ML20101M192
| ML20101M192 | |
| Person / Time | |
|---|---|
| Site: | Davis Besse |
| Issue date: | 03/29/1996 |
| From: | CENTERIOR ENERGY |
| To: | |
| Shared Package | |
| ML20101M131 | List: |
| References | |
| NUDOCS 9604050186 | |
| Download: ML20101M192 (11) | |
Text
.
CONTAINMENT SYSTEMS HYDROGEN PURGE SYSTEM LIMITING CONDITION FOR OPERATION 3.6.4.4 A containment hydrogen purge system shall be OPERABLE.
APPLICABILITY: MODES 1 and 2.
ACTION:
1 With the containment hydrogen purge system inoperable, restore the i
hydrogen purge system to OPERABLE status within 30 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
SURVEILLANCE REQUIREMENTS 4.6.4.4 The hydrogen purge system shall be demonstrated OPERABLE:
4 i
a.
At least once per 18 months by initiating flow through the HEPA l
filters and charcoal adsorbers and verifying that the system j
operates for at least 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with the heaters on, b.
At least once per 18 months or (1) after any structural main-tenance on the HEPA filter or' charcoal adsorber housings, or (2) following painting, fire or chemical release in any venti-lation zone comunicating with the system by:
1.
Verifying that the cleanup system satisfies the in-place penetration and bypass leakage testing acceptance criteria l
of less than 1% and uses the test procedure guidance in Regulatory Positions C.S.a. C.5.c. and C.5.d of Regulatory Guide 1.52, Revision 2 March 1978, and the system flow rate is 100 cfm t 10%; and Verifyin9.J Ithii 31 days after removal,le obtained inthat a laboratory l 2.
w analysis of a representative carbon samp accordance with Regulatory Position C.6.b of Regulatory Guide 1.52, Revision 2. March 1978, mee oratory l
testing criteria of Regulatory Positio C.6.a,
Regulatory Guide 1.52, Revision 2. March 1978, for a methyliodide penetration of less than 1%.
- Sec. A L d nJsRT~
DAVIS-BESSE, UNIT 1 3/4 6-26 Amendment No.155 9604050186 960329 PDR ADOCK 05000346 P
PDR l
CONTAINMENT SYSTEMS
\\
I'JRVEILLANCE REQUIREMENTS 'Continueol within 31 days after reoval, that a laboratory ana c.
Position C.6.b of Regulatory Guide 1.52. Revision 2
- j meets the laboratory testing criteria of Regulatory Positio C.6.a #
of Regulatory Guide 1.52, Revision 2, March 1978, for a methy to penetration of less than 1%.
d.
At least once per 18 months by:
{
1.
Verifying that the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 25 inches
- i Water Gauge while operating the systs at a flow rate of 100 cfm i 10%; and i
ll 2.
Verifying that the heaters dissipate 2.010.4 kw when tested in accordance with ANSI N510-1980, t
After each complete or partial replacment of a HEPA filter e.
bank, by verifying that the cleanup system satisfies the l
in-place penetration and bypass leakage testing acceptance l
criteria of less than 1% in accordance with ANSI M510-1980
,j for a 00P test aerosol while operating the systs at a flow 1
j rate of 100 cfm i 10%.
l f.
i After each complete or partial replacement of a charcoal i
adsorber bank, by verifying that the cleanup syste satisfies the in-place penetration and bypass leakage testing acceptance criteria of less than 1% in accordance with ANSI N510-1980 for a halogenated hydrocarbon refrigerant test gas while operating l
the systs at a flow rate of 100 cfm i 10%.
4 See on+fueNc) Id.SEL T i
i
'0 AVIS-BESSE, UNIT 1 3/4 6-27 Amendment No.155
\\
INFORMATION ONLY CONTAINMENT SYSTEM 3/4.6.5 $HIELO SUILDING EMERGENCY VENTILATION SYSTEM i
1 LIMITING CON 0! TION FOR OPERATION 3.6.5.1 Two independent emergency ventilation systems shall be OPERABLE.
l APPLICABILITY: MODES 1, 2, 3 and 4 l
ACTION:
With one emergency ventilation system inoperable, restore the inoperable system to OPERABLE status within 7 days or be in at least HOT STAND 8Y within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 l
hours.
SURVEILLANCE REOUIREMENTS 4.6.5.1 Each emergency ventilation system shall be demonstrated OPERA 8LE:
At least once per 31 days on a STAGGERED TEST BASIS by initiating.
a.
from the control room, flow through the HEPA filters and charcoal adsorbers and verifying that the system operates for at least 15 minutes.
b.
At least once per 18 months or (1) after any structural main-tenance on the HEPA filter or charcoal adsorber housings, or (2) following oainting, fire or chemical release in any venti-lation zone comunicating with the system by:
l l
DAVIS-BESSE. UNIT 1 3/4 6-28 Amendment No.155 l
l CONTAINMENT SYSTEMS lfSURVEILLANCEREQUIREMENTS (Continued) 1.
Verifying that the cleanup system satisfies the in-place penetration and bypass leakage testing acceptance criteria of less than 1% and uses the test procedure guidance in Regulatory Positions C.S.a. C.S.c and C.5.d of Regulatory Guide 1.52. Revision 2, March 1978, and the systen flow l
rate is 8,000 cfm i 10%;
2.
Verifying, within 31 days af ter removal, that a laboratory analysis of a representative carbon sample obtained in accordance with Regulatory Position C.6.b of Regulatory Guide 1.52,~ Revision 2, March 1978, meets th aboratory l
testing criteria of Regulatory Position
.6.
Regulatory l
Guide 1.52, Revision 2, March 1978, for a methyliodide penetration of less than 1%; and 3.
Verifying a system flow rate of 8,000 cfm i 10% during i
system operation when tested in accordance with ANSI N510-1980.
l After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation, by verify-c.
ing, within 31 days after removal, that a laboratory analysis of a representative carbon sample obtained in accordance with Regulatory Position C.6.b of Regulatory Guide 1.52, Revision 2, March 1978 the laboratory testing criteria of Regulatory m
t Position Regulatory Guide 1.52, Revision 2, March 1978, for a meth ide penetration of less than 1%.
d.
At least once per 18 months by:
1.
Verifying that the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 6 inches l
Water Gauge while operating the system at a flow rate of 8,000 cfm i 10%;
2.
Verifying that the system starts automatically on any containment isolation test signal; 3.
Verifying that the filter cooling bypass valves can be manually opened; and
- See, N e b d IWEr T-l DAVIS-BESSE, UNIT 1 3/4 6-29 Amendment No. 43.135,155 k
INFORMATION ONLY CONTAINMENT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 4.
Verifying that each system produces a negative pressure of greater than or equal to 0.25 inches Water Gauge in the I
annulus within 4 seconds after the fan attains a flow rate l
of 8000 cfm i 10%. This test is to be performed with the flow path established prior to starting the EVS fan, and the other dampers associated with the negative pressure boundary closed.
Af ter each complete or partial replacement of a HEPA filter e.
bank, by verifying that the cleanup system satisfies the in-place penetration and bypass leakage testing acceptance crf teria of less than 1% in accordence with ANSI N510-1980 for a 00P test aerosol while operating the system at a flow rate of 8000 cfm i 10%.
f.
After each complete or partial replacement of a charcoal adsorber bank, by verifying that the cleanup system satisfies the in-place penetration and bypass leakage testing acceptance t
criteria of less than 1% in accordance with ANSI N510-1980 for a halogenated hydrocarbon refrigerant test gas while operating the system at a flow rate of 8000 cfm i 10%.
DAVIS-BESSE, UNIT 1 3/4 6-30 Amendrnent No. 3 J35.155
i INFORMATION ONLY PLANT SYSTEMS
.I l 3/4.7.6 CONTROL ROOM EMERGENCY VENTILATION SYSTEM i
l l
j, LIMITING CONDITION FOR OPERATION l
3.7.6.1 Two independent control room emergency ventilation systems shall be OPERABLE.
APPLICABILITY: MODES 1, 2, 3 and 4.
ACTION:
With one control room emergency ventilation system inoperable, restore the inoperable system to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
SURVEILLANCE REQUIREMENTS 4.7.6.1 Each control room emergency ventilation system shall be demonstrated OPERABLE:
At least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> by verifying that the control room air a.
temperature is less than or equal to 110*F when the control room emergency ventilation system is operating.
I b.
At least once per 31 days on a STAGGERED TEST BASIS by initiating, from the control room, flow through the HEPA filters and charcoal adsorbers and verifying that the system operates for at least 15 minutes.
At least once per 18 months or (1) after any structural maintenance c.
on the HEPA filter or charcoci adsorber housings, or (2) following painting, fire or chemical release in any ventilation zone comuni-cating with the system by:
DAVIS-BESSE, UNIT 1 3/4 7-17 Amendment No. 125,155
PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) l 1.
Verifying that the cleanup system satisfies the in-place i
penetration and bypass leakage testing acceptance criteria i
of less than 1% and uses the test procedure guidance in Regulatory Positions C.S.a. C.5.c and C.5.d of Regulatory Guide 1.52, Revision 2, March 1978, and the system flow rate is 3300 cfm i 10%;
I 2.
Verifying, within 31 days after removal, that. a laboratory l
analysis of a representative carbon sample obtained in accordance with Regulatory Position C.6.b of Regulatory Guide 1.52, Revision 2 March 1978, mee aboratory testing criteria of Regulatory Positio C.6.a Regulatory Guide 1.52, Revision 2, March 1978, for a methyliodide penetration of less than 1%; and 3.
Verifying a system flow rate of 3300 cfm + 10% during system operation when tested in accordance with INSI N510-1980.
d.
After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation by verifying, within 31 days after removal, that a. laboratory analysis of a representative carbon sample obtained in accordance with Regulatory Position C.6.b of Regulatory Guide 1.52, Revision 2, March 197B._ meets the laboratory testing criteria of Regulatory PositionlG_.6.a'jY Regulatory Guide 1.52, Revision 2, March 1978, for a methylfodide penetration of less than 1%.
l e.
At least once per 18 months by:
1.
Verifying that the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 4.4 inches Water Gauge while operating the system at a flow rate of l
3300 cfm i 10%;
2.
Verifying that the control room nonnal ventilation system is isolated by a SFAS test signal and a Station Vent Radiation Hign test signal; and i
+ S< = -t% L d ea screi-i 9
DAVIS-BESSE, UNIT 1 3/4 7-18 Amendment No. 134,135,155 1
INFORMATION ONLY pLm Sv51mS l
SURVEILLANCE REQUIREMENTS (Continued) l 3.
Verifying that the makeup flow of the system is 300 cfm i 10%
l when supplying the control room with outside air.
l f.
After each complete or partial replacement of a HEPA filter bank, by verifying that the cleanup system satisfies the in-place penetration and bypass leakage testing acceptance criteria of I
less than 1% in accordance with ANSI N510-1980 for a D0P test aerosol while operating the system at a flow rate of 3300 cfm i 10%.
g.
After each complete or partial replacement of a charcoal adsorber bank, by verifying tnat the cleanup system satisfies the in-place penetration and bypass leakage testing acceptance criteria of less than 1% in accordance with ANSI N510-1980 for a halogenated hydro-carbon refrigerant test gas while operating the system at a flow rate of 3300 cfm i 10%.
l l
1 DAVIS-BESSE, UNIT 1 3/4 7-19 Amendment No.155
1 c.
t INSERT Footnote SR 4.6.4.4.b.2 SR 4.6.4.4.c SR 4.6.5.1.b.2 SR 4.6.5.1.c SR 4.7.6.1.c.2 SR 4.7.6.1.d M_
- The test is performed in accordance with ASTM D 3803-1979 with the following conditions:
- 1) Equilibrate for 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br /> at 30oC and 70% relative humidity
- 2) Challenge for 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> at 300C and 70% relative humidity
- 3) Elution for 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> at 30oc and 70% relative humidity i
L
f Dochet Number 50-346 License Number NPF-3
.' ' Serial Number 2369 l
Page 1 ENVIRONMENTAL ASSESSMENT l
, Identification of Proposed Action This proposed action involves the Davis-Besse Nuclear Power Station j
(DBNPS), Unit Number 1, Operating License Number NPF-3, Appendix A, l
Technical Specifications (TS). A license amendment application is proposed to revise TS 3/4.6.4.4, " Hydrogen Purge System, 3/4.6.5 - Shield Building Emergency Ventilation System, and 3/4.7.6, " Control Room Emergency Ventilation System to reference the current charcoal filter laboratory testing methodology. The test is in accordance with ASTM D 3803-1979 with the following conditions:
1.
Equilibrate for 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br /> at 30oc and 70% relative humidity 2.
Challenge for 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> at 30oc and 70% relative humidity l
3.
Elution for 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> at 30oC and 70% relative humidity Need for the Proposed Action The changes proposed are needed to allow continued plant operation. A l
plant shutdown would be required due to the inability to perform the surveillance tests literally required by the TS in the time available.
Environmental Impact of the Proposed Action The proposed license amendment involves a change to a requirement with respect to the use of facility components located within the restricted l
area as defined in 10CFR Part 20. As discussed in the Significant Hazards Consideration, this proposed license amendment does not involve a l
significant hazards consideration. The proposed changes to allow continued plant operation do not alter source terms, containment isolation or l
allowable releases.
In addition, the proposed changes do not involve an increase in the amounts, and no change in the types, of any radiological effluents that may be allowed to be released offsite.
Furthermore, there is no increase in the individual or cumulative occupational radiation exposure.
With regard to potential non-radiological impacts, the proposed license amendment involves no increase in the amounts or change in types of any i
non-radiological effluents that may be released offsite, and has no other environmental impact.
Based on the above, Toledo Edison concludes that there are no significant radiological or non-radiological environmental impacts associated with the proposed license amendment.
i l
_ _ _ =
\\
l Docket Number 50-346 l
License Number NPF-3
' Serial Number 2369 Page 2 l
Alternatives to the Proposed Action Since Toledo Edison has conc.inded that the environmental effects of the proposed action are not significant, any alternatives will have only i
similar or greater environmental impacts. The principal alternative would i
be not to grant the license amendment.
This would not reduce the environmental impacts attributable to the facility.
Furthermore, it would force a shutdown of the facility in accordance with TS 3.0,3 upon expiration of the allowed outage time of TS Action Statement 4.0.3 as applied to TS 3.6.5.1 and TS 3.7.6.1.
Alternative Use of Resources This action does not involve the use of resources not previously considered l
in the Final Environmental Statement Related to the Operation of the l
Davis-Besse Nuclear Power Station, Unit Number 1 (NUREG 75/097).
l Findino of No Sionificant Impact l
Toledo Edison has reviewed the proposed license amendment against the l
criteria of 10CFR51.30 for an environmental assessment. As demonstrated above, the proposed license amendment does not involve a significant hazards consideration, does not increase the types or amounts of effluents that may be released offsite, and does not increase individual or cumulative occupational radiation exposures. Accordingly, Toledo Edison finds that the proposed license amendment, if approved by the Nuclear Regulatory Commission, will have no significant impact on the environment and that no Environmental Impact Statement is required.
l l
l l
l l