ML20086D703: Difference between revisions
StriderTol (talk | contribs) (StriderTol Bot insert) |
StriderTol (talk | contribs) (StriderTol Bot change) |
||
| Line 2: | Line 2: | ||
| number = ML20086D703 | | number = ML20086D703 | ||
| issue date = 02/24/1977 | | issue date = 02/24/1977 | ||
| title = Telecopy Ro:On 770223,while Withdrawing in-sequence Control Rod to Bring Reactor Critical,Reactor Period of Less than 5 | | title = Telecopy Ro:On 770223,while Withdrawing in-sequence Control Rod to Bring Reactor Critical,Reactor Period of Less than 5 Obtained | ||
| author name = Eliason L | | author name = Eliason L | ||
| author affiliation = NORTHERN STATES POWER CO. | | author affiliation = NORTHERN STATES POWER CO. | ||
Revision as of 06:43, 16 April 2020
Text
_ __ ,
~
BiKSRB NORYHERN STATES POWER COMPANY F0hTICEll/> h'lCLEAR GDT: RAT 1h'G PlJdG FOhTIG11/), FrIhWESOTA 55362 gg
- PILE 0000, February 24, 1977 Mr. J. G. Keppler, Director Region III~
Office of Inspection and Enforcement ;
United States hbclear Regulatory Corrassion l 799 Roosevelt Road I Glen Ellyn, Illinois 60137 l
Dear Mr ~Keppler:
I FONTICELID NIELEAR GDFutATING PIN!f Docket No. 50-263 License No. DPR 22 On Febniary .25,1977, sdille withdrawing an in-sequence control rod to bring i the reactor critical, a reactor period of less than 5 seconds was obtained, '
Analyses perfonned by the NSP core analysis group shows that the corbination of high temperature and hip,h renen concentration at the time of the occurrence, established conditions such that criticality occurred on an unusually high reactivity worth control rod notch. The obsenred period was consistent with the core analysis data.
Yours very truly,
,-s .
L.'R. E11 on Plant Fhnager LRE/kik cc: Director, Office of Mwiagement Infonnstion 6 Program Control G. Charnoff '
Minnesota Pollution Control Agency l Attn: J. W. Ferman !
File Copy sent to telecopier to Mr. Keppjer.
.v 8312020461 780426 - ,, . - : . . ~ . . ,
. , a c;. . . . t., , . ,, . -s,..,..m..m.....,,w..,.._,...
__ . u