Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 11 Status: [Y] N U
Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-Ul-16 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.
Additional space is provided at the end of this checklist for documenting other comments.
- 1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
- 2.
Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
Minor lack of thread engagement judged to be acceptable.
- 3.
Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,
condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
- 4.
Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Several light fixtures with slightly-open S-hooks; not open enough to allow light fixture to fall from hook. Judged to be acceptable. Identified in IR 1404697.
One light fixture beam clamp oriented incorrectly. Station vertical seismic acceleration is low. Judged to be acceptable. Identified in IR 1404697.
- 5.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?
Threaded fire piping, room heater, and associated piping well-supported. All other piping is welded.
- 6.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?
Hydrogen bottles well-supported in rack. Other gas bottles adequately chained.
D-119
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 11 Status: [I] N U Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-U1-16 7.
Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Valve chained on floor to robust UI RHR to FPC pipe. Judged to be acceptable.
Yes Spool piece toolbox within 12 inches of robust duct riser. Judged to be acceptable.
Stanchions relocated to acceptable position during walkdown.
- 8.
Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Variety of minor bends in rod hangers all judged to be acceptable.
Yes Comments Seismic Walkdown Team: D. Carter & J. Griffith - 8/21/2012 Evaluated by:
_Jd62k. David Carter Date:
10/4/2012 Ae James Griffith 10/4/2012 D-120
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 11 Status: EKI N U Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-Ul-16 D-121
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 11 Status: F N U Area Walk-By Checklist (AWC)
ULC I -
D-122
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 11 Status: r-* N U
Area Walk-By Checklist (AWC)
D-123
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 11 Status: EI N U Area Walk-By Checklist (AWC)
D-124
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 11 Status: LIII N U
Area Walk-By Checklist (AWC) 8-21-12 Quad Cities 231 D-125
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 8 of 11 Status: FYII N U Area Walk-By Checklist (AWC)
D-126
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 9 of 11 Status: LII N U
Area Walk-By Checklist (AWC)
D-1 27
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 10 of 11 Status:
Y N
U Area Walk-By Checklist (AWC)
D-1 28
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 11 of 11 Status: F-] N U Area Walk-By Checklist (AWC) 8-21-12 Quad Cities 238 D-129
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 10 Status:
] N U
Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-Ul-17 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.
Additional space is provided at the end of this checklist for documenting other comments.
- 1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?.
- 2.
Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
Minor lack of thread engagement judged to be acceptable.
- 3.
Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,
condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
- 4.
Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Incorrect beam clamp orientation between HCU rows. Station vertical seismic acceleration is small. Judged to be acceptable. Identified in IR 1404697.
Overhead light fixture with slightly-open S-hook. Fixture not able to fall from hook. Identified in IR 1404697..
1 of 2 bolts missing between backs of racks at positions 30-51 and 30-35 at top. Judged to be acceptable. Identified in IR 1403391.
8'x8' 3-sided U-shaped masonry wall (107, 117, and 118 per B-1 734, Rev. C) is safety related.
- 5.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?
Threaded fire pipe is well supported and judged acceptable.
Two room heaters and associated piping well supported and judged to be acceptable.
- 6.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?
D-130
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 10 Status:
I N U
Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-Ul-17
- 7.
Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Gas bottles well supported in rack. No concern.
Seismic storage issue corrected during walkdown. See IR 1405922.
- 8.
Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Minor bends in rod hangers judged to be acceptable.
Interaction between various pipes and conduits judged to be acceptable.
Yes Yes Cabinet 2201-86A with doors open. Per A T#843351-02 and WR#2869 77:
cabinet is not safety-related nor a seismic concern.
Comments Seismic Walkdown Team: D. Carter & J. Griffith - 8/21/2012 Evaluated by:
QZJA/dk David Carter Date:
10/4/2012 James Griffith 10/4/2012 Photos D-131
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 10 Status: LI-I N U
Area Walk-By Checklist (AWC)
D-132
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 10 Status: F-] N U
Area Walk-By Checklist (AWC)
D-133
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 10 Status: r N U Area Walk-By Checklist (AWC)
D-1 34
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 10 Status:
T N
U Area Walk-By Checklist (AWC)
D-135
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 10 Status: r-j N U
Area Walk-By Checklist (AWC)
D-1 36
Quad Cities Generating Station Unit I 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 8 of 10 Status: FYZ N U Area Walk-By Checklist (AWC)
D-137
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 9 of 10 Status: [-* N U Area Walk-By Checklist (AWC)
D-138
Quad Cities Generating Station Unit 1 12QO108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 10 of 10 Status: FY-] N U Area Walk-By Checklist (AWC)
D-139
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 5 Status: FY-] N U Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-U1-18 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.
Additional space is. provided at the end of this checklist for documenting other comments.
- 1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
- 2.
Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
- 3.
Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,
condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Conduits close to rod hangers with adequate flexibility are judged to be acceptable.
- 4.
Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
IR 1402669:
Overhead light fixtures have open S-hooks. Excessive swing mitigated by conduit, unistrut, etc. Fixtures not judged to disengage from S-hooks and therefore are acceptable. Repaired by FIN team on 8/20/12.
- 5.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?
- 6.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?
- 7.
Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.j., scaffoldinq, lead shielding)?
D-140
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 5 Status: F-1 N U Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-U1-18
- 8.
Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?
Comments Seismic Walkdown Team: D. Carter & J. Griffith - 8/20/2012 Evaluated by:
,*,A(Qk David Carter Date:
10/4/2012 James Griffith 10/4/2012 D-141
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 5 Status: r N
U Area Walk-By Checklist (AWC)
D-142
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 5 Status:
Yj N U
Area Walk-By Checklist (AWC)
D-143
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 5 Status: ErI N U Area Walk-By Checklist (AWC)
D-144
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 2 Status: E-N U
Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-U1-19 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.
Additional space is provided at the end of this checklist for documenting other comments.
- 1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
- 2.
Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
- 3.
Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,
condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Overhead equipment not visible due to drop ceilings outside of cabinet and sheet metal ceiling inside.
- 4.
Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
- 5.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?
- 6.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?
D-145
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 2 Status:
Y N
U Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-Ul-19
- 7.
Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Stored rolling ladder near Panels 901-13 and 943-5. Informed Unit Supervisor to resolve.
Panels 901-55 and 901-56 have small filing cabinets next to each end of cabinets. Filing cabinet orientation acceptable to prevent seismic interaction.
Informed Unit Supervisor to correct.
Orientation of file cabinets located behind control boards in north east comer prevents interaction with main control boards.
See IR 1405922.
Large cabinets anchored to wall and judged to be acceptable.
- 8.
Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Yes Comments Seismic Walkdown Team: D. Carter & J. Griffith - 8/20/2012 Per Operations, no photos permitted in control room.
Evaluated by:
P,-JJA6.
David Carter Date:
10/4/2012 James Griffith 10/4/2012 Photos D-146
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 8 Status: F N
U Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-Ul-20 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.
Additional space is provided at the end of this checklist for documenting other comments.
- 1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
- 2.
Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
- 3.
Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,
condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
- 4.
Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Trolley on top currently at middle of switchgear 19, away from stops. Current position judged to be acceptable. Pin recommended as permanent fix. Current condition is judged to be acceptable. See IR 1419584.
Adjacent masonry wall at south end near switchgear 19 restrained at top.
Judged to be acceptable.
Light fixture at south end of switchgear 18 has open S-hooks; mitigated by position and power cord tether to wall. Judged to be acceptable. Identified in IR 1403072.
Rod-hung conduits in contact with fire protection pipe rod hangers. Conduits and rods are flexible and judged to be acceptable.
- 5.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?
Threaded fire piping well-supported.
- 6.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?
D-147
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 8 Status: F N U Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-Ul-20
- 7.
Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Ladder near abandoned MG set judged to be acceptable. Relocated Operations gang-box during walk-by. See IR 1405922.
- 8.
Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Yes Yes Comments Seismic Walkdown Team: D. Carter & J. Griffith - 8/20/2012 Evaluated by:
,;ldk, David Carter Date:
10/12/2012 A
James Griffith 10/12/2012 D-148
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 8 Status: LI N U Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-Ul-20 D-149
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 8 Status: T N U Area Walk-By Checklist (AWC)
D-150
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 8 Status: LI] N U
Area Walk-By Checklist (AWC)
D-151
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 8 Status:
T N
U Area Walk-By Checklist (AWC)
Location Bid Eievs Room/Area AWC-U 1 -20 8-20-12 Quad Cities 180 (8) 8-20-12 Quad Cities 215 (1)
D-152
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 8 Status: jYjj N U
Area Walk-By Checklist (AWC)
D-153
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 8 of 8 Status: FT-1 N U
Area Walk-By Checklist (AWC)
D-154
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 5 Status: F N U Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-U1-21 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near oneor more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.
Additional space is provided at the end of this checklist for documenting other comments.
- 1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
- 2.
Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
- 3.
Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,
condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
- 4.
Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Masonry wall adjacent to Switchgear 14-1 restrained at top. Judged to be acceptable.
Fire piping in contact with robust portion of light fixture; judged to be acceptable.
Rod-hung conduit in contact with fire protection pipe rod hangers. Conduit and hangers are flexible and judged to be acceptable.
- 5.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?
Fire piping well-supported.
- 6.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?
Metal oil rag storage bin with cover judged to be acceptable.
D-155
Quad Cities Generating Station Unit I 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 5 Status: FYi N U Area Walk-By Checklist (AWC)
Location (Bldg, 8lev, Room/Area):
AWC-Ul-21
- 7.
Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Station ladder near abandoned MG set judged to be acceptable.
- 8.
Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?
Yes Yes Comments Seismic Walkdown Team: D. Carter & J. Griffith - 8/20/2012 Evaluated by:
- .AI*.
David Carter Date:
10/4/2012
- 0 James Griffith 10/4/2012 Photos D-1 56
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 5 Status: F] N U Area Walk-By Checklist (AWC)
D-157
Quad Cities Generating Station Unit 1 12Q0108.40-R-O01 Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 5 Status: YI N U
Area Walk-By Checklist (AWC)
D-158
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 5 Status: EY N U Area Walk-By Checklist (AWC) 8-20-12 Quad Cities 231 (7) t-zu-iz uuao tItles zoi (w)
D-159
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 6 Status: F] N U Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-U1-22 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.
Additional space is provided at the end of this checklist for documenting other comments.
- 1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
2, Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
1-1001-160A PI support corroded on side. Judged to be acceptable for small gauge load.
- 3.
Based on a visual inspection from the floor, do' the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,
condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Bare pipe in contact with insulated pipe at several locations. Judged to be acceptable.
- 4.
Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Overhead light fixtures judged to be acceptable.
- 5.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?
Sump in room. Threaded fire pipe well-supported, all other pipes welded.
- 6.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?
- 7.
Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Humidifier acceptable; no soft targets.
Teletower scaffold with outriggers in place will not overturn. Located near robust targets. Judged to be acceptable. See IR 1405922.
D-160
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 6 Status: FTI N U
Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-U1-22
- 8.
Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?
Comments Seismic Walkdown Team: D. Carter & J. Griffith - 8/22/2012 Evaluated by:
David Carter Date:
10/4/2012 V'
James Griffith 10/4/2012 D-161
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 6 Status: F-] N U Area Walk-By Checklist (AWC)
D-162
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 6 Status: Eli N U Area Walk-By Checklist (AWC)
D-163
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 6 Status:
T N
U Area Walk-By Checklist (AWC)
D-164
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 6 Status: LII N U Area Walk-By Checklist (AWC)
D-165
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 10 Status:
T N
U Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-U1-23 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.
Additional space is provided at the end of this checklist for documenting other comments.
- 1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
- 2.
Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
- 3.
Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,
condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
- 4.
Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Overhead light fixtures judged to be acceptable.
- 5.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?
Fire piping, room heater, and associated piping well-supported judged to be acceptable.
- 6.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?
- 7.
Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Scaffold behind MCC 18-3 is restrained against tipping (braces to ceiling) and against movement (brace to wall and contact with robust auxiliary steel).
Judged to be acceptable.
D-166
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 10 Status: [-i] N U
Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-U1-23
- 8.
Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?
Comments Seismic Walkdown Team: D. Carter & J. Griffith on 8/22/12 Evaluated by:
Z-4-7 David Carter Date:
10/4/2012 P
James Griffith 10/4/2012 D-167
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 10 Status: F N U Area Walk-By Checklist (AWC)
D-168
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 10 Status:
YII N U Area Walk-By Checklist (AWC)
D-1 69
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 10 Status: r-]
N U
Area Walk-By Checklist (AWC) u-zz-iz uuaa uixies 1 iu D-170
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 10 Status: El N U Area Walk-By Checklist (AWC) s-zz-1iz uuaa tImeS -iwz D-171
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 10 Status: FY] N U
Area Walk-By Checklist (AWC)
D-1 72
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 8 of 10 Status: EZ] N U
Area Walk-By Checklist (AWC) 8-22-12 Quad Cities 197 D-173
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 9 of 10 Status: [Y N U Area Walk-By Checklist (AWC)
D-174
Quad Cities Generating Station Unit I 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 10 of 10 Status: El] N U
Area Walk-By Checklist (AWC) 8-22-12 Quad Cities 200 D-175
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 1 of 7 Status: ET] N U
Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-Ul-24 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.
Additional space is provided at the end of this checklist for documenting other comments.
- 1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?
Pipe support at 1-2301-42 base plate has minor edge gap. Judged to be acceptable.
- 2.
Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
1-2304-3 switch box missing I of 4 anchors. Unistruts and anchors with minor corrosion. Judged to be acceptable.
- 3.
Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g.,
condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?
Minor bends in hanger rods judged to be acceptable. Several contacts between flexible items judged to be acceptable.
- 4.
Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
Overhead light fixtures with slightly-open S-hooks not open enough for fixture to fall from hook. Judged to be acceptable.
- 5.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?
Threaded fire piping, room heaters, and associated piping well-supported and judged to be acceptable.
- 6.
Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?
Covered oil waste can is judged to be acceptable.
- 7.
Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?
Ladder chained to rugged pipe at pipe support judged to be acceptable.
Two scaffolds in room are well-restrained.
D-176
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 2 of 7 Status: F N U Area Walk-By Checklist (AWC)
Location (Bldg, Elev, Room/Area):
AWC-Ul-24
- 8.
Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?
Floor grating/gallery supports unanchored at some locations. Walls and edge of slab restrain gallery/gallery laterally. Judged to be acceptable.
Conduit near Valve 1-2301-6-MO missing support attachment judged not to be of seismic concern. Valve 1-2301-3-MO missing I of 4 support bolts. Seismic acceleration of basement is low and support is rgidly mounted. Judged to be acceptable. See IR 1404153.
Comments Seismic Walkdown Team: D. Carter & J. Griffith - 8/23/2012 Evaluated by-
,QI-IQ*, David Carter Date:
10/12/2012 A,
James Griffith 10/12/2012 D-177
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 3 of 7 Status: F N
U Area Walk-By Checklist (AWC)
D-178
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 4 of 7 Status: rY_] N U
Area Walk-By Checklist (AWC)
D-179
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 5 of 7 Status: rYIII N U
Area Walk-By Checklist (AWC)
D-180
Quad Cities Generating Station Unit 1 12Q0108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 6 of 7 Status: L-* N U
Area Walk-By Checklist (AWC)
D-181
Quad Cities Generating Station Unit 1 1200108.40-R-001 Rev. 3 Correspondence No.: RS-12-169 Sheet 7 of 7 Status: F-* N U
Area Walk-By Checklist (AWC)
D-182