{{#Wiki_filter:Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 4 Status: --Y--I N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-3903 Equipment Class: (5) Horizontal Pumps Eauioment DescriDtion:
{{#Wiki_filter:Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 4 Status: --Y--I N U
PUMP, DG COOLING -U2 DIESEL GENERATOR COOLING WATER PUMP Project: Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-3903 Equipment Class:
(5) Horizontal Pumps Eauioment DescriDtion:
PUMP, DG COOLING - U2 DIESEL GENERATOR COOLING WATER PUMP Project:
Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
TB, 547.00 ft, ALL Manufacturer/Model:
TB, 547.00 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings.
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Additional space is provided at the end of this checklist for documenting other comments.Anchorage 1. Is anchorage configuration verification required (i.e., is the item one of the 50%of SWEL items requiring such verification)?
Anchorage
Yes 2. Is the anchorage free of bent, broken, missing or loose hardware?Yes 3. Is the anchorage free of corrosion that is more than mild surface oxidation?
: 1.
Yes 4. Is the anchorage free of visible cracks in the concrete near the anchors?Yes 5. Is the anchorage configuration consistent with plant documentation? (Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Is anchorage configuration verification required (i.e., is the item one of the 50%
Yes 6. Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
of SWEL items requiring such verification)?
Yes C-423 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 4 Status: Eli] N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-3903 Equipment Class: (5) Horizontal Pumps Eauioment DescriDtion:
Yes
PUMP. DG COOLING -U2 DIESEL GENERATOR COOLING WATER PUMP Interaction Effects 7. Are soft targets free from impact by nearby equipment or structures?
: 2.
Yes Yes 8. Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Is the anchorage free of bent, broken, missing or loose hardware?
Yes
: 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes
: 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Yes
: 5.
Is the anchorage configuration consistent with plant documentation? (Note:
This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Yes
: 6.
Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes C-423
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 4 Status: Eli] N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-3903 Equipment Class:
(5) Horizontal Pumps Eauioment DescriDtion:
PUMP. DG COOLING - U2 DIESEL GENERATOR COOLING WATER PUMP Interaction Effects
: 7.
Are soft targets free from impact by nearby equipment or structures?
Yes Yes
: 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Overhead light fixtures judged to be acceptable.
Overhead light fixtures judged to be acceptable.
: 9. Do attached lines have adequate flexibility to avoid damage?Yes 10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?Yes Other Adverse Conditions
: 9.
: 11. Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Do attached lines have adequate flexibility to avoid damage?
Comments SEWS Anchorage Notes: Pump anchored by six 7/8" (3 per side) cast-in-place anchors.Seismic Walkdown Team: J. Griffith & M. Wodarcyk -8/8/2012 Evaluated by: James Griffith Date: 10/4/2012 Michael Wodarcyk 10/4/2012 C-424 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 4 Status: r-1 N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-3903 Equipment Class: (5) Horizontal Pumps Equipment
Yes
: 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Other Adverse Conditions
: 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Comments SEWS Anchorage Notes:
Pump anchored by six 7/8" (3 per side) cast-in-place anchors.
Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/8/2012 Evaluated by:
James Griffith Date:
10/4/2012 Michael Wodarcyk 10/4/2012 C-424


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 4 Status: r-1 N U
Description:==
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-3903 Equipment Class:
(5) Horizontal Pumps Equipment


PUMP, DG COOLING -U2 DIESEL GENERATOR COOLING WATER PUMP Photos C-425 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 4 Status: Fv7i N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-390 3 Equipment Class: EauiDment DescriDtion:
== Description:==
(5) Horizontal Pumps PUMP. DG COOLING -U2 DIESEL GENERATOR COOLING WATER PUMP 20120808-QuadCities-2 363 20120808-QuadCities-2 364 C-426 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: LY N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250 VDC BATT 2 Equipment Class: (15) Batteries on Racks Equipment
PUMP, DG COOLING - U2 DIESEL GENERATOR COOLING WATER PUMP Photos C-425


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 4 Status: Fv7i N U
Description:==
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-390 3 Equipment Class:
EauiDment DescriDtion:
(5) Horizontal Pumps PUMP. DG COOLING - U2 DIESEL GENERATOR COOLING WATER PUMP 20120808-QuadCities-2 363 20120808-QuadCities-2 364 C-426


BATTERY, 250V Project: Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: LY N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250 VDC BATT 2 Equipment Class:
(15) Batteries on Racks Equipment
 
== Description:==
BATTERY, 250V Project:
Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
TB, 628.00 ft, ALL Manufacturer/Model:
TB, 628.00 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings.
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Additional space is provided at the end of this checklist for documenting other comments.Anchoracqe
Anchoracqe
: 1. Is anchorage configuration verification required (i.e., is the item one of the 50% Yes of SWEL items requiring such verification)?
: 1.
: 2. Is the anchorage free of bent, broken, missing or loose hardware?
Is anchorage configuration verification required (i.e., is the item one of the 50%
Yes Although a missing anchor was discussed in the SQUG notes, a thorough examination revealed that there are no missing anchors.3. Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes of SWEL items requiring such verification)?
: 2.
Is the anchorage free of bent, broken, missing or loose hardware?
Yes Although a missing anchor was discussed in the SQUG notes, a thorough examination revealed that there are no missing anchors.
: 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes Minor surface corrosion judged to be acceptable.
Yes Minor surface corrosion judged to be acceptable.
: 4. Is the anchorage free of visible cracks in the concrete near the anchors? Yes Minor floor shrinkage cracks judged to be acceptable.
: 4.
: 5. Is the anchorage configuration consistent with plant documentation? (Note: Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Is the anchorage free of visible cracks in the concrete near the anchors?
: 6. Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?
Yes Minor floor shrinkage cracks judged to be acceptable.
C-427 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: F N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250 VDC BATT 2 Equipment Class: (15) Batteries on Racks Equipment  
: 5.
Is the anchorage configuration consistent with plant documentation? (Note:
Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
: 6.
Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?
C-427
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: F N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250 VDC BATT 2 Equipment Class:
(15) Batteries on Racks Equipment
 
== Description:==
BATTERY, 250V Interaction Effects
: 7.
Are soft targets free from impact by nearby equipment or structures?
Yes
: 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Yes
: 9.
Do attached lines have adequate flexibility to avoid damage?
: 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Yes Other Adverse Conditions
: 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Comments SEWS Anchorage Notes:
Each leg anchored by a single 3/8" Wedge type expansion anchor through a 3x3x1/4" clip angle thru-bolted thru the tube leg.
Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/7/2012 Evaluated by:
James Griffith Date:
10/4/2012 Michael Wodarcyk 10/4/2012 C-428
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status:
Y N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
Equipment Class:
Equipment Descrip ion:
250 VDC BATT 2 (15) Batteries on Racks BATTERY, 250V m m m
C-429
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status: FYI N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250 VDC BATT 2 Equipment Class:
(15) Batteries on Racks C-430


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status: FI N
Description:==
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250 VDC BATT 2 Equipment Class:
(15) Batteries on Racks C-431


BATTERY, 250V Interaction Effects 7. Are soft targets free from impact by nearby equipment or structures?
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status:
Yes 8. Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
T N U Seismic Walkdown Checklist (SWC)
Yes 9. Do attached lines have adequate flexibility to avoid damage?10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?Yes Yes Other Adverse Conditions
Equipment ID No.:
: 11. Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
250 VDC BATT 2 Equipment Class:
Comments SEWS Anchorage Notes: Each leg anchored by a single 3/8" Wedge type expansion anchor through a 3x3x1/4" clip angle thru-bolted thru the tube leg.Seismic Walkdown Team: J. Griffith & M. Wodarcyk -8/7/2012 Evaluated by: James Griffith Date: 10/4/2012 Michael Wodarcyk 10/4/2012 C-428 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status: Y N U Seismic Walkdown Checklist (SWC)Equipment ID No.: Equipment Class: Equipment Descrip ion: 250 VDC BATT 2 (15) Batteries on Racks BATTERY, 250V m m m C-429 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status: FYI N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250 VDC BATT 2 Equipment Class: (15) Batteries on Racks C-430 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status: FI N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250 VDC BATT 2 Equipment Class: (15) Batteries on Racks C-431 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status: T N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250 VDC BATT 2 Equipment Class: (15) Batteries on Racks itDescrition BATTERY 250V C-432 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status: Y--1 N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250 VDC BATT 2 Equipment Class: (15) Batteries on Racks C-433 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: FY-] N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250VDC MCC 2 Equipment Class: (1) Motor Control Centers Eauioment Descriotion:
(15) Batteries on Racks itDescrition BATTERY 250V C-432
MCC Project: Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status:
Y--1 N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250 VDC BATT 2 Equipment Class:
(15) Batteries on Racks C-433
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: FY-] N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250VDC MCC 2 Equipment Class:
(1) Motor Control Centers Eauioment Descriotion:
MCC Project:
Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
TB, 615.00 ft, ALL Manufacturer/Model:
TB, 615.00 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings.
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Additional space is provided at the end of this checklist for documenting other comments.Anchorage 1. Is anchorage configuration verification required (i.e., is the item one of the 50%of SWEL items requiring such verification)?
Anchorage
No 2. Is the anchorage free of bent, broken, missing or loose hardware?Yes 3. Is the anchorage free of corrosion that is more than mild surface oxidation?
: 1.
Yes 4. Is the anchorage free of visible cracks in the concrete near the anchors?Yes Minor shrinkage cracks in floor judged to be acceptable.
Is anchorage configuration verification required (i.e., is the item one of the 50%
: 5. Is the anchorage configuration consistent with plant documentation? (Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
of SWEL items requiring such verification)?
No
: 2.
Is the anchorage free of bent, broken, missing or loose hardware?
Yes
: 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes
: 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Yes Minor shrinkage cracks in floor judged to be acceptable.
: 5.
Is the anchorage configuration consistent with plant documentation? (Note:
This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Not Applicable
Not Applicable
: 6. Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
: 6.
Yes C-434 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: T N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250VDC MCC 2 Equipment Class: (1) Motor Control Centers Equipment  
Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes C-434
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status:
T N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250VDC MCC 2 Equipment Class:
(1) Motor Control Centers Equipment
 
== Description:==
MCC Interaction Effects
: 7.
Are soft targets free from impact by nearby equipment or structures?
: 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Overhead light fixtures judged to be acceptable. Masonry wall in vicinity restrained at top and judged to be acceptable.
: 9.
Do attached lines have adequate flexibility to avoid damage?
: 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Yes Yes Yes Other Adverse Conditions
: 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/7/2012 Evaluated by:
James Griffith Date:
10/4/2012 Michael Wodarcyk 10/4/2012 C-435
 
Quad Cities Generating Station Unit 2 1200108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status: FYI N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250VDC MCC 2 Equipment Class:
(1) Motor Control Centers Equipment
 
== Description:==
MCC Photos C-436


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status: [KI N U Seismic Walkdown Checklist (SWC)
Description:==
Equipment ID No.:
250VDC MCC 2 Equipment Class:
(1) Motor Control Centers 20120807-QuadCities-2 200 C-437


MCC Interaction Effects 7. Are soft targets free from impact by nearby equipment or structures?
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status:
: 8. Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
T N
Overhead light fixtures judged to be acceptable.
U Seismic Walkdown Checklist (SWC)
Masonry wall in vicinity restrained at top and judged to be acceptable.
Equipment ID No.:
: 9. Do attached lines have adequate flexibility to avoid damage?10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?Yes Yes Yes Yes Other Adverse Conditions
25OVDC MCC 2 Equipment Class:
: 11. Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
(1) Motor Control Centers C-438
Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk -8/7/2012 Evaluated by: James Griffith Date: 10/4/2012 Michael Wodarcyk 10/4/2012 C-435 Quad Cities Generating Station Unit 2 1200108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status: FYI N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250VDC MCC 2 Equipment Class: (1) Motor Control Centers Equipment


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status: [-ý N U Seismic Walkdown Checklist (SWC)
Description:==
Equipment ID No.:
250VDC MCC 2 Equipment Class:
(1) Motor Control Centers 20120807-QuadCities-2 208 C-439


MCC Photos C-436 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status: [KI N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250VDC MCC 2 Equipment Class: (1) Motor Control Centers 20120807-QuadCities-2 200 C-437 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status: T N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 25OVDC MCC 2 Equipment Class: (1) Motor Control Centers C-438 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status: [-ý N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250VDC MCC 2 Equipment Class: (1) Motor Control Centers 20120807-QuadCities-2 208 C-439 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status: T N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250VDC MCC 2 Equipment Class: (1) Motor Control Centers 20120807-QuadCities-2 211 C-440 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: T N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250VDC MCC 2A Equipment Class: (1) Motor Control Centers Equipment
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status:
T N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250VDC MCC 2 Equipment Class:
(1) Motor Control Centers 20120807-QuadCities-2 211 C-440


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: T N U
Description:==
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250VDC MCC 2A Equipment Class:
(1) Motor Control Centers Equipment


MCC Project: Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
== Description:==
MCC Project:
Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
RB, 623.00 ft, ALL Manufacturer/Model:
RB, 623.00 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings.
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Additional space is provided at the end of this checklist for documenting other comments.Anchorage 1. Is anchorage configuration verification required (i.e., is the item one of the 50%of SWEL items requiring such verification)?
Anchorage
: 2. Is the anchorage free of bent, broken, missing or loose hardware?3. Is the anchorage free of corrosion that is more than mild surface oxidation?
: 1.
: 4. Is the anchorage free of visible cracks in the concrete near the anchors?Minor shrinkage cracks in floor judged to be acceptable.
Is anchorage configuration verification required (i.e., is the item one of the 50%
: 5. Is the anchorage configuration consistent with plant documentation? (Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
of SWEL items requiring such verification)?
: 6. Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
: 2.
Yes Yes Yes Yes Yes Yes C-441 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: TI N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250VDC MCC 2A Equipment Class: (1) Motor Control Centers Equipment
Is the anchorage free of bent, broken, missing or loose hardware?
: 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
: 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Minor shrinkage cracks in floor judged to be acceptable.
: 5.
Is the anchorage configuration consistent with plant documentation? (Note:
This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
: 6.
Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes Yes Yes Yes Yes Yes C-441


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: TI N U
Description:==
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250VDC MCC 2A Equipment Class:
(1) Motor Control Centers Equipment


MCC Interaction Effects 7. Are soft targets free from impact by nearby equipment or structures?
== Description:==
MCC Interaction Effects
: 7.
Are soft targets free from impact by nearby equipment or structures?
Door on back of MCC has minor skew at bottom. Door is adequately latched and judged to be acceptable.
Door on back of MCC has minor skew at bottom. Door is adequately latched and judged to be acceptable.
: 8. Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
: 8.
Overhead light fixtures judged to be acceptable.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Short U-shaped masonry walls (65, 66, and 67 per B-1734, Rev. C) behind MCC are safety-related.
Overhead light fixtures judged to be acceptable. Short U-shaped masonry walls (65, 66, and 67 per B-1734, Rev. C) behind MCC are safety-related.
Yes Yes 9. Do attached lines have adequate flexibility to avoid damage?Yes 10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?Yes Other Adverse Conditions
Yes Yes
: 11. Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
: 9.
Do attached lines have adequate flexibility to avoid damage?
Yes
: 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Other Adverse Conditions
: 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Clearance between MCC and fence judged to be acceptable.
Clearance between MCC and fence judged to be acceptable.
Comments SEWS Anchorage Notes: Welded to embedded angle with total of 33" L 1/4" th fillet distributed fairly even. There is 33" of weld in the front and back. Pad is anchored to floor by 1/2" CEA @ 12" half each side.Seismic Walkdown Team: J. Griffith & M. Wodarcyk -8/6/2012 Evaluated by: James Griffith Date: 10/4/2012 Michael Wodarcyk 10/4/2012 C-442 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status: F N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 25OVDC MCC 2A Equipment Class: (1) Motor Control Centers Equipment  
Comments SEWS Anchorage Notes:
Welded to embedded angle with total of 33" L 1/4" th fillet distributed fairly even. There is 33" of weld in the front and back. Pad is anchored to floor by 1/2" CEA @ 12" half each side.
Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/6/2012 Evaluated by:
James Griffith Date:
10/4/2012 Michael Wodarcyk 10/4/2012 C-442
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
25OVDC MCC 2A Equipment Class:
(1) Motor Control Centers Equipment
 
== Description:==
MCC C-443
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status:
T N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250VDC MCC 2A Equipment Class:
(1) Motor Control Centers zu1 zuaUo-uIuaouIuleS-/"1 is C-444
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status:
Y N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250VDC MCC 2A Equipment Class:
(1) Motor Control Centers C-445


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status:
Description:==
Y N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
25OVDC MCC 2A Equipment Class:
(1) Motor Control Centers C-446


MCC C-443 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status: T N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250VDC MCC 2A Equipment Class: (1) Motor Control Centers zu1 zuaUo-uIuaouIuleS-/"1 is C-444 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status: Y N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250VDC MCC 2A Equipment Class: (1) Motor Control Centers C-445 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status: Y N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 25OVDC MCC 2A Equipment Class: (1) Motor Control Centers C-446 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status: Y-j N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 250VDC MCC 2A Equipment Class: (1) Motor Control Centers C-447 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: T N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5745A Equipment Class: (10) Air Handlers Equipment
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status:
Y-j N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
250VDC MCC 2A Equipment Class:
(1) Motor Control Centers C-447


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status:
Description:==
T N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5745A Equipment Class:
(10) Air Handlers Equipment


COOLER, CUBICLE -HEAT EXCHANGER CONTACT STEAM-LIQUID Project: Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
== Description:==
COOLER, CUBICLE - HEAT EXCHANGER CONTACT STEAM-LIQUID Project:
Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
TB, 547.00 ft, ALL Manufacturer/Model:
TB, 547.00 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings.
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Additional space is provided at the end of this checklist for documenting other comments.Anchorage 1. Is anchorage configuration verification required (i.e., is the item one of the 50%of SWEL items requiring such verification)?
Anchorage
No 2. Is the anchorage free of bent, broken, missing or loose hardware?Yes 3. Is the anchorage free of corrosion that is more than mild surface oxidation?
: 1.
Yes 4. Is the anchorage free of visible cracks in the concrete near the anchors?Not Applicable Supports for cooler are welded to steel framing in ceiling.5. Is the anchorage configuration consistent with plant documentation? (Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Is anchorage configuration verification required (i.e., is the item one of the 50%
of SWEL items requiring such verification)?
No
: 2.
Is the anchorage free of bent, broken, missing or loose hardware?
Yes
: 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes
: 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Not Applicable Supports for cooler are welded to steel framing in ceiling.
: 5.
Is the anchorage configuration consistent with plant documentation? (Note:
This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Not Applicable
Not Applicable
: 6. Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
: 6.
Yes C-448 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: Y]I N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5745A Equipment Class: (10) Air Handlers EcuiDment  
Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes C-448
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: Y]I N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5745A Equipment Class:
(10) Air Handlers EcuiDment
 
== Description:==
COOLER, CUBICLE - HEAT EXCHANGER CONTACT STEAM-LIQUID Interaction Effects
: 7.
Are soft targets free from impact by nearby equipment or structures?
Yes
: 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Yes
: 9.
Do attached lines have adequate flexibility to avoid damage?
Yes
: 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Other Adverse Conditions
: 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the.safety functions of the equipment?
Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/8/2012 Evaluated by:
James Griffith Date:
10/4/2012 Michael Wodarcyk 10/4/2012 C-449
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status:
Y--I N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5745A Equipment Class:
(10) Air Handlers Equipment


==
== Description:==
Description:==
COOLER, CUBICLE - HEAT EXCHANGER CONTACT STEAM-LIQUID C-450


COOLER, CUBICLE -HEAT EXCHANGER CONTACT STEAM-LIQUID Interaction Effects 7. Are soft targets free from impact by nearby equipment or structures?
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status: [-Y N
Yes 8. Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
U Seismic Walkdown Checklist (SWC)
Yes 9. Do attached lines have adequate flexibility to avoid damage?Yes 10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?Yes Other Adverse Conditions
Equipment ID No.:
: 11. Have you looked for and found no adverse seismic conditions that could Yes adversely affect the.safety functions of the equipment?
2-5745A Equipment Class:
Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk -8/8/2012 Evaluated by: James Griffith Date: 10/4/2012 Michael Wodarcyk 10/4/2012 C-449 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status: Y--I N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5745A Equipment Class: (10) Air Handlers Equipment  
(10) Air Handlers Equipment


==
== Description:==
Description:==
COOLER, CUBICLE - HEAT EXCHANGER CONTACT STEAM-LIQUID C-451


COOLER, CUBICLE -HEAT EXCHANGER CONTACT STEAM-LIQUID C-450 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status: [-Y N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5745A Equipment Class: (10) Air Handlers Equipment
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status:
Y-I N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5745A Equipment Class:
(10) Air Handlers C-452


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status:
Description:==
Y] N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5745A Equipment Class:
(10) Air Handlers LE - HEAT U10VOU/
14:0 20120808-QuadCities-2 394 C-453


COOLER, CUBICLE -HEAT EXCHANGER CONTACT STEAM-LIQUID C-451 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status: Y-I N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5745A Equipment Class: (10) Air Handlers C-452 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status: Y] N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5745A Equipment Class: (10) Air Handlers LE -HEAT U10VOU/ 14:0 20120808-QuadCities-2 394 C-453 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status: T N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5745A Equipment Class: (10) Air Handlers C-454 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet I of 13 Status: j-Y] N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers Equipment
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status:
T N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5745A Equipment Class:
(10) Air Handlers C-454


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet I of 13 Status: j-Y] N U Seismic Walkdown Checklist (SWC)
Description:==
Equipment ID No.:
2-5747 Equipment Class:
(10) Air Handlers Equipment


COOLER, CUBICLE -HPCI ROOM COOLER Project: Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
== Description:==
COOLER, CUBICLE - HPCI ROOM COOLER Project:
Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
RB, 554.00 ft, ALL Manufacturer/Model:
RB, 554.00 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings.
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Additional space is provided at the end of this checklist for documenting other comments.Anchorage 1. Is anchorage configuration verification required (i.e., is the item one of the 50% Yes of SWEL items requiring such verification)?
Anchorage
: 1.
Is anchorage configuration verification required (i.e., is the item one of the 50%
Yes of SWEL items requiring such verification)?
Although SQUG notes described 5 rods supporting the cooler, a total of 6 rods were observed supporting the cooler. Each rod has a plate with four 1/2" anchors to the ceiling. Minor bend in 1 of the 6 rods is judged to be acceptable.
Although SQUG notes described 5 rods supporting the cooler, a total of 6 rods were observed supporting the cooler. Each rod has a plate with four 1/2" anchors to the ceiling. Minor bend in 1 of the 6 rods is judged to be acceptable.
: 2. Is the anchorage free of bent, broken, missing or loose hardware?
: 2.
Yes 3. Is the anchorage free of corrosion that is more than mild surface oxidation?
Is the anchorage free of bent, broken, missing or loose hardware?
Yes 4. Is the anchorage free of visible cracks in the concrete near the anchors? Yes 5. Is the anchorage configuration consistent with plant documentation? (Note: Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Yes
: 6. Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?
: 3.
C-455 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 13 Status: LYII N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers Equipment  
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes
: 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Yes
: 5.
Is the anchorage configuration consistent with plant documentation? (Note:
Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
: 6.
Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?
C-455
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 13 Status: LYII N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5747 Equipment Class:
(10) Air Handlers Equipment
 
== Description:==
COOLER, CUBICLE - HPCI ROOM COOLER Interaction Effects
: 7.
Are soft targets free from impact by nearby equipment or structures?
: 8.
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Overhead light fixture with open S-hook. Cooler exhaust ports protect soft targets below. Judged to be acceptable. See IR 1400098.
: 9.
Do attached lines have adequate flexibility to avoid damage?
Cooler is restrained to wall on each end; thus, there are no concerns regarding the relative flexibility of the cooler and attached piping.
: 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Yes Yes Yes Other Adverse Conditions
: 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Comments SEWS Anchorage Notes:
Cooler hung on five 5/8" rods. Each rod is anchored by four 1/2" concrete expansion anchors.
Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/9/2012 Evaluated by:
A" James Griffith Date:
10/16/2012 Michael Wodarcyk 10/16/2012 C-456
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 13 Status:
Y] N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5747 Equipment Class:
(10) Air Handlers Equipment
 
== Description:==
COOLER, CUBICLE - HPCI ROOM COOLER Photos C-457
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 13 Status:
Y-I N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5747 Equipment Class:
(10) Air Handlers C-458
 
Quad Cities Generating Station Unit 2 1200108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 13 Status:
Y N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5747 Equipment Class:
(10) Air Handlers 20120809-QuadCities-2 229 C-459
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 13 Status:
Y-I N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5747 Equipment Class:
(10) Air Handlers LE - HF C-460
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 13 Status: EKI N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5747 Equipment Class:
(10) Air Handlers C-461
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 8 of 13 Status:
YI N U
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5747 Equipment Class:
(10) Air Handlers C-462
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 9 of 13 Status: r-Z N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5747 Equipment Class:
(10) Air Handlers C-463
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 10 of 13 Status: F]
N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5747 Equipment Class:
(10) Air Handlers
,LE - HF C-464


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 11 of 13 Status: r*
Description:==
N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5747 Equipment Class:
(10) Air Handlers
;LE - HPCI RO(
C-465


COOLER, CUBICLE -HPCI ROOM COOLER Interaction Effects 7. Are soft targets free from impact by nearby equipment or structures?
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 12 of 13 Status:
: 8. Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
Y N
Overhead light fixture with open S-hook. Cooler exhaust ports protect soft targets below. Judged to be acceptable.
U Seismic Walkdown Checklist (SWC)
See IR 1400098.9. Do attached lines have adequate flexibility to avoid damage?Cooler is restrained to wall on each end; thus, there are no concerns regarding the relative flexibility of the cooler and attached piping.10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?Yes Yes Yes Yes Other Adverse Conditions
Equipment ID No.:
: 11. Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
2-5747 Equipment Class:
Comments SEWS Anchorage Notes: Cooler hung on five 5/8" rods. Each rod is anchored by four 1/2" concrete expansion anchors.Seismic Walkdown Team: J. Griffith & M. Wodarcyk -8/9/2012 Evaluated by: A" '' James Griffith Date: 10/16/2012 Michael Wodarcyk 10/16/2012 C-456 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 13 Status: Y] N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers Equipment
(10) Air Handlers
;LE - HPCI RO(
C-466


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 13 of 13 Status: [III N U
Description:==
Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5747 Equipment Class:
(10) Air Handlers
- HF C-467


COOLER, CUBICLE -HPCI ROOM COOLER Photos C-457 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 13 Status: Y-I N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers C-458 Quad Cities Generating Station Unit 2 1200108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 13 Status: Y N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers 20120809-QuadCities-2 229 C-459 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 13 Status: Y-I N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers LE -HF C-460 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 13 Status: EKI N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers C-461 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 8 of 13 Status: YI N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers C-462 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 9 of 13 Status: r-Z N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers C-463 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 10 of 13 Status: F] N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers ,LE -HF C-464 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 11 of 13 Status: N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers;LE -HPCI RO(C-465 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 12 of 13 Status: Y N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers;LE -HPCI RO(C-466 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 13 of 13 Status: [III N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5747 Equipment Class: (10) Air Handlers-HF C-467 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: FT I N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5748A Equipment Class: (10) Air Handlers Eauioment Descrirption:
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: FT I N U Seismic Walkdown Checklist (SWC)
COOLER, CUBICLE -2A CS PMP RM COOLER Project: Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
Equipment ID No.:
2-5748A Equipment Class:
(10) Air Handlers Eauioment Descrirption:
COOLER, CUBICLE - 2A CS PMP RM COOLER Project:
Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):
RB, 554.00 ft, ALL Manufacturer/Model:
RB, 554.00 ft, ALL Manufacturer/Model:
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings.
Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.
Additional space is provided at the end of this checklist for documenting other comments.Anchorage 1. Is anchorage configuration verification required (i.e., is the item one of the 50%of SWEL items requiring such verification)?
Anchorage
Yes 2. Is the anchorage free of bent, broken, missing or loose hardware?Yes 3. Is the anchorage free of corrosion that is more than mild surface oxidation?
: 1.
Yes 4. Is the anchorage free of visible cracks in the concrete near the anchors?Minor shrinkage cracks in wall and ceiling judged to be acceptable.
Is anchorage configuration verification required (i.e., is the item one of the 50%
: 5. Is the anchorage configuration consistent with plant documentation? (Note: This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
of SWEL items requiring such verification)?
Yes Yes 6. Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes
Yes C-468 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: FY-] N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5748A Equipment Class: (10) Air Handlers Equipment
: 2.
Is the anchorage free of bent, broken, missing or loose hardware?
Yes
: 3.
Is the anchorage free of corrosion that is more than mild surface oxidation?
Yes
: 4.
Is the anchorage free of visible cracks in the concrete near the anchors?
Minor shrinkage cracks in wall and ceiling judged to be acceptable.
: 5.
Is the anchorage configuration consistent with plant documentation? (Note:
This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)
Yes Yes
: 6. Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?
Yes C-468


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: FY-] N U Seismic Walkdown Checklist (SWC)
Description:==
Equipment ID No.:
2-5748A Equipment Class:
(10) Air Handlers Equipment


COOLER, CUBICLE -2A CS PMP RM COOLER Interaction Effects 7. Are soft targets free from impact by nearby equipment or structures?
== Description:==
COOLER, CUBICLE - 2A CS PMP RM COOLER Interaction Effects
: 7.
Are soft targets free from impact by nearby equipment or structures?
Tube in contact with cooler brace. Tube is flexible, brace is rigid; judged to be acceptable.
Tube in contact with cooler brace. Tube is flexible, brace is rigid; judged to be acceptable.
: 8. Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
: 8.
: 9. Do attached lines have adequate flexibility to avoid damage?Cooler is restrained to wall; thus, there are no concerns regarding the relative flexibility of the cooler and attached piping.10. Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?Yes Yes Yes Yes Other Adverse Conditions
Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?
: 11. Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
: 9.
Comments SEWS Anchorage Notes: Cooler supported by four 5/8" rods. Each rod is anchored by four 1/2" concrete expansion anchors.Seismic Walkdown Team: J. Griffith & M. Wodarcyk -8/9/2012 Evaluated by: 0 VA James Griffith Date: 10/4/2012 Michael Wodarcyk 10/4/2012 C-469 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status: F N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5748A Equipment Class: (10) Air Handlers Equipment  
Do attached lines have adequate flexibility to avoid damage?
Cooler is restrained to wall; thus, there are no concerns regarding the relative flexibility of the cooler and attached piping.
: 10.
Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?
Yes Yes Yes Yes Other Adverse Conditions
: 11.
Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?
Comments SEWS Anchorage Notes:
Cooler supported by four 5/8" rods. Each rod is anchored by four 1/2" concrete expansion anchors.
Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/9/2012 Evaluated by:
0 VA James Griffith Date:
10/4/2012 Michael Wodarcyk 10/4/2012 C-469
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status: F N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5748A Equipment Class:
(10) Air Handlers Equipment
 
== Description:==
COOLER, CUBICLE - 2A CS PMP RM COOLER Photos C-470
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status:
T N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5748A Equipment Class:
(10) Air Handlers C-471
 
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status: [YII N U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5748A Equipment Class:
(10) Air Handlers C-472


==
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status: rj-N U Seismic Walkdown Checklist (SWC)
Description:==
Equipment ID No.:
2-5748A Equipment Class:
(10) Air Handlers LE - 2A CS F C-473


COOLER, CUBICLE -2A CS PMP RM COOLER Photos C-470 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status: T N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5748A Equipment Class: (10) Air Handlers C-471 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status: [YII N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5748A Equipment Class: (10) Air Handlers C-472 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status: rj- N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5748A Equipment Class: (10) Air Handlers LE -2A CS F C-473 Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status: T N U Seismic Walkdown Checklist (SWC)Equipment ID No.: 2-5748A Equipment Class: (10) Air Handlers E -2A CS PMP RM COOLER C-474}}
Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status:
T N
U Seismic Walkdown Checklist (SWC)
Equipment ID No.:
2-5748A Equipment Class:
(10) Air Handlers E - 2A CS PMP RM COOLER C-474}}

Latest revision as of 19:34, 11 January 2025

Report 12Q0108.40-R-002, Rev. 3, Seismic Walkdown Report in Response to the 50.54(f) Information Request Re Fukushima Near-Term Force Recommendation 2.3: Seismic for Quad Cities Generating Station Unit 2. Part 9 of 15
ML12361A092
Person / Time
Site: Quad Cities Constellation icon.png
Issue date: 10/31/2012
From: Delaney M
Stevenson & Associates
To:
Office of Nuclear Reactor Regulation
Shared Package
ML123620010 List:
References
RS-12-169 12Q0108.40-R-002, Rev 3
Download: ML12361A092 (52)


Text

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 4 Status: --Y--I N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-3903 Equipment Class:

(5) Horizontal Pumps Eauioment DescriDtion:

PUMP, DG COOLING - U2 DIESEL GENERATOR COOLING WATER PUMP Project:

Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):

TB, 547.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

Yes

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Yes

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-423

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 4 Status: Eli] N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-3903 Equipment Class:

(5) Horizontal Pumps Eauioment DescriDtion:

PUMP. DG COOLING - U2 DIESEL GENERATOR COOLING WATER PUMP Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead light fixtures judged to be acceptable.

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments SEWS Anchorage Notes:

Pump anchored by six 7/8" (3 per side) cast-in-place anchors.

Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/8/2012 Evaluated by:

James Griffith Date:

10/4/2012 Michael Wodarcyk 10/4/2012 C-424

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 4 Status: r-1 N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-3903 Equipment Class:

(5) Horizontal Pumps Equipment

Description:

PUMP, DG COOLING - U2 DIESEL GENERATOR COOLING WATER PUMP Photos C-425

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 4 Status: Fv7i N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-390 3 Equipment Class:

EauiDment DescriDtion:

(5) Horizontal Pumps PUMP. DG COOLING - U2 DIESEL GENERATOR COOLING WATER PUMP 20120808-QuadCities-2 363 20120808-QuadCities-2 364 C-426

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: LY N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250 VDC BATT 2 Equipment Class:

(15) Batteries on Racks Equipment

Description:

BATTERY, 250V Project:

Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):

TB, 628.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchoracqe

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

Yes of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes Although a missing anchor was discussed in the SQUG notes, a thorough examination revealed that there are no missing anchors.

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes Minor surface corrosion judged to be acceptable.

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes Minor floor shrinkage cracks judged to be acceptable.

5.

Is the anchorage configuration consistent with plant documentation? (Note:

Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

6.

Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?

C-427

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: F N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250 VDC BATT 2 Equipment Class:

(15) Batteries on Racks Equipment

Description:

BATTERY, 250V Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments SEWS Anchorage Notes:

Each leg anchored by a single 3/8" Wedge type expansion anchor through a 3x3x1/4" clip angle thru-bolted thru the tube leg.

Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/7/2012 Evaluated by:

James Griffith Date:

10/4/2012 Michael Wodarcyk 10/4/2012 C-428

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status:

Y N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

Equipment Class:

Equipment Descrip ion:

250 VDC BATT 2 (15) Batteries on Racks BATTERY, 250V m m m

C-429

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status: FYI N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250 VDC BATT 2 Equipment Class:

(15) Batteries on Racks C-430

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status: FI N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250 VDC BATT 2 Equipment Class:

(15) Batteries on Racks C-431

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status:

T N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250 VDC BATT 2 Equipment Class:

(15) Batteries on Racks itDescrition BATTERY 250V C-432

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status:

Y--1 N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250 VDC BATT 2 Equipment Class:

(15) Batteries on Racks C-433

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: FY-] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250VDC MCC 2 Equipment Class:

(1) Motor Control Centers Eauioment Descriotion:

MCC Project:

Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):

TB, 615.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes Minor shrinkage cracks in floor judged to be acceptable.

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-434

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status:

T N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250VDC MCC 2 Equipment Class:

(1) Motor Control Centers Equipment

Description:

MCC Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead light fixtures judged to be acceptable. Masonry wall in vicinity restrained at top and judged to be acceptable.

9.

Do attached lines have adequate flexibility to avoid damage?

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/7/2012 Evaluated by:

James Griffith Date:

10/4/2012 Michael Wodarcyk 10/4/2012 C-435

Quad Cities Generating Station Unit 2 1200108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status: FYI N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250VDC MCC 2 Equipment Class:

(1) Motor Control Centers Equipment

Description:

MCC Photos C-436

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status: [KI N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250VDC MCC 2 Equipment Class:

(1) Motor Control Centers 20120807-QuadCities-2 200 C-437

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status:

T N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

25OVDC MCC 2 Equipment Class:

(1) Motor Control Centers C-438

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status: [-ý N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250VDC MCC 2 Equipment Class:

(1) Motor Control Centers 20120807-QuadCities-2 208 C-439

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status:

T N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250VDC MCC 2 Equipment Class:

(1) Motor Control Centers 20120807-QuadCities-2 211 C-440

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: T N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250VDC MCC 2A Equipment Class:

(1) Motor Control Centers Equipment

Description:

MCC Project:

Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):

RB, 623.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

2.

Is the anchorage free of bent, broken, missing or loose hardware?

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Minor shrinkage cracks in floor judged to be acceptable.

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes Yes Yes Yes Yes Yes C-441

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: TI N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250VDC MCC 2A Equipment Class:

(1) Motor Control Centers Equipment

Description:

MCC Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Door on back of MCC has minor skew at bottom. Door is adequately latched and judged to be acceptable.

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead light fixtures judged to be acceptable. Short U-shaped masonry walls (65, 66, and 67 per B-1734, Rev. C) behind MCC are safety-related.

Yes Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Clearance between MCC and fence judged to be acceptable.

Comments SEWS Anchorage Notes:

Welded to embedded angle with total of 33" L 1/4" th fillet distributed fairly even. There is 33" of weld in the front and back. Pad is anchored to floor by 1/2" CEA @ 12" half each side.

Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/6/2012 Evaluated by:

James Griffith Date:

10/4/2012 Michael Wodarcyk 10/4/2012 C-442

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

25OVDC MCC 2A Equipment Class:

(1) Motor Control Centers Equipment

Description:

MCC C-443

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status:

T N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250VDC MCC 2A Equipment Class:

(1) Motor Control Centers zu1 zuaUo-uIuaouIuleS-/"1 is C-444

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status:

Y N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250VDC MCC 2A Equipment Class:

(1) Motor Control Centers C-445

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status:

Y N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

25OVDC MCC 2A Equipment Class:

(1) Motor Control Centers C-446

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status:

Y-j N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

250VDC MCC 2A Equipment Class:

(1) Motor Control Centers C-447

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status:

T N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5745A Equipment Class:

(10) Air Handlers Equipment

Description:

COOLER, CUBICLE - HEAT EXCHANGER CONTACT STEAM-LIQUID Project:

Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):

TB, 547.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

No

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Not Applicable Supports for cooler are welded to steel framing in ceiling.

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Not Applicable

6.

Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-448

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: Y]I N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5745A Equipment Class:

(10) Air Handlers EcuiDment

Description:

COOLER, CUBICLE - HEAT EXCHANGER CONTACT STEAM-LIQUID Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Yes

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Yes

9.

Do attached lines have adequate flexibility to avoid damage?

Yes

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the.safety functions of the equipment?

Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/8/2012 Evaluated by:

James Griffith Date:

10/4/2012 Michael Wodarcyk 10/4/2012 C-449

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status:

Y--I N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5745A Equipment Class:

(10) Air Handlers Equipment

Description:

COOLER, CUBICLE - HEAT EXCHANGER CONTACT STEAM-LIQUID C-450

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status: [-Y N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5745A Equipment Class:

(10) Air Handlers Equipment

Description:

COOLER, CUBICLE - HEAT EXCHANGER CONTACT STEAM-LIQUID C-451

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status:

Y-I N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5745A Equipment Class:

(10) Air Handlers C-452

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status:

Y] N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5745A Equipment Class:

(10) Air Handlers LE - HEAT U10VOU/

14:0 20120808-QuadCities-2 394 C-453

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status:

T N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5745A Equipment Class:

(10) Air Handlers C-454

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet I of 13 Status: j-Y] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers Equipment

Description:

COOLER, CUBICLE - HPCI ROOM COOLER Project:

Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):

RB, 554.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

Yes of SWEL items requiring such verification)?

Although SQUG notes described 5 rods supporting the cooler, a total of 6 rods were observed supporting the cooler. Each rod has a plate with four 1/2" anchors to the ceiling. Minor bend in 1 of the 6 rods is judged to be acceptable.

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Yes

5.

Is the anchorage configuration consistent with plant documentation? (Note:

Yes This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

6.

Based on the above anchorage evaluations, is the anchorage free of Yes potentially adverse seismic conditions?

C-455

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 13 Status: LYII N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers Equipment

Description:

COOLER, CUBICLE - HPCI ROOM COOLER Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

Overhead light fixture with open S-hook. Cooler exhaust ports protect soft targets below. Judged to be acceptable. See IR 1400098.

9.

Do attached lines have adequate flexibility to avoid damage?

Cooler is restrained to wall on each end; thus, there are no concerns regarding the relative flexibility of the cooler and attached piping.

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments SEWS Anchorage Notes:

Cooler hung on five 5/8" rods. Each rod is anchored by four 1/2" concrete expansion anchors.

Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/9/2012 Evaluated by:

A" James Griffith Date:

10/16/2012 Michael Wodarcyk 10/16/2012 C-456

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 13 Status:

Y] N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers Equipment

Description:

COOLER, CUBICLE - HPCI ROOM COOLER Photos C-457

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 13 Status:

Y-I N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers C-458

Quad Cities Generating Station Unit 2 1200108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 13 Status:

Y N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers 20120809-QuadCities-2 229 C-459

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 13 Status:

Y-I N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers LE - HF C-460

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 13 Status: EKI N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers C-461

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 8 of 13 Status:

YI N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers C-462

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 9 of 13 Status: r-Z N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers C-463

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 10 of 13 Status: F]

N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers

,LE - HF C-464

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 11 of 13 Status: r*

N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers

LE - HPCI RO(

C-465

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 12 of 13 Status:

Y N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers

LE - HPCI RO(

C-466

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 13 of 13 Status: [III N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5747 Equipment Class:

(10) Air Handlers

- HF C-467

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: FT I N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5748A Equipment Class:

(10) Air Handlers Eauioment Descrirption:

COOLER, CUBICLE - 2A CS PMP RM COOLER Project:

Quad Cities 2 SWEL Location (Bldg, Elev, Room/Area):

RB, 554.00 ft, ALL Manufacturer/Model:

Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1.

Is anchorage configuration verification required (i.e., is the item one of the 50%

of SWEL items requiring such verification)?

Yes

2.

Is the anchorage free of bent, broken, missing or loose hardware?

Yes

3.

Is the anchorage free of corrosion that is more than mild surface oxidation?

Yes

4.

Is the anchorage free of visible cracks in the concrete near the anchors?

Minor shrinkage cracks in wall and ceiling judged to be acceptable.

5.

Is the anchorage configuration consistent with plant documentation? (Note:

This question only applies if the item is one of the 50% for which an anchorage configuration verification is required.)

Yes Yes

6. Based on the above anchorage evaluations, is the anchorage free of potentially adverse seismic conditions?

Yes C-468

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: FY-] N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5748A Equipment Class:

(10) Air Handlers Equipment

Description:

COOLER, CUBICLE - 2A CS PMP RM COOLER Interaction Effects

7.

Are soft targets free from impact by nearby equipment or structures?

Tube in contact with cooler brace. Tube is flexible, brace is rigid; judged to be acceptable.

8.

Are overhead equipment, distribution systems, ceiling tiles and lighting, and masonry block walls not likely to collapse onto the equipment?

9.

Do attached lines have adequate flexibility to avoid damage?

Cooler is restrained to wall; thus, there are no concerns regarding the relative flexibility of the cooler and attached piping.

10.

Based on the above seismic interaction evaluations, is equipment free of potentially adverse seismic interaction effects?

Yes Yes Yes Yes Other Adverse Conditions

11.

Have you looked for and found no adverse seismic conditions that could Yes adversely affect the safety functions of the equipment?

Comments SEWS Anchorage Notes:

Cooler supported by four 5/8" rods. Each rod is anchored by four 1/2" concrete expansion anchors.

Seismic Walkdown Team: J. Griffith & M. Wodarcyk - 8/9/2012 Evaluated by:

0 VA James Griffith Date:

10/4/2012 Michael Wodarcyk 10/4/2012 C-469

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status: F N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5748A Equipment Class:

(10) Air Handlers Equipment

Description:

COOLER, CUBICLE - 2A CS PMP RM COOLER Photos C-470

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status:

T N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5748A Equipment Class:

(10) Air Handlers C-471

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status: [YII N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5748A Equipment Class:

(10) Air Handlers C-472

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status: rj-N U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5748A Equipment Class:

(10) Air Handlers LE - 2A CS F C-473

Quad Cities Generating Station Unit 2 12Q0108.40-R-002, Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status:

T N

U Seismic Walkdown Checklist (SWC)

Equipment ID No.:

2-5748A Equipment Class:

(10) Air Handlers E - 2A CS PMP RM COOLER C-474