 Issue dateTitleTopic
ML20154A7262 September 1988Special Rept:On 880726,motor-driven Fire Pump Out of Svc for More than 7 Days.Caused by Action Taken to Allow Cleaning & Insp of of E-42 4 Kv bus.Motor-driven Fire Pump Restored to Operable Status on 880821
ML20154A9611 September 1988Special Rept:On 880822,discharge Pressure Lost While Motor Driven Fire Pump in Operation.Caused by Crack That Formed in Column Pipe Flange Area Where It Bolts to Pump.Motor Driven Pump Removed from Pump Structure,Disassembled & Inspected
ML20154P35927 May 1988Special Rept:On 880415,carbon Dioxide Fire Suppression Sys Taken Out of Svc for More than 14 Days.Caused by Continuous Fire Watch Required in Cable Spreading Room During Repair of Hole in Floor.Hole Repaired & Subj Sys Returned to SvcFire Barrier
Continuous fire watch
Fire Watch
ML20195B85015 June 1988Special Rept:On 870215,packing Leak from RCIC Outboard Isolation Valve Reported to Operating Shift.Caused by Steam Leak.New Grease Replaced.On 870915,degradation to Motor Operator & Field Wiring Discovered.Components ReplacedPacking leak
Stroke time
ML20195E5013 November 1988Special Rept:On 881020,diesel Driven Fire Pump Failed to Start Automatically During Surveillance Test.Caused by Inadequate Test.Diesel Driven Fire Pump & auto-start Feature Tested & Rev of Fire Pumps Surveillance Tests in Process
ML20196G5527 March 1988Ro:On 880302 & 05,motor Driven Fire Pumps Declared Inoperable.Caused by Level in Storage Tank Dropped Due to Oil Being Transferred from Storage to Day Tank.Diesel Fuel Added Storage Tank to Bring Level Above 300 Gallon Limit
ML20199F44027 March 1986Special Rept:On 860216,during Cold Shutdown,Condensate Storage Tank (CST) Filled & Overflowed Into CST Moat & Outside Moat.Caused by Blown Fuse Resulting in Removal of Power from Hotwell Level Controllers.Fuse Mods Considered
ML20205H25621 October 1988Ro:On 881020,diesel Driven Fire Pump Failed to Start Automatically During Performance of Surveillance Test.Cause Under Investigation.Diesel Driven Fire Pump Subsequently Tested Successfully & Returned to Svc
ML20214U0344 June 1987Special Rept:During Update of Safe Shutdown Data Base, Conditions Re Unencapsulated Cables in Fire Areas Identified as Reportable Per Confirmatory Action Ltr 86-07 & App R. Caused by Exclusion from Previous Analysis.Fire Watch BegunSafe Shutdown
Fire Watch
ML20214W7695 June 1987Special Rept:On 870428,bus E22 Deenergized to Perform Series of outage-related Mods,Causing Motor Driven Fire Pump to Be out-of-svc for More than 7 Days,In Violation of Tech Specs. Motor Driven Fire Pump Restored to Svc on 870515
ML20236K9113 August 1987Ro:On 870731,motor Driven Fire Pump Automatically Started on Decreasing Header Pressure at 140 Psig.Caused by Personnel Digging in Yard Directly Behind Radwaste Bldg.Affected Portion of Fire Header Isolated for Repair of Leak
ML20238C50721 December 1987Special Rept:On 871111,diesel-driven Fire Pump Failed Surveillance Test & Declared Inoperable.Cause Unknown.Four Sets of Cells for Two Batteries Replaced & Charged W/Portable Charger.Surveillance Test Procedure Revised
ML20245B33914 April 1989Special Rept:On 890303,seismic Monitoring Instruments Inoperable for More than 30 Days.Caused by Triaxial Accelerometer Cables Picking Up Electrical Noise Which Caused Spurious Alarms.Noise Filters Will Be Installed
ML20245H44610 August 1989Ro:On 890710,diesel Driven Fire Pump Out of Svc for More than 7 Days.Caused by Disconnected Coolant Hose from Engine Block During Test,Draining Coolant from Engine & Heat Exchanger.Insp & Repair of Engine Performed
ML20245J5571 May 1989Ro:On 890331,motor Driven Fire Pump Out of Svc in Excess of 7 Days.Caused by Removal of Pump from Svc on 890324 to Allow Implementation of Electrical Mods.Diesel Driven Fire Pump Verified Operable & Tested Every 72 H