ML19351D622: Difference between revisions
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
StriderTol (talk | contribs) (StriderTol Bot change) |
||
(One intermediate revision by the same user not shown) | |||
Line 18: | Line 18: | ||
=Text= | =Text= | ||
{{#Wiki_filter:-_ _ _ . . _ _ _ _ .__ . _ _ .. _ _ _ _ _ _ . _ | {{#Wiki_filter:-_ _ _ . . _ _ _ _ .__ . _ _ .. _ _ _ _ _ _ . _ | ||
i i O INSTRUMENTATION i | |||
l FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION i | |||
i i O | |||
INSTRUMENTATION i | |||
l FIRE DETECTION INSTRUMENTATION | |||
LIMITING CONDITION FOR OPERATION i | |||
3.3.3.8 As a minimum, the fire detection instrumentation for each fire | 3.3.3.8 As a minimum, the fire detection instrumentation for each fire | ||
. detection zone shown in Table 3.3-14 shall be OPERABLE. | . detection zone shown in Table 3.3-14 shall be OPERABLE. | ||
j APPLICABILITY: Whenever equipment in that fire detection zone is required to be OPERABLE. | j APPLICABILITY: Whenever equipment in that fire detection zone is required to be OPERABLE. | ||
1 I ACTION: With the number of OPERABLE fire detection instrument (s) less than j the minimum number OPERABLE requirement of Table 3.3-14: | 1 I ACTION: With the number of OPERABLE fire detection instrument (s) less than j the minimum number OPERABLE requirement of Table 3.3-14: | ||
: a. Within 1 hour establish a fire watch patrol to inspect the | : a. Within 1 hour establish a fire watch patrol to inspect the | ||
; accessible zone (s) with the inoperable instrument (s) at least | ; accessible zone (s) with the inoperable instrument (s) at least once per hour, and i | ||
once per hour, and i | |||
l- b. Restore the inoperable instrument (s) to OPERABLE status within L 14 days or, in lieu of any other report required by Specifi- | l- b. Restore the inoperable instrument (s) to OPERABLE status within L 14 days or, in lieu of any other report required by Specifi- | ||
; cation 6.9.1, prepare and submit a Special Report to the 4 | ; cation 6.9.1, prepare and submit a Special Report to the 4 | ||
Line 46: | Line 36: | ||
4.3.3.8.1 Each of the above required accessible fire detection instruments | 4.3.3.8.1 Each of the above required accessible fire detection instruments | ||
, shall be demonstrated OPERABLE at least once per 6 months by performance 2 | , shall be demonstrated OPERABLE at least once per 6 months by performance 2 | ||
of a CHANNEL. FUNCTIONAL TEST. Each of the above required inaccessible | of a CHANNEL. FUNCTIONAL TEST. Each of the above required inaccessible fire detection instrument shall be demonstrated OPERABLE at len.,e once i | ||
fire detection instrument shall be demonstrated OPERABLE at len.,e once i | |||
per 18 months by performance of a CllANNEL FUNCTIONAL TEST. | per 18 months by performance of a CllANNEL FUNCTIONAL TEST. | ||
l 4 | l 4 | ||
'4.3.3.8.2 The NFPA Code 72D Class A supervised circuits supervision | '4.3.3.8.2 The NFPA Code 72D Class A supervised circuits supervision associated with the detector alarms of each of the above required fire | ||
associated with the detector alarms of each of the above required fire | |||
; detection instruments shall be demonstrated OPERABLE at lease once per , | ; detection instruments shall be demonstrated OPERABLE at lease once per , | ||
1 6 months. l I | 1 6 months. l I | ||
Line 60: | Line 45: | ||
; Specification 4.3.3.8.3 and the control room shall be demonstrated , | ; Specification 4.3.3.8.3 and the control room shall be demonstrated , | ||
r ' OPERABLE at least once per 31 days. ! | r ' OPERABLE at least once per 31 days. ! | ||
l | l DAVIS-BESSE, UNIT 1 3/4 3-52 Amendment No. | ||
1 8 01014Op e . . -. - ._ - .- -- - .. - -. . | |||
DAVIS-BESSE, UNIT 1 3/4 3-52 Amendment No. | |||
1 | |||
8 01014Op e . . -. - ._ - .- -- - .. - -. . | |||
Sheet 1 of 4 TABLE 3.3-14 FIRE DETECTION INSTRUMENTS INSTRUMENT LOCAFION MINIMUM INSTRUMENTS OPERABLE HEAT FLAME SMOKE | |||
Sheet 1 of 4 TABLE 3.3-14 FIRE DETECTION INSTRUMENTS | |||
INSTRUMENT LOCAFION MINIMUM INSTRUMENTS OPERABLE HEAT FLAME SMOKE | |||
: 1. Containment | : 1. Containment | ||
#a. FDZ-RCP 1 Elev. 603' 0 0 1* | #a. FDZ-RCP 1 Elev. 603' 0 0 1* | ||
#b. FDZ-RCP 2 Elev. 603' O O 1* | #b. FDZ-RCP 2 Elev. 603' O O 1* | ||
#c. FDZ-RCP 3 Elev. 603' 0 0 1* | #c. FDZ-RCP 3 Elev. 603' 0 0 1* | ||
#d. FDZ-RCP 4 Elev. 603' O O 1* | #d. FDZ-RCP 4 Elev. 603' O O 1* | ||
#e. FDZ-PZR Elev. 603' O O 1* | #e. FDZ-PZR Elev. 603' O O 1* | ||
Line 93: | Line 64: | ||
#b. FDZ-236H Elev. 774' O O 3 | #b. FDZ-236H Elev. 774' O O 3 | ||
#c. FDZ-236L Elev. 590' 0 0 9 | #c. FDZ-236L Elev. 590' 0 0 9 | ||
: 3. Auxiliary Building | : 3. Auxiliary Building | ||
: a. FDZ 402 - #1 Electrical Penetration Rm. | : a. FDZ 402 - #1 Electrical Penetration Rm. | ||
Line 116: | Line 86: | ||
,, .,c ,, - - ,,e- , , - --- n | ,, .,c ,, - - ,,e- , , - --- n | ||
. ~, > | . ~, > | ||
Sheet 2 of 4 I_'STRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE HEAT FLAME SMOKE | |||
Sheet 2 of 4 | |||
I_'STRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE HEAT FLAME SMOKE | |||
: 3. Auxiliary Building (Continued) i~ | : 3. Auxiliary Building (Continued) i~ | ||
: j. FDZ 209 - Corridor to il Mech. Pent. Rm. | : j. FDZ 209 - Corridor to il Mech. Pent. Rm. | ||
Elev. 565' O O 3 | Elev. 565' O O 3 | ||
: k. FDZ 227 - Boric Acid Evap Passageway Elev. 565' 0 0 6 | |||
: k. FDZ 227 - Boric Acid Evap Passageway | |||
Elev. 565' 0 0 6 | |||
: 1. FDZ 208 - #1 Mechanical Penetration Rm. | : 1. FDZ 208 - #1 Mechanical Penetration Rm. | ||
Elev. 565' 0 0 10 | Elev. 565' 0 0 10 | ||
Line 145: | Line 105: | ||
; Elev. 565' O O 2 | ; Elev. 565' O O 2 | ||
) t. FDZ 101 - Equipment and Pipe Tunnel l' Elev. 545' O O 1 | ) t. FDZ 101 - Equipment and Pipe Tunnel l' Elev. 545' O O 1 | ||
: u. FDZ 105 - ECCS Pump Room 1-1 Elev. 545' O 0, 4 | : u. FDZ 105 - ECCS Pump Room 1-1 Elev. 545' O 0, 4 | ||
: v. FDZ 110 - Corridor to Central Aren of j Aux Bldg. - Elev. 54C5 0 0 5 l w. FDZ 113 - Decay Heat Exchange. Pit l i Elev. 545' O O 1 l | : v. FDZ 110 - Corridor to Central Aren of j Aux Bldg. - Elev. 54C5 0 0 5 l w. FDZ 113 - Decay Heat Exchange. Pit l i Elev. 545' O O 1 l | ||
: x. FDZ 115 - ECCS Pump Room 1-2 Elev. 545' O O 2 | : x. FDZ 115 - ECCS Pump Room 1-2 Elev. 545' O O 2 | ||
: y. FDZ 124 - Clean Waste Receiver Tank Rm. 1 Elev. 545' O O 4 | : y. FDZ 124 - Clean Waste Receiver Tank Rm. 1 Elev. 545' O O 4 | ||
: 4. Auxiliary Building Fan Rooms | : 4. Auxiliary Building Fan Rooms | ||
: a. FDZ 500 - Radwaste & Fuel Handling Area and Air Supply Area - | : a. FDZ 500 - Radwaste & Fuel Handling Area and Air Supply Area - | ||
Elev. 623' O O 20 l | Elev. 623' O O 20 l | ||
: b. FDZ 501 - Radwaste Exhaust Equipment and Main Station Exhaust Fan Room Elev. 623' O 0 22 | |||
: b. FDZ 501 - Radwaste Exhaust Equipment and Main Station Exhaust Fan Room | |||
Elev. 623' O 0 22 | |||
: c. FDZ 515 - Purge and Exhaust Equipment Rm. | : c. FDZ 515 - Purge and Exhaust Equipment Rm. | ||
Elev. 623' O O 22 | Elev. 623' O O 22 | ||
: d. FDZ 516 - Non-rad Air and Exhaust Equip. | : d. FDZ 516 - Non-rad Air and Exhaust Equip. | ||
Rm. - Elev. 623' O O 5 l | Rm. - Elev. 623' O O 5 l | ||
l g- v-- y , - , - ,, . - - _ - - - - . - | l g- v-- y , - , - ,, . - - _ - - - - . - | ||
Sheet 3 of 4 INSTRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE HEAT FLAME SMOKE | |||
Sheet 3 of 4 | |||
INSTRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE HEAT FLAME SMOKE | |||
: 5. Control Room Complex l | : 5. Control Room Complex l | ||
: a. FDZ 505 - Main Control Board Cabinets 3 | : a. FDZ 505 - Main Control Board Cabinets 3 | ||
Elev. 623' O O | Elev. 623' O O | ||
: b. FDZ SOS - Control Cabinet Room Elev. 623' O O 5 | : b. FDZ SOS - Control Cabinet Room Elev. 623' O O 5 FDZ 505 - Computer Room - Elev. 623' O O 1 c. | ||
FDZ 505 - Computer Room - Elev. 623' O O 1 c. | |||
l | l | ||
: 6. Cable Spreading Room 0 0 5 | : 6. Cable Spreading Room 0 0 5 | ||
: a. FDZ 422A - Elev. 613' l | : a. FDZ 422A - Elev. 613' l | ||
l | l | ||
: 7. A/C Equipment Room | : 7. A/C Equipment Room | ||
: a. FDZ 603 - Elev. 643' O O 11 | : a. FDZ 603 - Elev. 643' O O 11 | ||
: 8. Diesel Generator Rooms | : 8. Diesel Generator Rooms | ||
**a. FDZ 318 - Diesel Generator Rm. 1-1 Elev. 585' 0 0 5 | **a. FDZ 318 - Diesel Generator Rm. 1-1 Elev. 585' 0 0 5 | ||
**b. FDZ 319 - Diesel Generator Rm. 1-2 Elev. 585' 0 0 4 | **b. FDZ 319 - Diesel Generator Rm. 1-2 Elev. 585' 0 0 4 | ||
Line 196: | Line 138: | ||
: a. ' | : a. ' | ||
FDZ 429B - Battery Room A - Elev. 603' O O 2 b. | FDZ 429B - Battery Room A - Elev. 603' O O 2 b. | ||
: 10. Component Cooling Water Pump Room 0 0 9 | : 10. Component Cooling Water Pump Room 0 0 9 | ||
: a. FDZ 328 - Elev. 585' | : a. FDZ 328 - Elev. 585' | ||
Line 202: | Line 143: | ||
: a. FDZ 237 - Auxiliary Feed Pump 1-1 O 3 Elev. 565' O | : a. FDZ 237 - Auxiliary Feed Pump 1-1 O 3 Elev. 565' O | ||
: b. FDZ 238 - Auxiliary Feed Pump 1-2 0 3 Elev. 565' 0 | : b. FDZ 238 - Auxiliary Feed Pump 1-2 0 3 Elev. 565' 0 | ||
d | |||
".* Sheet 3 of 4 MINIMUM INSTRUMENTS OPERABLE INSTRUMENT LOCATION HEAT FLAME SMOKE I | |||
".* Sheet 3 of 4 MINIMUM INSTRUMENTS OPERABLE | |||
INSTRUMENT LOCATION HEAT FLAME SMOKE I | |||
i 5. Control Room Complex l a. FDZ 505 - Main Control Board Cabinets 3 O O l | i 5. Control Room Complex l a. FDZ 505 - Main Control Board Cabinets 3 O O l | ||
Elev. 623' | Elev. 623' | ||
Line 216: | Line 151: | ||
~ | ~ | ||
c. | c. | ||
l 6. Cable Spreading Room O O 5 i a. FDZ 422A - Elev. 613' 1 | l 6. Cable Spreading Room O O 5 i a. FDZ 422A - Elev. 613' 1 | ||
i | i | ||
. 7. A/C Equipment Room | . 7. A/C Equipment Room O O 11 | ||
: a. FDZ 603 - Elev. 643' i | |||
O O 11 | i 8. Diesel Generator Rooms 4 | ||
: a. FDZ 603 - Elev. 643' | |||
**a. FDZ 318 - Diesel Generator Rm. 1-1 Elev. 585' 0 0 5 l | **a. FDZ 318 - Diesel Generator Rm. 1-1 Elev. 585' 0 0 5 l | ||
**b. FDZ 319 - Diesel Generacor Rm. 1-2 4 Eler. 585' 0 0 | **b. FDZ 319 - Diesel Generacor Rm. 1-2 4 Eler. 585' 0 0 | ||
Line 235: | Line 165: | ||
: a. FDZ 428A - Battery Room B - Elev. 603' O 0 0 2 | : a. FDZ 428A - Battery Room B - Elev. 603' O 0 0 2 | ||
: b. FDZ 429B - Battery Room A - Elev. 603' | : b. FDZ 429B - Battery Room A - Elev. 603' | ||
: 10. Component Cooling Water Pump Room 0 0 9 | : 10. Component Cooling Water Pump Room 0 0 9 | ||
: a. FDZ 328 - Elev. 585' | : a. FDZ 328 - Elev. 585' | ||
Line 241: | Line 170: | ||
: a. FDZ 237 - Auxiliary Feed Pump 1-1 0 0 3 Elev. 565' | : a. FDZ 237 - Auxiliary Feed Pump 1-1 0 0 3 Elev. 565' | ||
: b. FDZ 23f; - Auxiliary Feed Pump 1-2 0 0 3 Elev. 565' | : b. FDZ 23f; - Auxiliary Feed Pump 1-2 0 0 3 Elev. 565' | ||
- _ _ - _ _ _ _ _ = _ . - - - - . - - - - . . _ _ _ _ - _ _ _ - - - _ _ _ | - _ _ - _ _ _ _ _ = _ . - - - - . - - - - . . _ _ _ _ - _ _ _ - - - _ _ _ | ||
o s | o s | ||
Sheet 4 of 4 MINIMUM INSTRUMENTS OPERABLE INSTaUMENT LOCATION 4 | |||
Sheet 4 of 4 | |||
MINIMUM INSTRUMENTS OPERABLE | |||
INSTaUMENT LOCATION 4 | |||
HEAT _ FLAME SMOKE | HEAT _ FLAME SMOKE | ||
: 12. Switchgear Roomg | : 12. Switchgear Roomg | ||
: a. FDZ 324 - CD ~31gb Voltage Switchgear O O 3 01ev. 585' | : a. FDZ 324 - CD ~31gb Voltage Switchgear O O 3 01ev. 585' | ||
Line 263: | Line 180: | ||
Elev. 585' O | Elev. 585' O | ||
: c. FDZ 323 - B High Voltage Switchgear O O 11 | : c. FDZ 323 - B High Voltage Switchgear O O 11 | ||
. Elev. 585' | . Elev. 585' l l | ||
l l | |||
: d. FDZ 428 - F High Voltage Switchgear l O O 12 j Elev. 603' | : d. FDZ 428 - F High Voltage Switchgear l O O 12 j Elev. 603' | ||
, c. FDZ 429 - E High Voltage Switchgear 6 O O | , c. FDZ 429 - E High Voltage Switchgear 6 O O | ||
* Elev. 603' | * Elev. 603' | ||
: 13. Intake Structure | : 13. Intake Structure | ||
: a. FDZ 052 - Diesel Fire Pump Room O O 1 Elev. 576' j b. FDZ 052- Service Water Pump Room O O 3 j Elev. 576' | : a. FDZ 052 - Diesel Fire Pump Room O O 1 Elev. 576' j b. FDZ 052- Service Water Pump Room O O 3 j Elev. 576' | ||
: c. FDZ 053 - Service Water Viv. Room 0 6 Elev. 565' 0 | : c. FDZ 053 - Service Water Viv. Room 0 6 Elev. 565' 0 4 | ||
4 | |||
i J | i J | ||
i l | i l j | ||
j | |||
+ | + | ||
l l | l l | ||
1 | |||
*The fire detection instruments located within the Containment are not required to be OPERABLE during the performance of Type A Containment Leakage Rate Tests. | *The fire detection instruments located within the Containment are not required to be OPERABLE during the performance of Type A Containment Leakage Rate Tests. | ||
**These detectors automatically actuate fire suppression systems. | **These detectors automatically actuate fire suppression systems. | ||
. . . _ . ._ -. __ .._ __ __}} | . . . _ . ._ -. __ .._ __ __}} |
Latest revision as of 02:19, 18 February 2020
ML19351D622 | |
Person / Time | |
---|---|
Site: | Davis Besse |
Issue date: | 10/07/1980 |
From: | TOLEDO EDISON CO. |
To: | |
Shared Package | |
ML19351D621 | List: |
References | |
NUDOCS 8010140249 | |
Download: ML19351D622 (5) | |
Text
-_ _ _ . . _ _ _ _ .__ . _ _ .. _ _ _ _ _ _ . _
i i O INSTRUMENTATION i
l FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION i
3.3.3.8 As a minimum, the fire detection instrumentation for each fire
. detection zone shown in Table 3.3-14 shall be OPERABLE.
j APPLICABILITY: Whenever equipment in that fire detection zone is required to be OPERABLE.
1 I ACTION: With the number of OPERABLE fire detection instrument (s) less than j the minimum number OPERABLE requirement of Table 3.3-14:
- a. Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> establish a fire watch patrol to inspect the
- accessible zone (s) with the inoperable instrument (s) at least once per hour, and i
l- b. Restore the inoperable instrument (s) to OPERABLE status within L 14 days or, in lieu of any other report required by Specifi-
- cation 6.9.1, prepare and submit a Special Report to the 4
Commission pursuant to Specification 6.9.2 within the next 30 j days outlining the action taken, the cause of the inoperability 1 and the plans and schedule for restoring the instrument (s) to OPERABLE status.
]
', c. The provisions of Specifications 3.0.3 and 3.0.4 are not
! applicable.
i I
SURVEILLANCE REQUIREMENTS i
4.3.3.8.1 Each of the above required accessible fire detection instruments
, shall be demonstrated OPERABLE at least once per 6 months by performance 2
of a CHANNEL. FUNCTIONAL TEST. Each of the above required inaccessible fire detection instrument shall be demonstrated OPERABLE at len.,e once i
per 18 months by performance of a CllANNEL FUNCTIONAL TEST.
l 4
'4.3.3.8.2 The NFPA Code 72D Class A supervised circuits supervision associated with the detector alarms of each of the above required fire
- detection instruments shall be demonstrated OPERABLE at lease once per ,
1 6 months. l I
i 1 4.3.3.8.3 The non-supervised circuits between the local panels in
- Specification 4.3.3.8.3 and the control room shall be demonstrated ,
r ' OPERABLE at least once per 31 days. !
l DAVIS-BESSE, UNIT 1 3/4 3-52 Amendment No.
1 8 01014Op e . . -. - ._ - .- -- - .. - -. .
Sheet 1 of 4 TABLE 3.3-14 FIRE DETECTION INSTRUMENTS INSTRUMENT LOCAFION MINIMUM INSTRUMENTS OPERABLE HEAT FLAME SMOKE
- 1. Containment
- a. FDZ-RCP 1 Elev. 603' 0 0 1*
- b. FDZ-RCP 2 Elev. 603' O O 1*
- c. FDZ-RCP 3 Elev. 603' 0 0 1*
- d. FDZ-RCP 4 Elev. 603' O O 1*
- e. FDZ-PZR Elev. 603' O O 1*
- f. FDZ 214 - Core Flooding Tank 1-1 Area Elev. 565' O O 3*
1 #g. FDZ 215 - Ctet. Letdown Cooler Area Elev. 565' O O 2*
- h. FDZ 220 - Incore Instrument Trench Area Elev. 565' O O 4*
- 1. FDZ 317 - Hatch Area - Elev. 565' O O 20 *
- j . FDZ 410 - East Passage - Elev. 603'/657' O O 9*
l l 2. Containment Annulus
- a. FDZ-A208 Elev. 590' O O 10
- b. FDZ-236H Elev. 774' O O 3
- c. FDZ-236L Elev. 590' 0 0 9
- 3. Auxiliary Building
- a. FDZ 402 - #1 Electrical Penetration Rm.
Elev. 603' 0 0 12
- b. FDZ 405 - Auxiliary Building Storage Rm.
Elev. 603' 0 0 1
- c. FDZ 427 - #2 Electrical Penetration Rm.
Elev. 603'
~
O O 7
- d. FDZ 303 - #3 Mechanical Pentration Rm.
Elev. 585' O O 12
- e. FDZ 304 - Corridor to Mech. Pent Rms 3&4 Elev. 585' O O 4
- f. FDZ 310 - Passage to BA Mix Tank Elev. 585' O O 8 g._ FDZ 312 - Spent Fuel Pool Pump Rm.
Elev. 585' O O 4
- h. FDZ 314 - #4 Mech. Pent. Room Elev. 585' 0 0 17
- 1. FDZ 300 - Fuel Handling Area Elev. 585' 0 0 5 i
- Fire Detectors in high radiation areas which are NOT accessible.
1 4
.-r g., --
m -
,, .,c ,, - - ,,e- , , - --- n
. ~, >
Sheet 2 of 4 I_'STRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE HEAT FLAME SMOKE
- 3. Auxiliary Building (Continued) i~
- j. FDZ 209 - Corridor to il Mech. Pent. Rm.
Elev. 565' O O 3
- k. FDZ 227 - Boric Acid Evap Passageway Elev. 565' 0 0 6
- 1. FDZ 208 - #1 Mechanical Penetration Rm.
Elev. 565' 0 0 10
- m. FDZ 231 - Clean Waste Booster Pump Rm.
Elev. 565' 0 0 1
- n. FDZ 232 - Primary & Deborating Demin Viv Rm. - Elev. 565' O O 1
- o. FDZ 234 - Boric Acid Evaporator Rm 1-2 l Elev. 565' 0 0 1
- p. FDZ 235 - Boric Acid Evaporator Rm 1-1 Elev. 565' f 0 1
- q. FDZ 236 - #2 Mechanical Penetration Pa.
Elev. 565' J 0 4
. r. FDZ 240 - Boric Acid Addition Tank Rm.
} Elev. 565' C 0 5 l s. FDZ 241 - Passage to B.A. Addition Tk Rm.
- Elev. 565' O O 2
) t. FDZ 101 - Equipment and Pipe Tunnel l' Elev. 545' O O 1
- u. FDZ 105 - ECCS Pump Room 1-1 Elev. 545' O 0, 4
- v. FDZ 110 - Corridor to Central Aren of j Aux Bldg. - Elev. 54C5 0 0 5 l w. FDZ 113 - Decay Heat Exchange. Pit l i Elev. 545' O O 1 l
- x. FDZ 115 - ECCS Pump Room 1-2 Elev. 545' O O 2
- y. FDZ 124 - Clean Waste Receiver Tank Rm. 1 Elev. 545' O O 4
- 4. Auxiliary Building Fan Rooms
- a. FDZ 500 - Radwaste & Fuel Handling Area and Air Supply Area -
Elev. 623' O O 20 l
- b. FDZ 501 - Radwaste Exhaust Equipment and Main Station Exhaust Fan Room Elev. 623' O 0 22
- c. FDZ 515 - Purge and Exhaust Equipment Rm.
Elev. 623' O O 22
- d. FDZ 516 - Non-rad Air and Exhaust Equip.
Rm. - Elev. 623' O O 5 l
l g- v-- y , - , - ,, . - - _ - - - - . -
Sheet 3 of 4 INSTRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE HEAT FLAME SMOKE
- 5. Control Room Complex l
- a. FDZ 505 - Main Control Board Cabinets 3
Elev. 623' O O
- b. FDZ SOS - Control Cabinet Room Elev. 623' O O 5 FDZ 505 - Computer Room - Elev. 623' O O 1 c.
l
- 6. Cable Spreading Room 0 0 5
- a. FDZ 422A - Elev. 613' l
l
- 7. A/C Equipment Room
- a. FDZ 603 - Elev. 643' O O 11
- 8. Diesel Generator Rooms
- a. FDZ 318 - Diesel Generator Rm. 1-1 Elev. 585' 0 0 5
- b. FDZ 319 - Diesel Generator Rm. 1-2 Elev. 585' 0 0 4
- c. FDZ 321A - Diesel Generator Day Tank Room 1 E1Ev. 5 0 0 1
- d. FDZ 320A - Diesel Generator Day 'fank Room,1 Elev. 5 0 0 1
- 9. Battery Rooms FDZ 428A - Battery Room B - Elev. 603' O O 2
- a. '
FDZ 429B - Battery Room A - Elev. 603' O O 2 b.
- 10. Component Cooling Water Pump Room 0 0 9
- a. FDZ 328 - Elev. 585'
- 11. Feed Pump Rooms
- a. FDZ 237 - Auxiliary Feed Pump 1-1 O 3 Elev. 565' O
- b. FDZ 238 - Auxiliary Feed Pump 1-2 0 3 Elev. 565' 0
d
".* Sheet 3 of 4 MINIMUM INSTRUMENTS OPERABLE INSTRUMENT LOCATION HEAT FLAME SMOKE I
i 5. Control Room Complex l a. FDZ 505 - Main Control Board Cabinets 3 O O l
Elev. 623'
- b. FDZ 505 - Control Cabinet Room 5 O O j , Elev. 623' 1 FDZ 505 - Computer Room - Elev. 623' O O
~
c.
l 6. Cable Spreading Room O O 5 i a. FDZ 422A - Elev. 613' 1
i
. 7. A/C Equipment Room O O 11
- a. FDZ 603 - Elev. 643' i
i 8. Diesel Generator Rooms 4
- a. FDZ 318 - Diesel Generator Rm. 1-1 Elev. 585' 0 0 5 l
- b. FDZ 319 - Diesel Generacor Rm. 1-2 4 Eler. 585' 0 0
- c. FDZ 321A - Diesel Generator Day Tank Room 1 Elsv. 5 0 0 1
- d. FDZ 320A-- Diesel Generator Day Tank 0 0 1 Room 1 Elev. 5
}1
- 9. Battery Rooms r
O 2
- a. FDZ 428A - Battery Room B - Elev. 603' O 0 0 2
- b. FDZ 429B - Battery Room A - Elev. 603'
- 10. Component Cooling Water Pump Room 0 0 9
- a. FDZ 328 - Elev. 585'
- 11. Feed Pump Rooms
- a. FDZ 237 - Auxiliary Feed Pump 1-1 0 0 3 Elev. 565'
- b. FDZ 23f; - Auxiliary Feed Pump 1-2 0 0 3 Elev. 565'
- _ _ - _ _ _ _ _ = _ . - - - - . - - - - . . _ _ _ _ - _ _ _ - - - _ _ _
o s
Sheet 4 of 4 MINIMUM INSTRUMENTS OPERABLE INSTaUMENT LOCATION 4
HEAT _ FLAME SMOKE
- 12. Switchgear Roomg
- a. FDZ 324 - CD ~31gb Voltage Switchgear O O 3 01ev. 585'
' b. FDZ 325 - A High Voltage Switchgear 8 O
Elev. 585' O
- c. FDZ 323 - B High Voltage Switchgear O O 11
. Elev. 585' l l
- d. FDZ 428 - F High Voltage Switchgear l O O 12 j Elev. 603'
, c. FDZ 429 - E High Voltage Switchgear 6 O O
- Elev. 603'
- 13. Intake Structure
- a. FDZ 052 - Diesel Fire Pump Room O O 1 Elev. 576' j b. FDZ 052- Service Water Pump Room O O 3 j Elev. 576'
- c. FDZ 053 - Service Water Viv. Room 0 6 Elev. 565' 0 4
i J
i l j
+
l l
1
- The fire detection instruments located within the Containment are not required to be OPERABLE during the performance of Type A Containment Leakage Rate Tests.
- These detectors automatically actuate fire suppression systems.
. . . _ . ._ -. __ .._ __ __