Proposed Tech Specs 3.3.3.8 & 4.3.3.8 Re Fire Detection Instrumentation
ML19351D622
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 10/07/1980
From:
TOLEDO EDISON CO.
To:
Shared Package
ML19351D621 List:
References
NUDOCS 8010140249
Download: ML19351D622 (5)


Text

-_ _

i i

O INSTRUMENTATION i

l FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION i

3.3.3.8 As a minimum, the fire detection instrumentation for each fire detection zone shown in Table 3.3-14 shall be OPERABLE.

j APPLICABILITY: Whenever equipment in that fire detection zone is required to be OPERABLE.

1 I

ACTION: With the number of OPERABLE fire detection instrument (s) less than j

the minimum number OPERABLE requirement of Table 3.3-14:

Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> establish a fire watch patrol to inspect the a.

accessible zone (s) with the inoperable instrument (s) at least once per hour, and i

l-b.

Restore the inoperable instrument (s) to OPERABLE status within L

14 days or, in lieu of any other report required by Specifi-cation 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 4

j days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the instrument (s) to 1

OPERABLE status.

]

c.

The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

i I

SURVEILLANCE REQUIREMENTS i

4.3.3.8.1 Each of the above required accessible fire detection instruments shall be demonstrated OPERABLE at least once per 6 months by performance 2

of a CHANNEL. FUNCTIONAL TEST.

Each of the above required inaccessible fire detection instrument shall be demonstrated OPERABLE at len.,e once i

per 18 months by performance of a CllANNEL FUNCTIONAL TEST.

'4.3.3.8.2 The NFPA Code 72D Class A supervised circuits supervision 4

associated with the detector alarms of each of the above required fire detection instruments shall be demonstrated OPERABLE at lease once per 1

6 months.

l I

i 4.3.3.8.3 The non-supervised circuits between the local panels in 1

Specification 4.3.3.8.3 and the control room shall be demonstrated

' OPERABLE at least once per 31 days.

r DAVIS-BESSE, UNIT 1 3/4 3-52 Amendment No.

8 01014Op e

Sheet 1 of 4 TABLE 3.3-14 FIRE DETECTION INSTRUMENTS INSTRUMENT LOCAFION MINIMUM INSTRUMENTS OPERABLE HEAT FLAME SMOKE 1.

Containment

  1. a.

FDZ-RCP 1 Elev. 603' 0

0 1*

  1. b.

FDZ-RCP 2 Elev. 603' O

O 1*

  1. c.

FDZ-RCP 3 Elev. 603' 0

0 1*

  1. d.

FDZ-RCP 4 Elev. 603' O

O 1*

  1. e.

FDZ-PZR Elev. 603' O

O 1*

  1. f.

FDZ 214 - Core Flooding Tank 1-1 Area Elev. 565' O

O 3*

1

  1. g.

FDZ 215 - Ctet. Letdown Cooler Area Elev. 565' O

O 2*

  1. h.

FDZ 220 - Incore Instrument Trench Area Elev. 565' O

O 4*

  1. 1.

FDZ 317 - Hatch Area - Elev. 565' O

O 20 *

  1. j. FDZ 410 - East Passage - Elev. 603'/657' O

O 9*

l l

2.

Containment Annulus

  1. a.

FDZ-A208 Elev. 590' O

O 10

  1. b.

FDZ-236H Elev. 774' O

O 3

  1. c.

FDZ-236L Elev. 590' 0

0 9

3.

Auxiliary Building a.

FDZ 402 - #1 Electrical Penetration Rm.

Elev. 603' 0

0 12 b.

FDZ 405 - Auxiliary Building Storage Rm.

Elev. 603' 0

0 1

c.

FDZ 427 - #2 Electrical Penetration Rm.

Elev. 603' O

O 7

~

d.

FDZ 303 - #3 Mechanical Pentration Rm.

Elev. 585' O

O 12 e.

FDZ 304 - Corridor to Mech. Pent Rms 3&4 Elev. 585' O

O 4

f.

FDZ 310 - Passage to BA Mix Tank Elev. 585' O

O 8

g._

FDZ 312 - Spent Fuel Pool Pump Rm.

Elev. 585' O

O 4

h.

FDZ 314 - #4 Mech. Pent. Room Elev. 585' 0

0 17 1.

FDZ 300 - Fuel Handling Area Elev. 585' 0

0 5

i

  1. Fire Detectors in high radiation areas which are NOT accessible.

1 4

.-r g.,

m

.,c

,,e-r.

n

~,

Sheet 2 of 4 I_'STRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE HEAT FLAME SMOKE 3.

Auxiliary Building (Continued) i

~

j.

FDZ 209 - Corridor to il Mech. Pent. Rm.

Elev. 565' O

O 3

k.

FDZ 227 - Boric Acid Evap Passageway Elev. 565' 0

0 6

1.

FDZ 208 - #1 Mechanical Penetration Rm.

Elev. 565' 0

0 10 FDZ 231 - Clean Waste Booster Pump Rm.

m.

Elev. 565' 0

0 1

n.

FDZ 232 - Primary & Deborating Demin Viv Rm. - Elev. 565' O

O 1

o.

FDZ 234 - Boric Acid Evaporator Rm 1-2 l

Elev. 565' 0

0 1

p.

FDZ 235 - Boric Acid Evaporator Rm 1-1 Elev. 565' f

0 1

q.

FDZ 236 - #2 Mechanical Penetration Pa.

Elev. 565' J

0 4

r.

FDZ 240 - Boric Acid Addition Tank Rm.

}

Elev. 565' C

0 5

l s.

FDZ 241 - Passage to B.A. Addition Tk Rm.

Elev. 565' O

O 2

)

t.

FDZ 101 - Equipment and Pipe Tunnel l

Elev. 545' O

O 1

u.

FDZ 105 - ECCS Pump Room 1-1 Elev. 545' O

0, 4

v.

FDZ 110 - Corridor to Central Aren of j

Aux Bldg. - Elev. 54C5 0

0 5

l w.

FDZ 113 - Decay Heat Exchange. Pit i

Elev. 545' O

O 1

x.

FDZ 115 - ECCS Pump Room 1-2 Elev. 545' O

O 2

y.

FDZ 124 - Clean Waste Receiver Tank Rm. 1 Elev. 545' O

O 4

4.

Auxiliary Building Fan Rooms a.

FDZ 500 - Radwaste & Fuel Handling Area and Air Supply Area -

Elev. 623' O

O 20 b.

FDZ 501 - Radwaste Exhaust Equipment and Main Station Exhaust Fan Room Elev. 623' O

0 22 FDZ 515 - Purge and Exhaust Equipment Rm.

c.

Elev. 623' O

O 22 d.

FDZ 516 - Non-rad Air and Exhaust Equip.

Rm. - Elev. 623' O

O 5

7 g-v--

y

Sheet 3 of 4 MINIMUM INSTRUMENTS OPERABLE INSTRUMENT LOCATION HEAT FLAME SMOKE 5.

Control Room Complex l

a.

FDZ 505 - Main Control Board Cabinets Elev. 623' O

O 3

b.

FDZ SOS - Control Cabinet Room Elev. 623' O

O 5

c.

FDZ 505 - Computer Room - Elev. 623' O

O 1

l 6.

Cable Spreading Room a.

FDZ 422A - Elev. 613' 0

0 5

l l

7.

A/C Equipment Room a.

FDZ 603 - Elev. 643' O

O 11 8.

Diesel Generator Rooms l

    • a.

FDZ 318 - Diesel Generator Rm. 1-1 Elev. 585' 0

0 5

    • b.

FDZ 319 - Diesel Generator Rm. 1-2 Elev. 585' 0

0 4

c.

FDZ 321A - Diesel Generator Day Tank Room 1 E1Ev. 5 0

0 1

d.

FDZ 320A - Diesel Generator Day 'fank Room,1 Elev. 5 0

0 1

9.

Battery Rooms FDZ 428A - Battery Room B - Elev. 603' O

O 2

a.

b.

FDZ 429B - Battery Room A - Elev. 603' O

O 2

10.

Component Cooling Water Pump Room a.

FDZ 328 - Elev. 585' 0

0 9

11.

Feed Pump Rooms a.

FDZ 237 - Auxiliary Feed Pump 1-1 Elev. 565' O

O 3

b.

FDZ 238 - Auxiliary Feed Pump 1-2 Elev. 565' 0

0 3

d Sheet 3 of 4 MINIMUM INSTRUMENTS OPERABLE INSTRUMENT LOCATION HEAT FLAME SMOKE I

i 5.

Control Room Complex FDZ 505 - Main Control Board Cabinets l

a.

l Elev. 623' O

O 3

b.

FDZ 505 - Control Cabinet Room Elev. 623' O

O 5

j,

~

c.

FDZ 505 - Computer Room - Elev. 623' O

O 1

l 6.

Cable Spreading Room i

a.

FDZ 422A - Elev. 613' O

O 5

1 i

7.

A/C Equipment Room a.

FDZ 603 - Elev. 643' O

O 11 i

i 8.

Diesel Generator Rooms 4

    • a.

FDZ 318 - Diesel Generator Rm. 1-1 Elev. 585' 0

0 5

l

    • b.

FDZ 319 - Diesel Generacor Rm. 1-2 Eler. 585' 0

0 4

FDZ 321A - Diesel Generator Day Tank c.

Room 1 Elsv. 5 0

0 1

d.

FDZ 320A-- Diesel Generator Day Tank Room 1 Elev. 5 0

0 1

}1 9.

Battery Rooms r

a.

FDZ 428A - Battery Room B - Elev. 603' O

O 2

b.

FDZ 429B - Battery Room A - Elev. 603' 0

0 2

10.

Component Cooling Water Pump Room a.

FDZ 328 - Elev. 585' 0

0 9

11.

Feed Pump Rooms FDZ 237 - Auxiliary Feed Pump 1-1 a.

Elev. 565' 0

0 3

b.

FDZ 23f; - Auxiliary Feed Pump 1-2 Elev. 565' 0

0 3

=

o Sheet 4 of 4 s

MINIMUM INSTRUMENTS OPERABLE INSTaUMENT LOCATION HEAT _

FLAME SMOKE 4

12.

Switchgear Roomg FDZ 324 - CD ~31gb Voltage Switchgear a.

01ev. 585' O

O 3

b.

FDZ 325 - A High Voltage Switchgear Elev. 585' O

O 8

FDZ 323 - B High Voltage Switchgear c.

l

. Elev. 585' O

O 11 l

d.

FDZ 428 - F High Voltage Switchgear l

j Elev. 603' O

O 12 FDZ 429 - E High Voltage Switchgear c.

Elev. 603' O

O 6

13.

Intake Structure FDZ 052 - Diesel Fire Pump Room a.

Elev. 576' O

O 1

j b.

FDZ 052-Service Water Pump Room Elev. 576' O

O 3

j FDZ 053 - Service Water Viv. Room c.

Elev. 565' 0

0 6

4 i

J i

j

+

l l

1

  • The fire detection instruments located within the Containment are not required to be OPERABLE during the performance of Type A Containment Leakage Rate Tests.
    • These detectors automatically actuate fire suppression systems.

__