ENS 40225: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 10/05/2003 03:00 EDT
| event date = 10/05/2003 03:00 EDT
| last update date = 11/19/2003
| last update date = 11/19/2003
| title = Inoperable Trains Of Control Room Emergency Filtration At Hope Creek
| title = Inoperable Trains of Control Room Emergency Filtration at Hope Creek
| event text = While performing common mode failure testing of the Emergency Diesel Generators (EDG), the 'C' EDG was declared INOPERABLE for planned installation of required test equipment. Concurrent with the inoperability of the 'C' EDG, the 'B' Control Room Emergency Filtration (CREF) System has been INOPERABLE for emergent corrective maintenance since 10/2/03 at 0502. Because the 'C' EDG is the emergency power supply for the 'A' CREF train, 'A' CREF was also declared INOPERABLE and Technical Specification 3.0.3 was entered as of 0300 hrs on 10/05/03. At 0430 hrs on 10/05/03, the test equipment was removed from 'C' EDG, thereby restoring it and 'A' CREF to an operable status, and Technical Specification 3.0.3 was exited. Testing did verify the absence of a common mode failure and all EDG's are operable. The Control Room Ventilation System provides heating, cooling, ventilation, and environmental control for the control room and adjacent areas. Under accident conditions, CREF ensures that the control room will remain habitable during and following all design basis accidents. Because the CREF system is required to automatically respond in the event of a design basis accident, having both trains of CREF inoperable at the same time impacted the ability to mitigate the consequences of an accident. Therefore, this event is being reported in accordance with 10CFR50.72(b)(3)(v)(D). The plant is currently in HOT SHUTDOWN for repair of an emergent turbine hydraulic fluid leak, with decay heat removal to the main condenser via turbine bypass valves.
| event text = While performing common mode failure testing of the Emergency Diesel Generators (EDG), the 'C' EDG was declared INOPERABLE for planned installation of required test equipment. Concurrent with the inoperability of the 'C' EDG, the 'B' Control Room Emergency Filtration (CREF) System has been INOPERABLE for emergent corrective maintenance since 10/2/03 at 0502. Because the 'C' EDG is the emergency power supply for the 'A' CREF train, 'A' CREF was also declared INOPERABLE and Technical Specification 3.0.3 was entered as of 0300 hrs on 10/05/03. At 0430 hrs on 10/05/03, the test equipment was removed from 'C' EDG, thereby restoring it and 'A' CREF to an operable status, and Technical Specification 3.0.3 was exited. Testing did verify the absence of a common mode failure and all EDG's are operable. The Control Room Ventilation System provides heating, cooling, ventilation, and environmental control for the control room and adjacent areas. Under accident conditions, CREF ensures that the control room will remain habitable during and following all design basis accidents. Because the CREF system is required to automatically respond in the event of a design basis accident, having both trains of CREF inoperable at the same time impacted the ability to mitigate the consequences of an accident. Therefore, this event is being reported in accordance with 10CFR50.72(b)(3)(v)(D). The plant is currently in HOT SHUTDOWN for repair of an emergent turbine hydraulic fluid leak, with decay heat removal to the main condenser via turbine bypass valves.
The NRC resident inspector was notified by the licensee.
The NRC resident inspector was notified by the licensee.

Latest revision as of 22:24, 1 March 2018

ENS 40225 +/-
Where
Hope Creek PSEG icon.png
New Jersey (NRC Region 1)
Reporting
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident
Time - Person (Reporting Time:+-0.57 h-0.0238 days <br />-0.00339 weeks <br />-7.80786e-4 months <br />)
Opened: Art Bready
06:26 Oct 5, 2003
NRC Officer: Rich Laura
Last Updated: Nov 19, 2003
40225 - NRC Website
Loading map...