Pages that link to "ML20097D733"
Jump to navigation
Jump to search
The following pages link to ML20097D733:
Displayed 50 items.
- BSEP-86-0973, Special Rept 1-SR-86-001:on 860522,two Fire Barrier Limiting Conditions Initiated to Allow Mods to Emergency Ac Diesel Generator.Fire Watches Maintained Until Conditions Terminated on 860611 (← links)
- BSEP-85-2207, Special Rept 2-8R-85-08:on 851129,determined That Fire Door 303,located at 50-ft Reactor Bldg Air Lock,Inoperable.Caused by Broken Latching Mechanism.Mechanism Throughly Cleaned & Lubricated.Part 21 Related (← links)
- BSEP-85-1827, Special Rept 2-SR-85-03:on 850915,fire Detection Sys Zone 5 Instrumentation for 20-ft Elevation in Reactor Bldg Declared Inoperable Due to Erroneous Fire Alarm.Specified 14-day Time Frame Exceeded on 850929.Instrumentation Returned to S (← links)
- BSEP-84-1441, Special Rept 2-SR-84-7:on 840511,limiting Condition for Operation Initiated for Fire Doors 203,301 & 303 to Allow Opening to Reduce Wear & Possible Damage from outage-related traffic.Seven-day Limit Exceeded.Fire Watches Maintained (← links)
- BSEP-88-0625, Suppl to Special Rept:On 860307,two Designated Fire Barrier Limiting Conditions for Operation Initiated.Plant Mod Will Be Installed During Upcoming Refueling/Maint Outage to Resolve Subj Differential Pressure Problem (← links)
- BSEP-88-1228, Special Rept 1-SR-88-003:on 881120,7-day Time Frame for Limiting Condition for Operation Exceeded.Caused by Fire Door 211 Being out-of-svc to Prevent Wear & Possible Damage to Locking Seals & Interlocks (← links)
- BSEP-98-0210, Special Rept:On 980824,temp Element 2-CAC-TE-1258-22 Failed. Cause of Failed Temp Element Cannot Be Conclusively Determined.Temp Element Will Be Replaced & Cable Connections Repaired (← links)
- BSEP-86-0340, Special Rept 2-SR-86-003:on 860223,fire Barrier Limiting Condition of Operation Initiated to Permit Removal of Penetration Seal in Diesel Generator Bldg.Fire Watches Maintained Until Work Completed on 860306 (← links)
- BSEP-86-0347, Special Rept 1-SR-86-002:on 860219,fire Barrier Limiting Condition for Operation (LCO) Initiated on Penetration Seal CB-2-301,Fire Door 221.LCO Initiated to Permit Air Circulation Between Computer Room & Electric Equipment Area (← links)
- BSEP-88-0475, Special Rept 2-SR-88-004:on 880414,14 Day Time Frame Exceeded for Limiting Condition for Operations.Caused by Problems W/Acquisition of Replacement Parts.Repairs Made & Sprinkler Header Returned to Svc (← links)
- BSEP-88-0474, Special Rept 1-SR-88-001:on 880419,14 Days Time Frame of Limiting Condition for Operation (LCO) Exceeded.Caused by Temporary Unavailability of Replacement Parts.Lco Will Remain in Effect Until Repairs Completed (← links)
- BSEP-86-0202, Special Rept:On 860117,Fire Detection Sys Zone 6 Instrumentation Inoperable Due to Inability to Clear Erroneous Fire Alarm.Caused by Sheared Detection Circuit Cable.Problem Should Be Resolved by 860307.Part 21 Related (← links)
- BSEP-88-0854, Special Rept 1-SR-88-001:limiting Condition for Operation (LCO) Established on 880405 for Fire Protection Deluge Valve 1-FP-DV-22 to Sprinkler Sys.Specified 14-day Time Frame of LCO Exceeded on 880419.Fire Watches Remain in Effect (← links)
- BSEP-88-0850, Special Rept 2-SR-88-002:on 880119,unit Reactor Bldg Fire Detection Sys Zone 14 Instrumentation Declared Inoperable Due to Erroneous Fire Alarms.Limiting Condition for Operation Initiated.Sys Returned to Svc (← links)
- BSEP-88-0853, Followup Special Rept:On 871228,limiting Condition for Operation to Permit Fire Suppression Sprinkler Header from Svc Exceeded.Caused by Unavailability of Addl Flow Switch 2-FP-FS-4059 in Plant Supply Sys.Switch Repaired (← links)
- BSEP-88-0094, Special Rept 1-SR-88-002:on 880126,limiting Condition for Operation (LCO) Initiated for Fire Door 203 in Reactor Bldg to Permit Opening Door to Help Prevent Wear & Possible Damage to Locking Seals & Interlocks.Lco Exceeded on 880202 (← links)
- BSEP-88-0037, Special Rept 2-SR-88-001:on 880110,7-day Time Frame of Fire Barrier Limiting Condition for Operation for Fire Door 203 Exceeded.Fire Watches Established & Will Be Maintained During Remainder of Refueling/Maint Outage (← links)
- BSEP-88-0165, Special Rept:On 880119,reactor Bldg Fire Detection Sys Zone 14 Instrumentation Inoperable Due to Erroneous Fire Alarms.Caused Not Determined.Time Frame of 14 Days of Involved LCO Exceeded on 880202 (← links)
- BSEP-85-2183, Special Rept 2-SR-85-9:on 851214,time Frame for Limiting Condition for Operation Exceeded.Caused by Fire Door 203 Being Out of Svc to Prevent Wear & Damage to Locking Seals & Interlocks.Fire Watches Maintained (← links)
- BSEP-85-2165, Special Rept 1-SR-85-11:on 851203 & 07,designated Fire Barrier Limiting Condition of Operation Exceeded for Fire Doors in Common Emergency Ac Diesel Generator Bldg.Doors Removed from Svc to Repair Weld Seam & Closer Mechanism (← links)
- BSEP-85-1099, Special Rept:On 850507,during Refueling/Maint Outage, Concurrent W/Power Operation of Unit 2,Units 1 & 2 Limiting Conditions for Operation Established for Fire Protection Deluge Valve 2-FP-DV-13 to Sprinkler Sys (← links)
- BSEP-85-2054, Special Rept 1-SR-85-010:on 851118,designated Fire Barrier Limiting Condition of Operation Initiated for Fire Door in Common Emergency Ac Diesel Generator Bldg.Inability of Door to Close Prevented Resolution by 851125 Deadline (← links)
- BSEP-85-1828, Ro:On 850927,during Surveillance Testing,Msivs 2-B21-F028A, F028C & F022C Failed to Fast Close.Caused by disc-to-seat Sticking of Asco Model 8323A36E Double Solenoid Valves.Addl Info Expected by 851025 (← links)
- BSEP-85-1652, Special Rept 1-SR-85-9:on 850824 & 27,7-day Specified Time Frames of Fire Barrier Limiting Conditions for Operation for Fire Doors 203 & 303,respectively,exceeded.Caused by Preventive Maint.Fire Watches in Reactor Bldg Maintained (← links)
- BSEP-86-0103, Special Rept 2-SR-86-001:on 860113,7-day Time Frame for Fire Barrier Limiting Condition for Operation Exceeded for Fire Door in Common Emergency Ac Diesel Generator Bldg.Hole in Door Repaired.Part 21 Related (← links)
- BSEP-85-1916, Special Rept 2-SR-85-7:on 851004,fire Barrier Limiting Condition for Operation Established for Fire Door 113 to Permit Routing Electrical Extension Cord Through Door to Allow Performance of Plant mod-related Work (← links)
- BSEP-85-1392, Suppl to Special Rept 1-SR-85-6:fire Barrier Penetration Seal Removed During Plant Mod Work Incorrectly Identified in 850725 Rept.Correct Identification Is Seal CB-2-244-21. Part 21 Related (← links)
- BSEP-93-0011, Special Rept 1-SR-93-001:on 921216,reactor Bldg Fire Detection Sys Declared Inoperable Due to Continuous Spurious Alarming in Ionization Detectors for More than 14 Days. Sensitivity Testing & Cleaning Implemented (← links)
- BSEP-93-0005, Special Rept 1-SR-93-002:on 930107,both Fire Suppression Sys Fire Pumps Were Made Inoperable to Allow Replacement of Isolation Valve.Personnel Were Stationed to Monitor Diesel Fire Pump Operation (← links)
- BSEP-93-0007, Special Rept 1-SR-93-002:on 930116,both Fire Suppression Sys Fire Pumps Will Be Made Inoperable for Approx 8 H to Allow Replacement of Isolation Valve (2-FP-V79).Personnel Will Be Stationed to Monitor Diesel Fire Pump Operation (← links)
- BSEP-92-0054, Special Rept 1-SR-92-010:on 921130,makeup Water Treatment Area Sprinkler Sys Declared Inoperable.On 921212,DG Bldg Southwest Switchgear Room Inoperable.On 921216,Unit 1 Air Lock Doors Blocked Open.On 921217,RWCU Barrier Inoperable (← links)
- BSEP-93-0003, Special Rept 1-SR-93-002:on 930107 Both Fire Suppression Sys Fire Pumps Will Be Made Inoperable for Approx 8 H to Permit Replacement of Isolation Valve & Associated Instrument Line. Personnel Will Monitor Diesel Fire Pump Operation (← links)
- BSEP-92-0036, Special Rept 1-SR-92-008:on 921007 & 09 EDG Bldg 50 Feet Elevation Fire Barrier Seals DG-3-437,472 & 473 Declared Inoperable,Respectively to Support Plant Mod 92-069.Seals Will Be Restored Prior to Startup of Either Unit (← links)
- BSEP-85-0690, RO 1-85-016:on 850406,Type C Leakage Limits Exceeded for RHR Subsystem a Suppression Pool Suction Valve 1-E11-F020A. LER Will Be Submitted within 30 Days Following Completion of Test (← links)
- BSEP-92-0026, Special Rept 1-SR-92-007:on 920919,conduit Leading to Seal AO-3-014 on Augmented Offgas 50-ft Elevation Declared Inoperable Due to Corrosion at Floor Penetration.Fire Watch Stationed Until Restoration of Fire Barrier Seal (← links)
- BSEP-92-0022, Special Rept 1-SR-92-006:on 920904 & 21,secondary Containment Airlock Doors Both Opened to Support Increased Traffic During Outage & Not Restored within 7 Days.Fire Watch Stationed & Remained in Place Until Barrier Restored (← links)
- BSEP-92-0025, Special Rept 2-SR-92-008:on 920909,crack Found in Thermo-Lag of Penetration Seal in Control Bldg Cable Spread Room During Review of NRC Bulletin 92-001.Seal Not Restored within 7 Days.Fire Watches Stationed in Affected Areas (← links)
- BSEP-84-2766, LER 1-84-18 Re Support to Snubber 1-E11-84SS491 Found to Be Reportable Per 10CFR50.73.LER Number 1-84-18 May Be Reassigned (← links)
- BSEP-85-0234, Special Rept 2-SR-85-1:on 850116,fire Barrier Limiting Condition for Operation Established to Permit Making 4-inch Core Bore in Cable Spread Room at Fire Barrier Seal CB-1-373,per Approved Plant Mod (← links)
- BSEP-85-0287, Special Rept 1-SR-85-1:on 850128,7-day Fire Barrier Limiting Condition for Operation Exceeded for Fire Door 117 of Unit 1 Battery Room B & Fire Door 113 of Unit 2 Battery Room B to Maintain Acceptable Room Temps (← links)
- BSEP-84-2282, Special Rept 1-SR-84-7:on 840924,fire Barrier Limiting Condition Initiated for Fire Door in Emergency Ac Diesel Generator Bldg.Caused by Failure of Door to Open & Close as Result of Differential Pressure Conditions (← links)
- BSEP-84-2275, Special Rept 1-SR-84-5:review Revealed That Procedure PT-04.1.6PC Re Containment Radiation Monitor Channel Calibr Not Performed by 840110 as Required.Caused by Personnel Entering Completion Date for Unit 2 in Unit 1 Tracking Sys (← links)
- BSEP-85-0091, Updated RO-2-83-95 Re Fire Seal Evaluation Program Accomplishments to Date,Status of Interim Compensatory & Preventative Measures & Planned Fire Seal Evaluation & Mod Tasks.Next Rept Will Be Submitted by 860131 (← links)
- BSEP-92-0013, Special Rept 2-SR-92-007:on 920823,fire Door 206 on 50-ft Elevation of EDG Bldg Declared Inoperable.Caused by Fire Door Not Latching Consistently Due to Broken Springs.Latch Repaired & Fire Watch Stationed in Area (← links)
- BSEP-92-0006, Special Rept 2-SR-92-006:on 920729,fire Doors in CR Stairwell Area Declared Inoperable to Perform Plant Mod.On 920731,secondary Containment Airlock Doors Both Opened.Fire Watch Stationed,Pending Restoration of Fire Door (← links)
- BSEP-85-0007, Special Rept 1-SR-84-6:on 841218,14-day Requirement of Limiting Conditions for Operation of Zone 14 Fire Detection Instruments Exceeded After 841204 Discovery That Control Room Annunciator Did Not Alarm During Performance Test (← links)
- BSEP-84-2725, RO-1-84-32:on 841116,automatic Isolation of Common Control Bldg Ventilation Sys Occurred Due to Actuation of Sys Intake Plenum Chlorine Detector 2X-AT-2977.Investigation Incomplete.Rept Will Be Submitted by 850104 (← links)
- BSEP-85-0386, Special Rept 2-SR-85-2:on 850206,fire Barrier Established for Fire Door 201.Caused by Routing Temporary Fire Suppression Supply Through Open Door to Provide Alternate Suppression for Stations 2-CB-1 & 2-CB-2 (← links)
- BSEP-84-2609, RO-2-84-12:on 841024,automatic Reactor Protection Sys High Pressure Scram Occurred When MSIVs Closed on Group 1 Isolation Signal.Investigation Still in Progress.Ler Will Be Delayed Until 841214 (← links)
- BSEP-84-2511, RO 1-84-18:on 841018,wide Flange Support Beam of Hydraulic Snubber 1-E11-89SS491 Twisted Slightly at Snubber Attachment.Investigation & Evaluation of Event Incomplete. LER Will Be Submitted by 841221 (← links)