ML20141K899: Difference between revisions

From kanterella
Jump to navigation Jump to search
(StriderTol Bot insert)
 
(StriderTol Bot change)
 
Line 14: Line 14:
| document type = TECHNICAL SPECIFICATIONS, TECHNICAL SPECIFICATIONS & TEST REPORTS
| document type = TECHNICAL SPECIFICATIONS, TECHNICAL SPECIFICATIONS & TEST REPORTS
| page count = 11
| page count = 11
| project =
| stage = Other
}}
}}


Line 167: Line 169:
Comed has evaluated the piping configuration for the ECCS discharge piping of the ECCS subsystems. A specific engineering evaluation of both a voided 2-inch and 8-inch                '
Comed has evaluated the piping configuration for the ECCS discharge piping of the ECCS subsystems. A specific engineering evaluation of both a voided 2-inch and 8-inch                '
RH line was performed. This evaluation concluded that the piping can withstand the dynamic loads caused by the maximum credible air void. Due to the higher-pressure l                        rating and smaller size of the SI and CV discharge piping, this evaluation is considered i
RH line was performed. This evaluation concluded that the piping can withstand the dynamic loads caused by the maximum credible air void. Due to the higher-pressure l                        rating and smaller size of the SI and CV discharge piping, this evaluation is considered i
bounding for the ECCS subsystems. The results of the evaluation were submitted for staff review in a letter dated March 12,1990, in support of Amendments 47 and 36 to the Operating Licenses for Byron and Braidwood, respectively. The proposed changes will not result in new failure modes because no new equipment is installed, and installed equipment is not operated in a new or different manner. Manual venting operations have been performed as permitted by system operation and piping configuration. This venting surveillance does not apply to subsystems in communication with operating systems                      ,
bounding for the ECCS subsystems. The results of the evaluation were submitted for staff review in a {{letter dated|date=March 12, 1990|text=letter dated March 12,1990}}, in support of Amendments 47 and 36 to the Operating Licenses for Byron and Braidwood, respectively. The proposed changes will not result in new failure modes because no new equipment is installed, and installed equipment is not operated in a new or different manner. Manual venting operations have been performed as permitted by system operation and piping configuration. This venting surveillance does not apply to subsystems in communication with operating systems                      ,
because the flows and/or pressures prevalent in these systems are suflicient to provide                j confidence that water hammer which could occur from voiding would not result in unacceptable dynamic loads from water hammer will not occur. Accordingly, this change                  i will not create the possibility of a new or different kind of accident.
because the flows and/or pressures prevalent in these systems are suflicient to provide                j confidence that water hammer which could occur from voiding would not result in unacceptable dynamic loads from water hammer will not occur. Accordingly, this change                  i will not create the possibility of a new or different kind of accident.
j l
j l

Latest revision as of 10:07, 12 December 2021

Proposed Tech Specs Revising TS Surveillance Requirement 4.5.2.b to Encompass non-operating ECCS Pumps & Discharge Piping Which Are Provided W/High Point Vent Valves
ML20141K899
Person / Time
Site: Byron, Braidwood  Constellation icon.png
Issue date: 05/24/1997
From:
COMMONWEALTH EDISON CO.
To:
Shared Package
ML20141K898 List:
References
NUDOCS 9706020066
Download: ML20141K899 (11)


Text

_ . . _ _ _ _ . . _ _ _ _ _ _ . . - . _ . _ . _ _ _ _ .__ _ _ _ _

+

l l, 9.

4

,- EMERGENCY CORE C0OLING SYSTEMS SURVEILLANCE REQUIREMENTS

4.5.2 Each ECCS subsystem shall be demonstrated OPERABLE

! a. At least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> by verifying that the following valves I i are in the indicated positions with power to the valve operators removed:

Valve Number Valve Function Valve Position MOV SI8806 Suction to the SI Open Pumps MOV SI8835 SI Pump Discharge Open*

To RCS Cold Legs MOV SI8813 SI Pump Recirculation Open ,

To The RWST 1 MOV SI8809A RHR Pump Discharge to Open* I RCS Cold Legs MOV SI8809B RHR Pump Discharge to Open*

RCS Cold Lg s MOV SI8840 RHR Pump Discharge to Closed RCS Hot Legs

" ~

MOV SI8802A SI Pump Discharge to Closed for Ooil I tkd4h RCS Hot Legs 6 0 "d MOV SI8802B SI Pump Dischar e to Closed Cfm t k egek 7; RCS Hot Legs l

b. /tleastonceper31daysby: (igg oal )[icable h +Ae filand SI 'ai Venting the EGGS pump singsanddschargepipinghighpoing l 66} e{es outside of containment, and
2) Verifying that each valve (manual, power-operated, or automatic) in the flow path that is not locked, sealed, or o
  • y secured in position, is in its correct positio . (@lg6 @ *'/ E
c. By a visual inspection which verifies that no loose debris ,

tra m , clothing, etc.) is present in the containment which could be transported to the containment sump and cause restriction of the pump suctions during LOCA conditions. This visual inspection shall Q erform p VenQ 4he CV' Sgsb #5 full of u>Jer h Obseasegl(g eyamni,g 4k, discLu e pb d +Le alle. CV P"~f "f> b 4ke discr<vy cLedC ,

valve ad ke Shyad Prbe^ o# +ke Ffg upsh,.i oC +ke srBsol l k ad 8 d 4k STOW Valve (oghcable -b the cV g 34em g e,1[ ),

" Valves may be realigned for testing pursuant to Specification 4.4.6.2.2.

9706020066 970524 PDR ADOCK 05000454 P PDR BYRON - UNITS 1 & 2 ~ 3/4 5-4 AMENDMENT NOS. 47 d 47-

~. - - - . - - _ . - .. - - - - .~.. - . _ .. - - _ _ - .

i

! 9 EMERGENCY CORE COOLING SYSTEMS l BASES

}

ECCS SUBSYSTEMS (Continued)

The limitation for a maximum of one centrifugal charging pump to be 1 i OPERABLE and the Surveillance Requirement to verify all charging pumps except j the required OPERA 8LE Charging pump to be inoperable in MODE 4 with one or

c re of the RCS cold legs less than or equal to 330*F, MODE 5, and MODE 6 with the reactor vessel head on, provides assurance that a mass addition pressure ,

i transient can be relieved by the operation of a single PORV or RHR suction i l- relief valve. Similarly, the requirement-to verify all Safety Injection pumps are inoperable in MODE 4 with the temperature of one or more of the RCS Cold a

< Legs less than or equal to 330*F, in MODE 5 with pressurizer level greater than j 5 percent (Level 409.5') and in MODE 6 with pressurizer level greater than

5 percent and the reactor vessel head resting on the reactor vessel flange,
provides assurance that a mass addition pressure transient can be relieved by a single PORV or RHR suction relief valve.

t l In MODE 5 and MODE 6 with pressurizer level less than or equal to 5 percent, e at least one Safety Injection pump or gravity feed from the RWST must be avail-

! able to mitigate the effects of a loss of decay heat removal during partially l drained conditions. Surveillance requirements assure availability, but prevent i inadvertent actuation during these modes. The desired flow path for the SI

( pump or gravity feed varies with RCS configuration and is, therefore, procedurally !

! addressed.

The Surveillance Requirements define what constitutes an adequate hot side i vent for various plant conditions. It was determined that removing the reactor

vessel head was an adequate vent under all conditions. Other venting alterna-1 tives have restrictions based on time from shutdown and RCS temperature. The values in the surveillance were taken from the graph on the following page.

i The Surveillance Requirements provided to ensure OPERABILITY of each l component ensures that at a minimum, the assumptions used in the safety analyses i are met and that subsystem OPERABILITY is maintained. Surveillance Requirements for throttle valve position stops and flow balance testing provide assurance that proper ECCS flows will be maintained in the event of a LOCA. Maintenance of proper flow resistance and pressure drop in the piping system to each j injection point is necessary to: (1) prevent total pump flow from exceeding runout conditions when the system is in its minimum resistance configuration,

. (2) provide the proper flow split between injection points in accordance with

the assumptions used in the ECCS-LOCA analyses, and (3) provide an acceptable i level of total ECCS flow to all injection points equal to or above that assumed
in the ECCS-LOCA analyses. The Surveillance Requirements for leakage testing i of ECCS check valves ensures that a failure of one valve will not cause an l intersystem LOCA. In Mode 3, with pressurizer pressure below 1000 psig, the 1 accumulators will be available with their isolation valves either closed but I energized, or open, whenever a SI8809 valve is closed to perform check valve j leakage testing.

/NRT f BYRON - UNITS 1 & 2 B 3/4 5-2 AMENDMENT NO.

ti

7 INSERT A For Unit I through cycle 8 and Unit 2 through cycle 7, surveillance Requirement 4.5.2.b.1 requires that the RH and SI pump casings and discharge piping high point vent valves be vented on a 31 day frequency. This venting surveillance does not apply to subsystems in communication with operating systems because the Dows and/or pressures prevalent in these systems are sufUcient to provide confidence that water hammer which could occur from voiding would not result in unacceptable dynamic loads. During shutdown cooling operation, the exclusion would apply to the operating RH pump, in addition to the ECCS piping in communication with the operating pump.

For Unit I through cycle 8 and Unit 2 through cycle 7, the TS 4.5.2.b.3 surveillance requirement to ultrasonically examine selected portions of piping involves the idle CV pump discharge piping up to the first check valve on the pump discharge and miniDow lines, and the stagnant portion of the piping upstream of the S18801 A/B adjacent to the vent valve S1045. This examination will i provide added assurance that the piping is water solid.

7

I l I

\

l +. l NITACIIMENT 11-2

{

l l MARKED UP PAGES FOR  !

j PROPOSED CliANGES TO APPENDIX A, I TECHNICAL SPECIFICATIONS, OF FACILITY OPERATING LICENSE NPF-77 BRAIDWOOD STATION UNIT 2 i REVISED PAGES:

1 4

3/4 5-4b B 3/4 5-2a 1

l 8

~ ~ ~ ~ ~Rii &Tsii~s^siHii~~ ~ ~ ' ~ ~,f.f s'.,T^n,u ^^ '. ",^{^ ~ '

^

k.biiG isciKiia ~ ~~ .

3, i EMERGENCY CDRE COOLING SYSTDts suRvr1LLANCE REDUIREMEWY1 __

4.5.2 Each ECCS subsystes shall be demonstrated OPERA 8LE:

a. At least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> by verifying that the following valves are in'the indicated positions with power to the valta operators removed:

1 N Valve Funetten Valva Petition

! MOV $!8806 suction to the SI Open Pumps MOV SI5835 31 W Discharge open*

l . To RCS Cold Legs MOV SI8813 SI pump Recirculation Open l To The RWST l MOV SI8809A RHR Pump Discharge to Open*

RCS Cold Legs MOV SIB 8098 RHR Pump Discharge to Open*

l RCS Cold Legs ggd MOV SIS 840 RHR Pump Discharge to RCS Hot Legs.

Closed MV SI8802A SI Pump Discharge to Closed l

b i l

l v%( cIc\(.b NV $188028 RCS Hot Legs SI Pump Dische ACS Hot Legs o Clas gqQs4ad %

l b. least once per 31 days by:

pc ow.\h

1) Venting th 4cCf ump ings and discharge piping high pain outside of neent, and 9eo scus
2) Verifying that each valve (manual, power-operated, or automatic) in the flow path that is not locked, sealed, or otherwise secured in position, is in its correct position.

l c. . By a visual inspection ate.) iswhich verifles in thethat no loose debris which (rans,be i present containment could trash, clothing,he transported to t containment sump and cause restriction of the gumpsuctionsd e Perfo M . , IL_71 r_apahuaynspection sh (opbcc L\R. % At CM34 od 71 h%Ei\

3h se cw +.,ua

.am;Meenu c\' %t G EEc^ N ama s c 4e S%cAS etw m mL+k*

(

ydg(o <. a9 \sestse % M OJ q ceu od h . ,

j - UNIT 3/4 5-4b _

ANENDMENT NO l M f ~ /

sm m, nu an l

I _ . _

L ^ ~rM i~u~chsius~ "~ ~ rax wo. sse sss riss es-2s-*7 2e 4e e.e, 5 EMEMEEY CRE fBOLIM SYSTS15 -

BASES - --

(

l ECCS SUBSYSTEMS (Continued)' l 1

which could result in unacceptable dynamic loadiap will not occur. Durine  !

normal operation, this exclusion would apply to t w High Head Safety Injection l subsystem. During shutdown cooling operation, the exclusion would apply to the l single re ired Centrifugal Charging p ep and operating RH pump, in addition to the ECCS ping to communication with the operating pumps. Because the centrifug charging pumps are not equipped with pap casing vent valves, and l the pap design and systes piping configuration allow the plaps to be maintained under positive pressure when in standby.. manual venting of these pumps is not required.

The surveillance requirement to ultrasonically examine selected portions of piping involves the idle CY pump discharge piping up to the first check valve on the pump discharge and miniflow lines, and the stagnant portion of the piping upstrem of the 15I8801 A/8 adjacent to the vent valve ISIO45. This will provide added assurance that the piping is water solid.

r wem-- h ,

1 4

l l

l l

(

?

l BRAIDWOOD - UNITS 1 & 2 B 3/4 5-2a AMENOMENT NO. M ,

CT AI 'd 214*04 L.LE0 :0T 266T'E2'

-- -- -~~

( .?

S.

(

I .

INSERT A For Unit 2 through cycle 6, surveillance Requirement 4.5.2.b.1 requires that the RH and SI pump casings and discharge piping high point vent valves be vented on a 31 day frequency. This venting surveillance does not apply to subsystems in communication with operating systems because the flows and/or pressures prevalent in these systems are sufficient to provide confidence that water hammer which could occur from voiding would not result in unacceptable dynamic l loads from water hammer will not occur. During shutdown cooling operation, the exclusion l would apply to the operating RH pump, in addition to the ECCS piping in communication with j the operating pump.

For Unit 2 through cycle 6, the TS 4.5.2.b.3 surveillance requirement to ultrasonically examine selected portions of piping involves the idle CV pump discharge piping up to the first check valve on the pump discharge and miniflow lines, and the stagnant portion of the piping upstream of the SI8801 A/B adjacent to the vent valve S1045. This examination will provide added assurance that the piping is water solid.

l I

l l

l l

l 9

i I

ATTACllMENT C EVALUATION OF SIGNiFICANT HAZARDS CONSIDERATIONS FOR ,

PROPOSED CHANGES TO APPENDIX A, l

TECHNICAL SPECIFICATIONS, OF l

FACILITY OPERATING LICENSES l NPF-37, NPF-66 AND NPF-77 Commonwealth Edison has evaluated this proposed amendment and determined that it involves no significant hazards considerations. According to Title 10 Code of Federal Regulations Section ,

50 Subsection 92 Paragraph c (10 CFR 50.92 (c)), a proposed amendment to an operating license involves no significant hazards considerations if operation of the facility in accordance with the l

proposed amendment would not:

1. Involve a significant increase in the probability or consequences of an accident

{

previously evaluated; or I

2. Create the possibility of a new or different kind of accident from any accident previously evaluated; or
3. Involve a significant reduction in a margin of safety.

A. INTRODUCTION Commonwealth Edison (Comed) proposes to revise Byron and Braidwood Technical I Specification (TS) 4.5.2.b. I and associated bases as they relate to the requirement to vent the Emergency Core Cooling System (ECCS) pump casings and discharge piping high points outside containment. The change will revise the venting requirement to encompass the non-operating ECCS pumps and discharge piping which are provided with high point vent valves. Those portions of the ECCS systems which are in communication with operating system pressure and/or flow will not be required to be vented This would normally encompass the High Head Safety Injection (CV) subsystem during Modes 1-4 operation, and the Low Head Safety injection Subsystem (RH) during periods when shutdown cooling is in operation. Additionally, the wording of the surveillance will be revised to clearly indicate that the installed high point vent valves and pump casing vent valves will be utilized to accomplish the venting operation. The Intermediate Head Safety Injection (SI) subsystem and the RH subsystem are equipped with pump casing vents. The centrifugal CV pumps are not equipped with pump casing vent valves due to the configuration of the suction and discharge piping. Both the suction and discharge piping enter the pump casing from the top, so the pumps are essentially self-venting. Finally, a new requirement is added to ultrasonically examine the discharge piping of the idle centrifugal pump and the podion of the piping upstream of the High Head Safety injection isolation valves 10

P 1 .

(SI8801 A and B) adjacent to the vent valve SIO45 every 31 days. These changes are required to ,

align the surveillance requirement with the physical construction of the installed piping, and accommodate operating conditions which preclude cycling the installed high point vent valves during system operation, while continuing to provide assurance that the ECCS piping remains i

water solid. These changes will be applicable only until the end of the current cycle for each unit.

l

! B. NO SIGNIFICANTIIAZARDS ANALYSIS  :

1. The proposed change does not involve a significant increase in the probability or consequences of an accident previously evaluated.

The proposed changes will align the surveillance requirements with the installed system design and normal operating conditions. No increase in the probability of an accident will occur as a result of this change. The conduct of surveillances required by the Technical Specifications is not postulated to initiate an accident. The level of surveillance performed to date has provided confidence that the objective of the current surveillance requirement has been met. As such, the proposed change does not result in a significant increase in the probability of occurrence of a previously analyzed accident.

The consequences of a previously analyzed accident are not increased. Operating experience has shown that the level of surveillance performed to date is suflicient to provide confidence that no significant voiding has occurred in the affected piping.

Ultrasonic examinations have confirmed the water solid condition of the piping. Although voiding is not expected, evaluation of postulated voided conditions confirm that unacceptable dynamic loading would not occur, and, therefore, the integrity of the ECCS l piping is not compromised. Thus, the ECCS will be capable of performing its design '

tunction of cooling the reactor core and providing shutdown capability following initiation of the certain accidents. This will ensure that the consequences of a previously analyzed j accident are not significantly increased.

Therefore, these proposed revisions do not result in a significant increase in the probability or consequences of an accident previously analyzed.

I i

11

e

2. The proposed change does not create the possibility of a new or different kind of accident from any accident previously evaluated.

The proposed changes do not create the possibility of a new or different kind of accident.

Comed has evaluated the piping configuration for the ECCS discharge piping of the ECCS subsystems. A specific engineering evaluation of both a voided 2-inch and 8-inch '

RH line was performed. This evaluation concluded that the piping can withstand the dynamic loads caused by the maximum credible air void. Due to the higher-pressure l rating and smaller size of the SI and CV discharge piping, this evaluation is considered i

bounding for the ECCS subsystems. The results of the evaluation were submitted for staff review in a letter dated March 12,1990, in support of Amendments 47 and 36 to the Operating Licenses for Byron and Braidwood, respectively. The proposed changes will not result in new failure modes because no new equipment is installed, and installed equipment is not operated in a new or different manner. Manual venting operations have been performed as permitted by system operation and piping configuration. This venting surveillance does not apply to subsystems in communication with operating systems ,

because the flows and/or pressures prevalent in these systems are suflicient to provide j confidence that water hammer which could occur from voiding would not result in unacceptable dynamic loads from water hammer will not occur. Accordingly, this change i will not create the possibility of a new or different kind of accident.

j l

3. The proposed change does not involve a significant reduction in a margin of s lety. j The margin of safety is not significantly reduced because the proposed change will provide suflicient assurance that excessive voiding will not occur. This will assure proper system functioning. Venting of the idle subsystems, in conjunction with the operating conditions of the subsystems in operation, provides confidence that voiding is not present. This has I been confirmed by the performance of ultrasonic examinations of the piping ofinterest.  ;

This meets the objective of the surveillance requirement and thus preserves the margin of j safety.

Therefore, based on the above evaluation, Comed has concluded that these changes involve no significant hazards considerations.

l l

l 12

! .. S

\

9.

j .N ATTACilMENT D i

t ENVIRONMENTAL ASSESSMENT FOR PROPOSED CHANGES TO APPENDIX A, TECHNICAL SPECIFICATIONS, OF j FACILITY OPERATING LICENSES I

NPF-37, NPF-66 AND NPF-77 l

Commonwealth Edison Company (Comed) has evaluated this proposed license amendment I request against the criteria for identification oflicensing and regulatory actions requiring environmental assessment in accordance with Title 10, Code of Federal Regulations, Part 51, Section 21 (10 CFR 51.21). Comed has determined that this proposed license amendment request meets the criteria fbr a categorical exclusion set forth in 10 CFR 51.22(c)(9). Tais determination is based upon the following

1. The proposed change involves the issuance of an amendment to a license for a reactor pursuant to 10 CFR 50 which changes a requirement with respect to installation or use of a facility component located within the restricted area, as defined in 10 CFR 20, or which changes an inspection or a surveillance requirement;
2. this proposed license amendment request involves no significant hazards considerations,
3. there is no significant change in the types or significant increase in the amounts of any ellluent that may be released offsite; and
4. there is no significant increase in individual or cumulative occupational radiatica exposure.

j Therefore, pursuant to 10 CFR 51.22(b), neither an environmental impact statement nor an environmental assessment is necessary for this license amendment request.

13 i

t