ML18130A746: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
Line 3: Line 3:
| issue date = 05/10/2018
| issue date = 05/10/2018
| title = LAR to Relocate PT Limits Curves to PTLR - Draft Supplemental Information Needed
| title = LAR to Relocate PT Limits Curves to PTLR - Draft Supplemental Information Needed
| author name = Galvin D J
| author name = Galvin D
| author affiliation = NRC/NRR/DORL/LPLII-2
| author affiliation = NRC/NRR/DORL/LPLII-2
| addressee name = Grzeck L
| addressee name = Grzeck L

Revision as of 07:03, 17 June 2019

LAR to Relocate PT Limits Curves to PTLR - Draft Supplemental Information Needed
ML18130A746
Person / Time
Site: Brunswick  Duke Energy icon.png
Issue date: 05/10/2018
From: Dennis Galvin
Plant Licensing Branch II
To: Grzeck L
Duke Energy Carolinas
References
L 2018-LLA-0094
Download: ML18130A746 (4)


Text

DRAFT SUPPLEMENTAL INFORMATION NEEDED AMENDMENT REQUEST TO REVISE THE TECHNICAL SPECIFICATIONS TO RELOCATE THE PRESSURE-TEMPERATURE LIMIT CURVES TO A PRESSURE AND TEMPERATURE LIMITS REPORT DUKE ENERGY PROGRESS, LLC BRUNSWICK STEAM ELECTRIC PLANT, UNITS 1 AND 2 DOCKET NO. 50-324 By letter dated April 4, 2018 (Agencywide Document Access and Management System (ADAMS) Accession No. ML18094B058), Duke Energy Progress, LLC (Duke Energy) submitted a license amendment request (LAR) for Brunswick Steam Electric Plant, Unit Nos. 1 and 2 (Brunswick). The proposed amendment to the Brunswick Technical Specifications (TSs) would revise and relocate the Pressure Temperature Limit Curves to a licensee-controlled Pressure and Temperature Limits Report (PTLR). The request was submitted in accordance with guidance provided in U.S. Nuclear Regulatory Commission (NRC) Generic Letter (GL) 96-03, "Relocation of the Pressure Temperature Limit Curves and Low Temperature Overpressure Protection System Limits," dated January 31, 1996.

In accordance with GL 96-03, Attachment 1, to implement a PTLR, requesting licensees are required, among other things, to propose to (1) use an NRC-approved methodology to develop the PTLR, (2) describe how the neutron fluence is calculated, and (3) provide the neutron fluence values that are used in the adjusted reference temperature calculation.

Duke Energy proposes to incorporate BWROG-TP-11-022-A, Revision 1, "Pressure Temperature Limits Report Methodology for Boiling Water Reactors," (ADAMS Accession No. ML13277A557) into the new TS Section 5.6.7, to describe the previously reviewed and approved analytical methods used to determine the PT Limits. Regarding the reactor vessel neutron fluence, Table 1-1 of BWROG-TP-11-022-A, Revision 1, states that fluence methods and results must comply with Regulatory Guide (RG) 1.190, "Calculational and Dosimetry Methods for Determining Pressure Vessel Neutron Fluence," March 2001 (ADAMS Accession No. ML010890301), and have NRC approval for use with this licensing topical report. LAR Enclosure Attachment 1, Section 3.2, "Technical Analysis," subsection titled "Neutron Fluence Calculations," explains that the fluence calculations were updated using an NRC-approved methodology in accordance with RG 1.190. However, the LAR does not indicate the method used or otherwise provide information demonstrating conformance with BWROG-TP-11-022-A, Revision 1. The neutron fluence values that are used in the adjusted reference temperature calculation are included in LAR Enclosure Attachment 1, Section 3.2.

LAR Enclosure Section 3.1 discusses the amendments (ADAMS Accession No. ML031690683), issued on June 18, 2003, that approved the current Brunswick PT Limits for 32 effective full-power years and the associated vessel fluence methodology. The proposed PTLR in LAR Enclosure Attachment 6, in Section 3.0 "Methodology," indicates that the neutron fluence is calculated in accordance with RG 1.190 as documented in Westinghouse Report, WCAP-17660-NP, Revision 0, "Neutron Exposure Evaluations for Core Shroud and Pressure Vessel Brunswick Units 1 and 2," November 2012. However, WCAP-17660-NP has not been submitted to the NRC.

The LAR does not clearly identify what NRC-approved neutron fluence methodology will be used with the PTLR in accordance with GL 96-03 and BWROG-TP-11-022-A, Revision 1. The LAR does not describe how the neutron fluence is calculated in accordance with GL 96-03. Duke Energy is requested to submit WCAP-17660-NP, or otherwise provide information that identifies the NRC-approved neutron fluence methodology used to develop the PTLR and that fully describes how the neutron fluence is calculated in accordance with RG 1.190.