FIN-2008003-03 | Wolf Creek | 30 June 2008 23:59:59 | Inadequate Containment Sump Inspection Procedure | |
05000482/FIN-2008003-04 | Wolf Creek | 30 June 2008 23:59:59 | Troubleshooting Activities Bypass Design Control for the Fuel Transfer System | Fuel cladding |
05000482/FIN-2008003-05 | Wolf Creek | 30 June 2008 23:59:59 | Inadequate Switchyard Work Proceudre Resulted in a Loss of Offsite Power | Significance Determination Process |
05000482/FIN-2008003-06 | Wolf Creek | 30 June 2008 23:59:59 | Failure to Verify Engineering Design Calculation Prior to Use | |
05000482/FIN-2008003-07 | Wolf Creek | 30 June 2008 23:59:59 | Inadequate Transformer Procedure Resulted in an Unplanned Reactor Trip and Forced Outage | |
05000482/FIN-2008003-08 | Wolf Creek | 30 June 2008 23:59:59 | Licensee-Identified Violation | Earthquake |
05000482/FIN-2008004-01 | Wolf Creek | 30 September 2008 23:59:59 | Incompatible procedures result in 6400 gallon drain of spent fuel pool | |
05000482/FIN-2008004-02 | Wolf Creek | 30 September 2008 23:59:59 | Use of hammer to reduce accumulator check valve leakage | Significance Determination Process |
05000482/FIN-2008004-03 | Wolf Creek | 30 September 2008 23:59:59 | Failure to adequately evaluate submerged safety-related cables | |
05000482/FIN-2008004-04 | Wolf Creek | 30 September 2008 23:59:59 | Emergency diesel generator lube oil heat exchanger leak due to water hammer | |
05000482/FIN-2008004-05 | Wolf Creek | 30 September 2008 23:59:59 | Water hammer caused by loss of offsite power exceeds heat exchanger bolt yield strength | |
05000482/FIN-2008004-06 | Wolf Creek | 30 September 2008 23:59:59 | Failure to completely close the spent fuel pool valve resulted in a loss of spent fuel pool water inventory. | |
05000482/FIN-2008004-07 | Wolf Creek | 30 September 2008 23:59:59 | Inadequate Reactor vessel head vent | Loop seal |
05000482/FIN-2008004-08 | Wolf Creek | 30 September 2008 23:59:59 | Diesel generator low frequency and voltage variation not considered in calculations | |
05000482/FIN-2008005-01 | Wolf Creek | 31 December 2008 23:59:59 | Maintenance Causes Unplanned Increase in Reactor Power | Fuel cladding |
05000482/FIN-2008005-02 | Wolf Creek | 31 December 2008 23:59:59 | Residual Heat Removal Suction Piping Saturation Temperature and Pressure | |
05000482/FIN-2008005-03 | Wolf Creek | 31 December 2008 23:59:59 | Equipment Out-of-Service Log Definitions Redefined Outside of Procedure Change Process | |
05000482/FIN-2008005-04 | Wolf Creek | 31 December 2008 23:59:59 | Licensee-Identified Violation | |
05000482/FIN-2008005-05 | Wolf Creek | 31 December 2008 23:59:59 | Licensee-Identified Violation | Substantial potential for overexposure |
05000482/FIN-2008006-01 | Wolf Creek | 31 March 2008 23:59:59 | Twenty-One Examples of Failure to Follow Seismic Requirements of Scaffolding Procedure | Earthquake Scaffolding |
05000482/FIN-2008006-02 | Wolf Creek | 31 March 2008 23:59:59 | Failure to Take Corrective Action For Missed Compensatory Measures | Significance Determination Process |
05000482/FIN-2008006-03 | Wolf Creek | 31 March 2008 23:59:59 | Failure to Take Corrective Actions For Missed Operability Evaluation | Significance Determination Process |
05000482/FIN-2008006-04 | Wolf Creek | 31 March 2008 23:59:59 | Failure to Take Timely Corrective Action To Establish Monitoring Frequency of AFW Pump Governor Null Set Drift | Significance Determination Process |
05000482/FIN-2008006-05 | Wolf Creek | 31 March 2008 23:59:59 | Failure to Take Timely Corrective Action to Correct Annunciator Feed Configuration Deficiencies. | Significance Determination Process |
05000482/FIN-2008006-06 | Wolf Creek | 31 March 2008 23:59:59 | Failure to Take Timely Corrective Action to Correct Barton Transmitter Defects | Significance Determination Process |
05000482/FIN-2008009-01 | Wolf Creek | 30 September 2008 23:59:59 | Failure to Provide an Accurate Shipping Manifest | Significance Determination Process |
05000482/FIN-2008010-01 | Wolf Creek | 31 December 2008 23:59:59 | Post-Fire Safe Shutdown Procedure did Not Identify Diagnostic Instrumentation | Safe Shutdown Fire Protection Program Hourly Fire Watch |
05000482/FIN-2008010-02 | Wolf Creek | 31 December 2008 23:59:59 | Failure to Ensure a Fire Pump Would Automatically Start for One Fire Area |