05000482/FIN-2008002-12
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Licensee-Identified Violation |
Description | Technical Specification 5.4.1.d specified that the licensee have fire protection procedures established, maintained, and implemented. Procedure OFN-RP-017, \"Control Room Evacuation,\" Revision 21, specified actions for a fire in the control room. Contrary to this requirement, the licensee determined that the procedure failed to provide mitigating actions for a failure of the field flash relay control circuit because of possible fire damage. As described in Section 4OA3.6, this finding was of very low safety significance |
Site: | Wolf Creek |
---|---|
Report | IR 05000482/2008002 Section 4OA7 |
Date counted | Mar 31, 2008 (2008Q1) |
Type: | NCV: Green |
cornerstone | No Cornerstone |
Identified by: | Licensee-identified |
Inspection Procedure: | |
Inspectors (proximate) | C Long D Stearns G Pick S Cochrum V Gaddy |
INPO aspect | |
' | |
Finding - Wolf Creek - IR 05000482/2008002 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Wolf Creek) @ 2008Q1
Self-Identified List (Wolf Creek)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||