Finding | |
|---|---|
| Title | Failure to implement fire protection impairment control permit requirements and compensatory measures. |
| Description | The inspectors identified a noncited violation of Technical Specification 5.4.1.d for failure to implement fire protection impairment control permit requirements and compensatory measures when operators received a trouble alarm on a fire detector in the auxiliary building. On January 26, 2008, operators discovered that Detector KC-104-XCH-ID-006 did not have a fire protection impairment control permit. This detector was adjacent to Detector KC- 104-XSH-ID-007 which was already inoperable in Impairment 2008-020. The licensees administrative procedure required fire detection in the area to be declared inoperable if two adjacent detectors are inoperable. This condition existed for approximately 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and would have required a compensatory continuous fire watch for the period that both detectors were inoperable. The residents identified that the control room turnover checklist contains a section for listing the KC008 alarms; however, the two turnover checklists for the two shifts following the initial alarm did not identify Detector KC-104-XCH-ID-006 as a Detector KC-008 alarm. The failure to implement fire protection impairment control permit requirements and establish compensatory measures for the auxiliary building 2026-foot level was considered a performance deficiency. The finding was more than minor because it was associated with the Mitigating Systems Cornerstone attribute of protection against external factors and affected the cornerstone objective of ensuring the availability of systems that respond to initiating events to prevent undesirable consequences. Specifically, this issue relates to the protection against fire example of protection against external factors attribute because the detectors were inoperable without ensuring compensatory measures were in place. The finding was of very low safety significance because it involved compensatory measures for the fixed fire protection system and was assigned a low degradation rating since less than 10 percent of the fire detectors in the area were disabled. The finding has crosscutting aspects in the area of human performance associated with work practices because the licensee failed to apply appropriate human error techniques such as self and peer-checking techniques to avoid committing errors H.4(a) (Section 1R05) |
| Site: | Wolf Creek |
|---|---|
| Report | IR 05000482/2008002 Section 1R05 |
| Date counted | Mar 31, 2008 (2008Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | C Long D Stearns G Pick S Cochrum V Gaddy |
| CCA | H.12, Avoid Complacency |
| INPO aspect | QA.4 |
| ' | |
Finding - Wolf Creek - IR 05000482/2008002 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Wolf Creek) @ 2008Q1
Self-Identified List (Wolf Creek)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||