{{#Wiki_filter:JOB PERFORMANCE MEASURE JPM-#-   ANO-2-JPM-NRC-AACSU REV. 01   PAGE   1   of   1 1 SYSTEM/DUTY AREA:
{{#Wiki_filter:JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU                           REV.       01                               PAGE 1 of 11 SYSTEM/DUTY AREA: Emergency Diesel Generator System TASK: Start up the AAC diesel generator manually locally JTA #: 206450201A4 KA VALUE         RO:       4.0           SRO:       4.3           KA  
Emergency Diesel Generator System TASK:   Start up the AAC diesel generator manually locally
 
JTA #:   206450201A4 KA VALUE RO:         4.0 SRO:         4.3 KA  


==REFERENCE:==
==REFERENCE:==
 
064 A4.01 APPROVED FOR ADMINISTRATION TO: RO:                 X       SRO:     X TASK LOCATION:             INSIDE CR:               OUTSIDE CR:       X       BOTH:
064 A4.01
SUGGESTED TESTING ENVIRONMENT AND METHOD                     (PERFORM OR SIMULATE):
 
PLANT SITE:       Simulate       SIMULATOR:                         LAB:
APPROVED FOR ADMINISTRATION TO:
POSITION EVALUATED:                 RO:                       SRO:
RO:         X SRO:         X TASK LOCATION:
ACTUAL TESTING ENVIRONMENT:               SIMULATOR:                 PLANT SITE:         X       LAB:
INSIDE CR:
TESTING METHOD:                     SIMULATE:         X                       PERFORM:
 
APPROXIMATE COMPLETION TIME IN MINUTES: 28 minutes REFERENCE(S): OP 2104.037 Rev 004-04-0 EXAMINEES NAME:                                                       SSN:                       -         -
OUTSIDE CR:
EVALUATORS NAME:                                                     DATE:
X BOTH:
SUGGESTED TESTING ENVIRONMENT AND METHOD (PERFORM OR SIMULATE):
PLANT SITE:
Simulate SIMULATOR:
 
LAB:
POSITION EVALUATED:
RO:
SRO:
ACTUAL TESTING ENVIRONMENT:
SIMULATOR:
 
PLANT SITE:
X LAB:
TESTING METHOD:
SIMULATE:           X PERFORM:
APPROXIMATE COMPLETION TIME IN MINUTES:
28 minutes REFERENCE(S):
OP 2104.037 Rev 004-04-0
 
EXAMINEE'S NAME:
 
SSN:                    
                -            
  -            
 
EVALUATOR'S NAME:
 
DATE:                
 
THE EXAMINEE'S PERFORMANCE WAS EVALUATED AGAINST THE STANDARDS CONTAINED IN THIS JPM AND IS DETERMINED TO BE:
THE EXAMINEE'S PERFORMANCE WAS EVALUATED AGAINST THE STANDARDS CONTAINED IN THIS JPM AND IS DETERMINED TO BE:
SATISFACTORY:
SATISFACTORY:                                       UNSATISFACTORY:
 
UNSATISFACTORY:
 
PERFORMANCE CHECKLIST COMMENTS:
PERFORMANCE CHECKLIST COMMENTS:
__________Start Time                __________ Stop Time              __________ Total Time Signature indicates this JPM has been compared to its applicable procedure by a qualified individual (not the examinee) and is current with that revision.
SIGNED:                                                                DATE:


__________
JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU                         REV.       01                               PAGE 2 of 11 THE EXAMINER SHALL REVIEW THE FOLLOWING WITH THE EXAMINEE:
Start Time
The examiner shall review the "Briefing Checklist - System Walkthrough" portion of OP 1064.023 Attachment 6 with the examinee.
__________
JPM INITIAL TASK CONDITIONS: The following conditions exist.
Stop Time__________
Total Time Signature indicates this JPM has been compared to its applicable procedure by a qualified individual (not the examinee) and is current with that revision.
SIGNED:
DATE:               
 
JOB PERFORMANCE MEASURE JPM-#-   ANO-2-JPM-NRC-AACSU REV. 01   PAGE   2   of   1 1 THE EXAMINER SHALL REVIEW THE FOLLOWING WITH THE EXAMINEE:
The examiner shall review the "Briefing Checklist - System Walkthrough" portion of OP 1064.023 Attachment 6 with the examinee.JPM INITIAL TASK CONDITIONS:
The following conditions exist.
: 1. The unit is at full power.
: 1. The unit is at full power.
: 2. The AAC Generator is in a normal standby condition and is aligned in accordance with OP 2104.037 Attachment "A"
: 2. The AAC Generator is in a normal standby condition and is aligned in accordance with OP 2104.037 Attachment A
: 3. The system dispatcher has been contacted
: 3. The system dispatcher has been contacted
: 4. Unit 1 has been informed
: 4. Unit 1 has been informed
: 5. There are no potential grid disturbances.
: 5. There are no potential grid disturbances.
TASK STANDARD: The AAC Diesel has been manually started locally and is at 4160 V and 900 rpm with the output breaker (2A-1001) closed.
TASK PERFORMANCE AIDS: OP 2104.037 Sections 7.0 and 8.0


TASK STANDARD:
JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU                           REV.       01                               PAGE 3 of 11 INITIATING CUE:
The AAC Diesel has been manually started locally and is at 4160 V and 900 rpm with the output breaker (2A-1001) closed.
The SS/CRS directs, "Start the AAC diesel manually locally using OP 2104.037 steps 8.5 through 8.6.10 for post maintenance testing."
 
CRITICAL ELEMENTS (C): 23 START TIME:
TASK PERFORMANCE AIDS:
PERFORMANCE CHECKLIST                                     STANDARDS                         (Circle One)
OP 2104.037 Sections 7.0 and 8.0
 
JOB PERFORMANCE MEASURE JPM-#-   ANO-2-JPM-NRC-AACSU REV. 01   PAGE   3   of   1 1 INITIATING CUE:
The SS/CRS directs, "Start the AAC diesel manually locally using OP 2104.037 steps 8.5 through 8.6.10 for post maintenance testing." CRITICAL ELEMENTS (C):
23                    
 
START TIME:
 
PERFORMANCE CHECKLIST STANDARDS (Circle One)
TRANSITION NOTE:
TRANSITION NOTE:
Go to the AAC diesel generator building to the AAC diesel switchgear room 1.Verify the speed raise/lower switch in OFF.POSITIVE CUE:
Go to the AAC diesel generator building to the AAC diesel switchgear room
: 1.     Verify the speed raise/lower switch    At panel 2C440, verified the speed      N/A SAT UNSAT in OFF.                                raise/lower switch in OFF.
POSITIVE CUE:
The speed raise/lower switch is in the middle position.
The speed raise/lower switch is in the middle position.
At panel 2C440, verified the speed raise/lower switch in OFF.
: 2.      Verify the voltage raise/lower        At panel 2C440, verified the voltage    N/A SAT UNSAT switch is in OFF.                     raise/lower switch in OFF.
N/A SAT UNSAT 2.Verify the voltage raise/lower switch is in OFF.
POSITIVE CUE:
POSITIVE CUE:
The voltage raise/lower switch is in the middle position.
The voltage raise/lower switch is in the middle position.
At panel 2C440, verified the voltage raise/lower switch in OFF.
: 3.      Verify the emergency stop switch      At panel 2C440, verified the           N/A SAT UNSAT is RELEASED.                           emergency stop switch is away from the base of the collar, but still flush with the outer rim on the collar.
N/A SAT UNSAT 3.Verify the emergency stop switch is RELEASED.
POSITIVE CUE:
POSITIVE CUE:
The emergency stop switch is RELEASED or out.
The emergency stop switch is RELEASED or out.
At panel 2C440, verified the emergency stop switch is away from
: 4.      Verify the engine control switch is    At panel 2C440, verified the engine    N/A SAT UNSAT in the MIDDLE position.               control switch was in the MIDDLE position between START and STOP.
 
the base of the collar, but still flush
 
with the outer rim on the collar.
N/A SAT UNSAT 4.Verify the engine control switch is in the MIDDLE position.
POSITIVE CUE:
POSITIVE CUE:
The engine control switch is in the MIDDLE position.
The engine control switch is in the MIDDLE position.
At panel 2C440, verified the engine control switch was in the MIDDLE


position between START and
JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU                       REV.     01                             PAGE 4 of 11 PERFORMANCE CHECKLIST                                   STANDARDS                     (Circle One)
 
: 5. Verify the local/remote switch is in  At panel 2C440, verified the          N/A SAT UNSAT STANDBY.                              local/remote handswitch in STANDBY.
STOP. N/A  SAT  UNSAT JOB PERFORMANCE MEASURE JPM-#-   ANO-2-JPM-NRC-AACSU REV. 01   PAGE   4   of   1 1 PERFORMANCE CHECKLIST STANDARDS (Circle One) 5.Verify the local/remote switch is in STANDBY.POSITIVE CUE:
POSITIVE CUE:
The local/remote switch is in STANDBY At panel 2C440, verified the local/remote handswitch in
The local/remote switch is in STANDBY
 
: 6. Verify the generator heater switch    At panel 2C440, verified the           N/A SAT UNSAT is in AUTO.                           handswitch in AUTO.
STANDBY. N/A SAT UNSAT 6.Verify the generator heater switch is in AUTO.
POSITIVE CUE:                          Observed the red light on for the generator space heater.
POSITIVE CUE
The generator heater switch is in AUTO and the red light is on.
: The generator heater switch is in AUTO and the red light is on.
: 7. Verify the lube oil heater switch is  At panel 2C440, verified the lube oil  N/A SAT UNSAT in AUTO.                               heater switch in AUTO.
At panel 2C440, verified the handswitch in AUTO.
POSITIVE CUE:                         Observed red light ON for the lube oil heater.
Observed the red light on for the generator space heater.
N/A SAT UNSAT 7.Verify the lube oil heater switch is in AUTO.POSITIVE CUE:
The lube oil heater switch is in AUTO and the red light is on.
The lube oil heater switch is in AUTO and the red light is on.
At panel 2C440, verified the lube oil heater switch in AUTO.
: 8. Verify the jacket water heater        At panel 2C440, verified the jacket    N/A SAT UNSAT switch is in AUTO.                    water heater switch in AUTO.
Observed red light ON for the lube oil heater.
POSITIVE CUE:                          Observed the red light on for the jacket water heater switch.
N/A  SAT  UNSAT 8.Verify the jacket water heater switch is in AUTO.
POSITIVE CUE:
The jacket water heater switch is in AUTO and the red light is on.
The jacket water heater switch is in AUTO and the red light is on.
At panel 2C440, verified the jacket water heater switch in AUTO.
: 9. Verify the current limiter circuit    Inside panel 2C440, verified the       N/A SAT UNSAT breaker is CLOSED.                     current limiter circuit breaker handle was pointing to the right or towards the panel (2C440) door.
Observed the red light on for the jacket water heater switch.
N/A SAT UNSAT 9.Verify the current limiter circuit breaker is CLOSED.
POSITIVE CUE:
POSITIVE CUE:
The current limiter circuit breaker handle is pointing to the right or
The current limiter circuit breaker handle is pointing to the right or toward the cabinet door.


toward the cabinet door.
JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU                       REV.     01                           PAGE 5 of 11 PERFORMANCE CHECKLIST                                   STANDARDS                   (Circle One)
Inside panel 2C440, verified the current limiter circuit breaker handle
: 10. Verify the idle/rated switch is in     Inside panel 2C440, verified the    N/A SAT UNSAT RATED.                                 idle/rated switch in RATED.
 
POSITIVE CUE:
was pointing to the right or towards
 
the panel (2C440) door.
N/A  SAT  UNSAT JOB PERFORMANCE MEASURE JPM-#-   ANO-2-JPM-NRC-AACSU REV. 01   PAGE   5   of   1 1 PERFORMANCE CHECKLIST STANDARDS (Circle One) 10.Verify the idle/rated switch is in RATED.POSITIVE CUE:
The idle/rated switch is in RATED.
The idle/rated switch is in RATED.
Inside panel 2C440, verified the idle/rated switch in RATED.
: 11. Check jacket water outlet              On panel 2C442, checked that        N/A SAT UNSAT temperature (2TI-7156).               2TI-7156 indicated >90°F.
N/A SAT UNSAT 11.Check jacket water outlet temperature (2TI
OR POSITIVE CUE:                          On a local computer screen, verified T7156 indicated >90°F.
-7156).POSITIVE CUE:
2TI-7156 indicates 100°F.
2TI-7156 indicates 100
OR T7156 indicates 100°F.
°F. OR T7156 indicates 100
: 12. Check lube oil from cooler             On panel 2C442, checked that        N/A SAT UNSAT temperature.                           2TI-7122 read >70°F.
°F.On panel 2C442, checked that 2TI-7156 indicated >90
OR POSITIVE CUE:                          On a local computer screen, checked T7122 read >70°F.
°F. OR On a local computer screen, verified T7156 indicated >90
2TI-7122 reads >70°F.
°F. N/A  SAT  UNSAT 12.Check lube oil from cooler temperature.
OR T7122 reads >70°F.
POSITIVE CUE:
TRANSITION NOTE:
2TI-7122 reads >70
°F. OR T7122 reads >70
°F.On panel 2C442, checked that 2TI-7122 read >70
°F. OR On a local computer screen, checked T7122 read >70
°F. N/A  SAT  UNSAT TRANSITION NOTE:
Go to the AAC diesel generator engine room.
Go to the AAC diesel generator engine room.
13.Check engine sump oil level.
: 13. Check engine sump oil level.          Using the "Keep Warm" side of the    N/A SAT UNSAT dipstick, checked the oil level between the FULL and ADD marks.
POSITIVE CUE:
POSITIVE CUE:
Sump oil level is between ADD and FULL on the "Keep Warm" side of the dipstick.
Sump oil level is between ADD and FULL on the "Keep Warm" side of the dipstick.
NEGATIVE CUE:
NEGATIVE CUE:
Sump oil level is greater than FULL on the "Engine Running" side of
Sump oil level is greater than FULL on the "Engine Running" side of the dipstick.


the dipstick.
JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU                         REV.     01                               PAGE 6 of 11 PERFORMANCE CHECKLIST                                     STANDARDS                         (Circle One)
Using the "Keep Warm" side of the dipstick, checked the oil level
: 14. Check jacket water expansion tank     At the top of the west wall in the      N/A SAT UNSAT level.                                 engine room, observed the jacket water expansion tank level between 1/4 and 3/4 in the sight glass on the POSITIVE CUE:                         side of the tank.
 
between the FULL and ADD marks.
N/A  SAT  UNSAT JOB PERFORMANCE MEASURE JPM-#-   ANO-2-JPM-NRC-AACSU REV. 01   PAGE   6   of   1 1 PERFORMANCE CHECKLIST STANDARDS (Circle One) 14.Check jacket water expansion tank level.POSITIVE CUE:
Level is 1/2 in sight glass.
Level is 1/2 in sight glass.
At the top of the west wall in the engine room, observed the jacket
: 15. Check fuel oil day tank level.        On 2LI-7201A, verified the fuel oil      N/A SAT UNSAT day tank level reads between 40 -
 
80%.
water expansion tank level between
 
1/4 and 3/4 in the sight glass on the
 
side of the tank.
N/A SAT UNSAT 15.Check fuel oil day tank level.
POSITIVE CUE:
POSITIVE CUE:
2LI-7201A, 2LI-7201B, and L7201 on the PLC read 60%.
OR 2LI-7201A, 2LI-7201B, and L7201 On 2LI-7201B verified the fuel oil on the PLC read 60%.
On 2LI-7201A, verified the fuel oil day tank level reads between 40 -
day tank level reads between 40 -
 
84%.
80%. OR On 2LI-7201B verified the fuel oil day tank level reads between 40 -
OR On the PLC for L7201, verified the fuel oil day tank level reads between 40 - 80%.
 
: 16. Check the manual jacking gear         Observed the east/west position of      N/A SAT UNSAT eccentric disengaged.                 the engagement shaft to be fully to the west (hex on the west end of the shaft sticking out of the housing)
84%. OR On the PLC for L7201, verified the fuel oil day tank level reads between
 
40 - 80%. N/A  SAT  UNSAT 16.Check the manual jacking gear eccentric disengaged.
POSITIVE CUE:
POSITIVE CUE:
The hex on the west end of the engagement shaft is sticking out
OR The hex on the west end of the Observed the gear on the east end engagement shaft is sticking out of the engagement shaft to be NOT of the housing engaged in the engine flywheel.
OR the gear on the east end of the engagement shaft is observed to NOT be engaged in the engine flywheel.
: 17. Check generator bearing oil levels. Checked the oil level in the inboard    N/A SAT UNSAT generator bearing oil sump at 1/4 to 3/4 in the bulls eye on the south POSITIVE CUE:                          side of the bearing.
The oil level in the bulls eye on the inboard and outboard generator Checked the oil level in the bearing oil sumps are 1/2 full.
outboard generator bearing oil sump at 1/4 to 3/4 in the bulls eye on the south side of the bearing.
EXAMINERS NOTE:
The manual operating shaft for the overspeed air damper protrudes from the lower left of the west side of the


of the housing OR the gear on the east end of the engagement shaft is observed to
JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU                          REV.      01                              PAGE 7 of 11 PERFORMANCE CHECKLIST                                    STANDARDS                      (Circle One) damper assembly.
 
: 18. Check the position of the             Observed the overspeed air damper      N/A SAT UNSAT overspeed air damper.                 pointer on the manual operating shaft indicating OPEN.
NOT be engaged in the engine flywheel.Observed the east/west position of the engagement shaft to be fully to
 
the west (hex on the west end of the
 
shaft sticking out of the housing)
OR Observed the gear on the east end of the engagement shaft to be NOT engaged in the engine flywheel.
N/A SAT UNSAT 17.Check generator bearing oil levels.
POSITIVE CUE:
POSITIVE CUE:
The oil level in the bulls eye on the inboard and outboard generator
The overspeed air damper pointer indicates open.
 
: 19. Check air start motor oiler oil       At the air start motor oilers,          N/A SAT UNSAT levels.                               observed oil level visible in the sight glass.
bearing oil sumps are 1/2 full.
Checked the oil level in the inboard generator bearing oil sump at 1/4 to
 
3/4 in the bulls eye on the south
 
side of the bearing.
Checked the oil level in the outboard generator bearing oil sump
 
at 1/4 to 3/4 in the bulls eye on the
 
south side of the bearing.
N/A SAT UNSAT EXAMINER'S NOTE:
The manual operating shaft for the overspeed air damper protrudes from the lower left of the west side of the JOB PERFORMANCE MEASURE JPM-#-  ANO-2-JPM-NRC-AACSU REV. 01  PAGE    7  of  1 1 PERFORMANCE CHECKLIST STANDARDS (Circle One) damper assembly.
18.Check the position of the overspeed air damper.
POSITIVE CUE:
POSITIVE CUE:
The overspeed air damper pointer indicates open.
Oil level indicated in oiler sight glass.
Observed the overspeed air damper pointer on the manual operating
: 20. Check governor hydraulic fluid         Locally, observed governor             N/A SAT UNSAT level.                                hydraulic fluid level at 1/2 in sight glass.
 
shaft indicating OPEN.
N/A  SAT  UNSAT 19.Check air start motor oiler oil levels.POSITIVE CUE:
Oil level indicated in oiler sight glass.At the air start motor oilers, observed oil level visible in the
 
sight glass.
N/A  SAT  UNSAT 20.Check governor hydraulic fluid level.POSITIVE CUE:
1/2 oil level indicated in sight glass.Locally, observed governor hydraulic fluid level at  
³ 1/2 in sight glass. N/A  SAT  UNSAT TRANSITION NOTE:
Go to the AAC diesel switchgear room 21.Verify 4160V breakers 2A901, 2A902, 2A903, and 2A904 are
 
open.POSITIVE CUE:
The PLC 4160 V Breakers screen indicates green for 2A901, 2A902, 2A903, and 2A904.
At the local AAC computer, selected "ELECTRICAL BUS
 
CONTROL"Selected "4160V BREAKERS"
 
Observed green open indications for 4160V breakers 2A901, 2A902, 2A903, and 2A904.
N/A  SAT  UNSAT JOB PERFORMANCE MEASURE JPM-#-  ANO-2-JPM-NRC-AACSU REV. 01  PAGE    8  of  1 1 PERFORMANCE CHECKLIST STANDARDS (Circle One) 22.Check "start constraints" clear.
POSITIVE CUE:
POSITIVE CUE:
Green lights lit for:-  " LOCAL/REMOTE SWITCH IN STANDBY
1/2 oil level indicated in sight glass.
"-  " FUEL SOLENOID OPEN
TRANSITION NOTE:
", and-  " PRE-LUBE LEVEL OK
Go to the AAC diesel switchgear room
".At the local AAC computer, selected "ENGINE START/STOP" Selected "START SCREEN"
: 21. Verify 4160V breakers 2A901,          At the local AAC computer,             N/A SAT UNSAT 2A902, 2A903, and 2A904 are            selected ELECTRICAL BUS open.                                  CONTROL POSITIVE CUE:                          Selected 4160V BREAKERS The PLC 4160 V Breakers screen indicates green for 2A901, 2A902, Observed green open indications 2A903, and 2A904.
for 4160V breakers 2A901, 2A902, 2A903, and 2A904.


Observed green lights lit for:- " KEY SWITCH IN STANDBY
JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU                      REV.      01                            PAGE 8 of 11 PERFORMANCE CHECKLIST                                  STANDARDS                    (Circle One)
"- " FUEL SOLENOID OPEN
: 22. Check start constraints clear.      At the local AAC computer,          N/A SAT UNSAT selected ENGINE START/STOP POSITIVE CUE:
", and- " PRE-LUBE LEVEL OK
Selected START SCREEN Green lights lit for:
". N/A  SAT  UNSAT (C)23.Start the engine.
              - "LOCAL/REMOTE SWITCH IN STANDBY"                      Observed green lights lit for:
POSITIVE CUE:
              - "FUEL SOLENOID OPEN",              - "KEY SWITCH IN STANDBY" and
                                                    - "FUEL SOLENOID OPEN", and
              - "PRE-LUBE LEVEL OK".
                                                    - "PRE-LUBE LEVEL OK".
(C) 23. Start the engine.                     At the local AAC computer on the    N/A SAT UNSAT START screen touched the START button, and observed engine speed POSITIVE CUE:                         and voltage at normal values.
Engine starts and accelerates to 900 rpm and 4160V.
Engine starts and accelerates to 900 rpm and 4160V.
NEGATIVE CUE:
NEGATIVE CUE:
Engine rolls but shuts down.
Engine rolls but shuts down.
At the local AAC computer on the START screen touched the START
: 24. Verify the generator output            On the local AAC computer or on      N/A SAT UNSAT breaker closed.                        2C-442, verified engine speed at 900 rpm and machine voltage at 4160V.
 
THEN POSITIVE CUES:
button, and observed engine speed
            - Engine at 900 rpm and 4160V.
Selected ELECTRICAL BUS
            - 2A1001 indicates red on the 480V CONTROL BREAKERS screen,
            - the building lights dimmed momentarily,                        Selected 480 V BREAKERS
            - breaker indication at the breaker cubicle is red and white lights on Observed the local AAC computer and green light off.
480V BREAKERS screen shows
            - Audible indication of the breaker    2A1001 red.
closing.


and voltage at normal values.
JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU                 REV.     01                         PAGE 9 of 11 PERFORMANCE CHECKLIST                           STANDARDS                 (Circle One)
N/A  SAT  UNSAT 24.Verify the generator output breaker closed.
: 25. Verify 2B16B1 closed.            On the local AAC computer at the N/A SAT UNSAT 480V BREAKER screen checked breaker 2B16B1 indicates red.
POSITIVE CUES:- Engine at 900 rpm and 4160V.- 2A1001 indicates red on the 480V BREAKERS screen,- the building lights dimmed momentarily,- breaker indication at the breaker cubicle is red and white lights on and green light off.- Audible indication of the breaker closing.On the local AAC computer or on 2C-442, verified engine speed at 900
 
rpm and machine voltage at 4160V.
THEN Selected "ELECTRICAL BUS CONTROL"Selected "480 V BREAKERS"
 
Observed the local AAC computer "480V BREAKERS" screen shows
 
2A1001 red.
N/A  SAT  UNSAT JOB PERFORMANCE MEASURE JPM-#-   ANO-2-JPM-NRC-AACSU REV. 01   PAGE   9   of   1 1 PERFORMANCE CHECKLIST STANDARDS (Circle One) 25.Verify 2B16B1 closed.
POSITIVE CUE:
POSITIVE CUE:
On the "480V BREAKER" screen, 2B16B1 indicates red; On the local AAC computer at the "480V BREAKER" screen checked breaker 2B16B1 indicates red.
On the 480V BREAKER screen, 2B16B1 indicates red;
N/A SAT UNSAT 26.Verify 2B16A1 open.
: 26. Verify 2B16A1 open.              On the local AAC computer 480V N/A SAT UNSAT BREAKER screen checked breaker 2B16A1 indicates green.
POSITIVE CUE:
POSITIVE CUE:
On the "480V BREAKER" screen, 2B16A1 indicates green; On the local AAC computer "480V BREAKER" screen checked breaker 2B16A1 indicates green.
On the 480V BREAKER screen, 2B16A1 indicates green; END STOP TIME:
N/A  SAT  UNSAT END STOP TIME:
 
JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU      REV. 01        PAGE 10 of 11 QUESTION ANSWER


JOB PERFORMANCE MEASURE JPM-#-   ANO-2-JPM-NRC-AACSU REV. 01   PAGE   10  of   1 1 QUESTION ANSWER JOB PERFORMANCE MEASURE JPM-#-  ANO-2-JPM-NRC-AACSU REV. 01  PAGE    11   of  1 1 EXAMINEE'S COPY JPM INITIAL TASK CONDITIONS:
JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU                           REV.       01                               PAGE 11 of 11 EXAMINEES COPY JPM INITIAL TASK CONDITIONS:
: 1. The unit is at full power.
: 1. The unit is at full power.
: 2. The AAC Generator is in a normal standby condition and is aligned in accordance with OP 2104.037 Attachment "A"
: 2. The AAC Generator is in a normal standby condition and is aligned in accordance with OP 2104.037 Attachment A
: 3. The system dispatcher has been contacted
: 3. The system dispatcher has been contacted
: 4. Unit 1 has been informed
: 4. Unit 1 has been informed

Latest revision as of 06:44, 24 November 2019

Init EXAM-4-2000-Draft JPM Aacsu - Su Aacg Locally Manually
ML003716750
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 04/24/2000
From:
NRC Region 4
To:
References
-RFPFR
Download: ML003716750 (11)


Text

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU REV. 01 PAGE 1 of 11 SYSTEM/DUTY AREA: Emergency Diesel Generator System TASK: Start up the AAC diesel generator manually locally JTA #: 206450201A4 KA VALUE RO: 4.0 SRO: 4.3 KA

REFERENCE:

064 A4.01 APPROVED FOR ADMINISTRATION TO: RO: X SRO: X TASK LOCATION: INSIDE CR: OUTSIDE CR: X BOTH:

SUGGESTED TESTING ENVIRONMENT AND METHOD (PERFORM OR SIMULATE):

PLANT SITE: Simulate SIMULATOR: LAB:

POSITION EVALUATED: RO: SRO:

ACTUAL TESTING ENVIRONMENT: SIMULATOR: PLANT SITE: X LAB:

TESTING METHOD: SIMULATE: X PERFORM:

APPROXIMATE COMPLETION TIME IN MINUTES: 28 minutes REFERENCE(S): OP 2104.037 Rev 004-04-0 EXAMINEES NAME: SSN: - -

EVALUATORS NAME: DATE:

THE EXAMINEE'S PERFORMANCE WAS EVALUATED AGAINST THE STANDARDS CONTAINED IN THIS JPM AND IS DETERMINED TO BE:

SATISFACTORY: UNSATISFACTORY:

PERFORMANCE CHECKLIST COMMENTS:

__________Start Time __________ Stop Time __________ Total Time Signature indicates this JPM has been compared to its applicable procedure by a qualified individual (not the examinee) and is current with that revision.

SIGNED: DATE:

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU REV. 01 PAGE 2 of 11 THE EXAMINER SHALL REVIEW THE FOLLOWING WITH THE EXAMINEE:

The examiner shall review the "Briefing Checklist - System Walkthrough" portion of OP 1064.023 Attachment 6 with the examinee.

JPM INITIAL TASK CONDITIONS: The following conditions exist.

1. The unit is at full power.
2. The AAC Generator is in a normal standby condition and is aligned in accordance with OP 2104.037 Attachment A
3. The system dispatcher has been contacted
4. Unit 1 has been informed
5. There are no potential grid disturbances.

TASK STANDARD: The AAC Diesel has been manually started locally and is at 4160 V and 900 rpm with the output breaker (2A-1001) closed.

TASK PERFORMANCE AIDS: OP 2104.037 Sections 7.0 and 8.0

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU REV. 01 PAGE 3 of 11 INITIATING CUE:

The SS/CRS directs, "Start the AAC diesel manually locally using OP 2104.037 steps 8.5 through 8.6.10 for post maintenance testing."

CRITICAL ELEMENTS (C): 23 START TIME:

PERFORMANCE CHECKLIST STANDARDS (Circle One)

TRANSITION NOTE:

Go to the AAC diesel generator building to the AAC diesel switchgear room

1. Verify the speed raise/lower switch At panel 2C440, verified the speed N/A SAT UNSAT in OFF. raise/lower switch in OFF.

POSITIVE CUE:

The speed raise/lower switch is in the middle position.

2. Verify the voltage raise/lower At panel 2C440, verified the voltage N/A SAT UNSAT switch is in OFF. raise/lower switch in OFF.

POSITIVE CUE:

The voltage raise/lower switch is in the middle position.

3. Verify the emergency stop switch At panel 2C440, verified the N/A SAT UNSAT is RELEASED. emergency stop switch is away from the base of the collar, but still flush with the outer rim on the collar.

POSITIVE CUE:

The emergency stop switch is RELEASED or out.

4. Verify the engine control switch is At panel 2C440, verified the engine N/A SAT UNSAT in the MIDDLE position. control switch was in the MIDDLE position between START and STOP.

POSITIVE CUE:

The engine control switch is in the MIDDLE position.

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU REV. 01 PAGE 4 of 11 PERFORMANCE CHECKLIST STANDARDS (Circle One)

5. Verify the local/remote switch is in At panel 2C440, verified the N/A SAT UNSAT STANDBY. local/remote handswitch in STANDBY.

POSITIVE CUE:

The local/remote switch is in STANDBY

6. Verify the generator heater switch At panel 2C440, verified the N/A SAT UNSAT is in AUTO. handswitch in AUTO.

POSITIVE CUE: Observed the red light on for the generator space heater.

The generator heater switch is in AUTO and the red light is on.

7. Verify the lube oil heater switch is At panel 2C440, verified the lube oil N/A SAT UNSAT in AUTO. heater switch in AUTO.

POSITIVE CUE: Observed red light ON for the lube oil heater.

The lube oil heater switch is in AUTO and the red light is on.

8. Verify the jacket water heater At panel 2C440, verified the jacket N/A SAT UNSAT switch is in AUTO. water heater switch in AUTO.

POSITIVE CUE: Observed the red light on for the jacket water heater switch.

The jacket water heater switch is in AUTO and the red light is on.

9. Verify the current limiter circuit Inside panel 2C440, verified the N/A SAT UNSAT breaker is CLOSED. current limiter circuit breaker handle was pointing to the right or towards the panel (2C440) door.

POSITIVE CUE:

The current limiter circuit breaker handle is pointing to the right or toward the cabinet door.

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU REV. 01 PAGE 5 of 11 PERFORMANCE CHECKLIST STANDARDS (Circle One)

10. Verify the idle/rated switch is in Inside panel 2C440, verified the N/A SAT UNSAT RATED. idle/rated switch in RATED.

POSITIVE CUE:

The idle/rated switch is in RATED.

11. Check jacket water outlet On panel 2C442, checked that N/A SAT UNSAT temperature (2TI-7156). 2TI-7156 indicated >90°F.

OR POSITIVE CUE: On a local computer screen, verified T7156 indicated >90°F.

2TI-7156 indicates 100°F.

OR T7156 indicates 100°F.

12. Check lube oil from cooler On panel 2C442, checked that N/A SAT UNSAT temperature. 2TI-7122 read >70°F.

OR POSITIVE CUE: On a local computer screen, checked T7122 read >70°F.

2TI-7122 reads >70°F.

OR T7122 reads >70°F.

TRANSITION NOTE:

Go to the AAC diesel generator engine room.

13. Check engine sump oil level. Using the "Keep Warm" side of the N/A SAT UNSAT dipstick, checked the oil level between the FULL and ADD marks.

POSITIVE CUE:

Sump oil level is between ADD and FULL on the "Keep Warm" side of the dipstick.

NEGATIVE CUE:

Sump oil level is greater than FULL on the "Engine Running" side of the dipstick.

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU REV. 01 PAGE 6 of 11 PERFORMANCE CHECKLIST STANDARDS (Circle One)

14. Check jacket water expansion tank At the top of the west wall in the N/A SAT UNSAT level. engine room, observed the jacket water expansion tank level between 1/4 and 3/4 in the sight glass on the POSITIVE CUE: side of the tank.

Level is 1/2 in sight glass.

15. Check fuel oil day tank level. On 2LI-7201A, verified the fuel oil N/A SAT UNSAT day tank level reads between 40 -

80%.

POSITIVE CUE:

OR 2LI-7201A, 2LI-7201B, and L7201 On 2LI-7201B verified the fuel oil on the PLC read 60%.

day tank level reads between 40 -

84%.

OR On the PLC for L7201, verified the fuel oil day tank level reads between 40 - 80%.

16. Check the manual jacking gear Observed the east/west position of N/A SAT UNSAT eccentric disengaged. the engagement shaft to be fully to the west (hex on the west end of the shaft sticking out of the housing)

POSITIVE CUE:

OR The hex on the west end of the Observed the gear on the east end engagement shaft is sticking out of the engagement shaft to be NOT of the housing engaged in the engine flywheel.

OR the gear on the east end of the engagement shaft is observed to NOT be engaged in the engine flywheel.

17. Check generator bearing oil levels. Checked the oil level in the inboard N/A SAT UNSAT generator bearing oil sump at 1/4 to 3/4 in the bulls eye on the south POSITIVE CUE: side of the bearing.

The oil level in the bulls eye on the inboard and outboard generator Checked the oil level in the bearing oil sumps are 1/2 full.

outboard generator bearing oil sump at 1/4 to 3/4 in the bulls eye on the south side of the bearing.

EXAMINERS NOTE:

The manual operating shaft for the overspeed air damper protrudes from the lower left of the west side of the

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU REV. 01 PAGE 7 of 11 PERFORMANCE CHECKLIST STANDARDS (Circle One) damper assembly.

18. Check the position of the Observed the overspeed air damper N/A SAT UNSAT overspeed air damper. pointer on the manual operating shaft indicating OPEN.

POSITIVE CUE:

The overspeed air damper pointer indicates open.

19. Check air start motor oiler oil At the air start motor oilers, N/A SAT UNSAT levels. observed oil level visible in the sight glass.

POSITIVE CUE:

Oil level indicated in oiler sight glass.

20. Check governor hydraulic fluid Locally, observed governor N/A SAT UNSAT level. hydraulic fluid level at 1/2 in sight glass.

POSITIVE CUE:

1/2 oil level indicated in sight glass.

TRANSITION NOTE:

Go to the AAC diesel switchgear room

21. Verify 4160V breakers 2A901, At the local AAC computer, N/A SAT UNSAT 2A902, 2A903, and 2A904 are selected ELECTRICAL BUS open. CONTROL POSITIVE CUE: Selected 4160V BREAKERS The PLC 4160 V Breakers screen indicates green for 2A901, 2A902, Observed green open indications 2A903, and 2A904.

for 4160V breakers 2A901, 2A902, 2A903, and 2A904.

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU REV. 01 PAGE 8 of 11 PERFORMANCE CHECKLIST STANDARDS (Circle One)

22. Check start constraints clear. At the local AAC computer, N/A SAT UNSAT selected ENGINE START/STOP POSITIVE CUE:

Selected START SCREEN Green lights lit for:

- "LOCAL/REMOTE SWITCH IN STANDBY" Observed green lights lit for:

- "FUEL SOLENOID OPEN", - "KEY SWITCH IN STANDBY" and

- "FUEL SOLENOID OPEN", and

- "PRE-LUBE LEVEL OK".

- "PRE-LUBE LEVEL OK".

(C) 23. Start the engine. At the local AAC computer on the N/A SAT UNSAT START screen touched the START button, and observed engine speed POSITIVE CUE: and voltage at normal values.

Engine starts and accelerates to 900 rpm and 4160V.

NEGATIVE CUE:

Engine rolls but shuts down.

24. Verify the generator output On the local AAC computer or on N/A SAT UNSAT breaker closed. 2C-442, verified engine speed at 900 rpm and machine voltage at 4160V.

THEN POSITIVE CUES:

- Engine at 900 rpm and 4160V.

Selected ELECTRICAL BUS

- 2A1001 indicates red on the 480V CONTROL BREAKERS screen,

- the building lights dimmed momentarily, Selected 480 V BREAKERS

- breaker indication at the breaker cubicle is red and white lights on Observed the local AAC computer and green light off.

480V BREAKERS screen shows

- Audible indication of the breaker 2A1001 red.

closing.

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU REV. 01 PAGE 9 of 11 PERFORMANCE CHECKLIST STANDARDS (Circle One)

25. Verify 2B16B1 closed. On the local AAC computer at the N/A SAT UNSAT 480V BREAKER screen checked breaker 2B16B1 indicates red.

POSITIVE CUE:

On the 480V BREAKER screen, 2B16B1 indicates red;

26. Verify 2B16A1 open. On the local AAC computer 480V N/A SAT UNSAT BREAKER screen checked breaker 2B16A1 indicates green.

POSITIVE CUE:

On the 480V BREAKER screen, 2B16A1 indicates green; END STOP TIME:

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU REV. 01 PAGE 10 of 11 QUESTION ANSWER

JOB PERFORMANCE MEASURE JPM-#- ANO-2-JPM-NRC-AACSU REV. 01 PAGE 11 of 11 EXAMINEES COPY JPM INITIAL TASK CONDITIONS:

1. The unit is at full power.
2. The AAC Generator is in a normal standby condition and is aligned in accordance with OP 2104.037 Attachment A
3. The system dispatcher has been contacted
4. Unit 1 has been informed
5. There are no potential grid disturbances.

INITIATING CUE:

The SS/CRS directs, "Start the AAC diesel manually locally using OP 2104.037 steps 8.5 through 8.6.10 for post maintenance testing."