Finding | |
|---|---|
| Title | Licensee-Identified Violation |
| Description | Technical Specification 5.4.1.d specified that the licensee have fire protection procedures established, maintained, and implemented. Procedure OFN-RP-017, \"Control Room Evacuation,\" Revision 21, specified actions for a fire in the control room. Contrary to this requirement, the licensee determined that the procedure failed to provide mitigating actions for a failure of the field flash relay control circuit because of possible fire damage. As described in Section 4OA3.6, this finding was of very low safety significance |
| Site: | Wolf Creek |
|---|---|
| Report | IR 05000482/2008002 Section 4OA7 |
| Date counted | Mar 31, 2008 (2008Q1) |
| Type: | NCV: Green |
| cornerstone | No Cornerstone |
| Identified by: | Licensee-identified |
| Inspection Procedure: | |
| Inspectors (proximate) | C Long D Stearns G Pick S Cochrum V Gaddy |
| INPO aspect | |
| ' | |