During an attempt to open
service water pump discharge Valve 1WS0002A on February 8, 2007, a plant operator initially attempted to open the valve with the pump secured but was unsuccessful because the valves manual handwheel was too difficult to turn against the system back pressure. However, Procedure SYS EA-120,
Service Water System Startup Revision 40A, states that
service water Pump 1WS01PA be started prior to opening the discharge valve to equalize system back pressure. A second attempt to open the valve was made with the
service water pump running to decrease differential pressure across the valve. The second attempt was also unsuccessful as the valves handwheel was still too difficult to operate. During the second attempt, the operator placed a wrench across the valvess handwheel to increase leverage and open the valve. The second attempt was not successful in opening the valve and resulted in damage to the handwheel and valve actuator internals due to the excessive torsion caused by using a wrench. Wolf Creek Standing Order 1, Valve Setup and Operation, Revision 37 as well as
Enertech (the valve vendor) Procedure
PA 97283, Installation, Operation and Maintenance Instructions -
Enertech Permaseat Valves, MAK, prohibit the use of a wrench and use of excessive force on the handwheel. Subsequently, the valves restoration position on the tracking document was then changed to closed. The valve was repaired as emergent work and returned to service after approximately
50 hours5.787037e-4 days <br />0.0139 hours <br />8.267196e-5 weeks <br />1.9025e-5 months <br /> of being
inoperable. The inspectors questioned whether the plant operator used appropriate guidance which resulted in applying excessive
torque with a wrench on the valves handwheel. This issue is captured in the licensees corrective action program under Condition Report 2007-000543. Because additional followup is needed to determine the significance, this issue is being treated as an Unresolved Item
URI 05000482/2007002-02, use of wrench on manual
service water valve handwheel.