Acceptance Review - License Amendment Request to Change TS 3.6.5, Containment Air Temperature
ML24205A214
Person / Time
Site: Farley  Southern Nuclear icon.png
Issue date: 07/23/2024
From: Turner Z
Plant Licensing Branch II
To: Sparkman W
Southern Nuclear Operating Co
Turner, Zachary
References
EPID L-2024-LLA-0098
Download: ML24205A214 (1)


Text

Zach Turner

From: Zach Turner Sent: Tuesday, July 23, 2024 1:45 PM To: Sparkman, Wesley A.

Cc: Joyce, Ryan M.; Michael Markley; John Lamb; Dawnmathews Kalathiveettil

Subject:

Acceptance Review - Farley 1 and 2 - License Amendment Request to change TS 3.6.5, "Containment Air Temperature," Actions

Wes,

By letter dated July 18, 2024 (Agencywide Documents Access and Management System (ADAMS)

Accession No. ML24201A107 - non-publicly available; ML24201A108 - publicly available), Southern Nuclear Operating Company (SNC, the licensee) submitted a license amendment request (LAR) for Joseph M. Farley Nuclear Plant (Farley), Units 1 and 2. The proposed LAR would revise the Farley, Units 1 and 2, Technical Specification (TS) 3.6.5, Containment Air Temperature, Actions upon exceeding the containment average air temperature limit of 120 degrees Fahrenheit (°F), and remove an expired Limiting Condition for Operation (LCO) Note. Specifically, the change would modify the TS 3.6.5 Actions if containment average air temperature exceeds the LCO of 120 degrees °F to allow continued operation for up to seven cumulative days per calendar year provided that the containment average air temperature does not exceed 122°F (verified within eight hours of containment average air temperature exceeding 120°F and once per eight hours thereafter) and that refueling water storage tank temperature remains less than or equal to 100°F (verified within eight hours of containment average air temperature exceeding 120°F and once per eight hours thereafter).

The purpose of this e-mail is to provide the results of the U.S. Nuclear Regulatory Commission (NRC) staffs acceptance review of this LAR. The acceptance review was performed to determine if there is sufficient technical information in scope and depth to allow the NRC staff to complete its detailed technical review. The acceptance review is also intended to identify whether the application has any readily apparent information insufficiencies in its characterization of the regulatory requirements or the licensing basis of the plant.

Consistent with Section 50.90 of Title 10 of the Code of Federal Regulations (10 CFR), an application for an amendment to a license (including the technical specifications) must fully describe the changes requested, and following as far as applicable, the form prescribed for original applications. Section 50.34 of 10 CFR addresses the content of technical information required. This section stipulates that the submittal address the design and operating characteristics, unusual or novel design features, and principal safety considerations.

The NRC staff has reviewed your application and concluded that it does provide technical information in sufficient detail to enable the NRC staff to complete its detailed technical review and make an independent assessment regarding the acceptability of the proposed LAR in terms of regulatory requirements and the protection of public health and safety and the environment. Given the lesser scope and depth of the acceptance review as compared to the detailed technical review, there may be instances in which issues that impact the NRC staffs ability to complete the detailed technical review are identified despite completion of an adequate acceptance review. If additional information is needed, you will be advised by separate correspondence.

1 Based on the information provided in your LAR, the NRC staff has estimated that this licensing request will take approximately 330 hours0.00382 days <br />0.0917 hours <br />5.456349e-4 weeks <br />1.25565e-4 months <br /> to complete. The NRC staff expects to complete this review by August 29, 2024. If there are emergent complexities or challenges in our review that would cause changes to the initial forecasted completion date or significant changes in the forecasted hours, the reasons for the changes, along with the new estimates, will be communicated during the routine interactions with the assigned project manager. These estimates are based on the NRC staffs initial review of the LAR and they could change, due to several factors including requests for additional information, unanticipated addition of scope to the review, and review by NRC advisory committees or hearing-related activities. Additional delay may occur if the submittal is provided to the NRC in advance or in parallel with industry program initiatives or pilot applications.

If you have any questions, please contact me at (301) 415-2258, or via email at Zachary.Turner@nrc.gov.

Very Respectfully, Zach Turner, Project Manager Nuclear Regulatory Commission Division of Operating Reactor Licensing NRR/DORL/LPL2-1 (301) 415-2258 Office: OWFN-07C12 Mail Stop: O-08 B01A