Supply Sys Nuclear Plant 2 1995 Annual Environ Operating Rept, Including Summary of Cooling Water Blowndown discharges,1995
ML17291B277
Person / Time
Site: Columbia Energy Northwest icon.png
Issue date: 12/31/1995
From:
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
To:
Shared Package
ML17291B276 List:
References
NUDOCS 9603250400
Download: ML17291B277 (2)


Text

WNP-2 COOLING WATER BLOWDOWN DISCHARGES, 1995 Days of pH TRC Discharge Volume Month Discharge (mg/1) (millions of gallons)

High Total Ave*

31 7.9 8.7 s0.1 49.5 1.60 2.59 Feb 24 7.9 8.6 <0.1 55.8 2.33 7.86 30 7.9 8.5 <0.1 68.5 2.28 5.11 Apr 24 7.6 8.7 <0.1 58.9 2.45 5.10 May 27 7.3 8.6 s0.1 53.9 1.99 3.26 Jun 24 7.5 8.7 <0.1 32.1 1.34 2.38 Jul 29 7.8 8,7 <0.1 34.4 1.19 2.43 Aug 31 8.0 8.5 s0.1 31.6 1.02 2.07 Sep 30 8.0 8.7 <0.1 31.8 1.06 2.20 Oct 30 7.9 8.7 s0.1 35.5 1.18 2.38 Nov 26 7.8 8.7 s0.1 34.6 1.33 2.38 Dec 16 7.6 8.4 <0.1 18.5 1.16 2.81 Permit Limit 6.5 9.0 0.1 5.60 9.40

  • Average daily discharge during the month.
    • Maximum daily discharge during the month.

Supply System Nuclear Plant No. 2 1995 Annual Environmental Operating Report 9603250400 9603i9 PDR ADOCK 05000397 R PDR