ML13163A319: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
Line 22: Line 22:
(1) the relationship in between shear wall column P7, P4, etc. to the SFP column 17 to 23 and P to W? (Yellow Highlight),   
(1) the relationship in between shear wall column P7, P4, etc. to the SFP column 17 to 23 and P to W? (Yellow Highlight),   


(2) missing Value (Green Highlight), and   
(2) missing Value (Green Highlight), and   


(3) below Table, foot note *SSE Max. Moment (IR = 1.111). This interaction ratio (IR) is unacceptable (need to see a conservative reanalysis [method] that has an IR below unity.  
(3) below Table, foot note *SSE Max. Moment (IR = 1.111). This interaction ratio (IR) is unacceptable (need to see a conservative reanalysis [method] that has an IR below unity.  


Thanks, John}}
Thanks, John}}

Revision as of 18:28, 28 April 2019

Another Heavy Loads Amendment Question
ML13163A319
Person / Time
Site: Zion  File:ZionSolutions icon.png
Issue date: 06/10/2013
From: Hickman J B
NRC/FSME/DWMEP/DURLD/RDB
To: Beckman D A
ZionSolutions
Hickman J B
References
Download: ML13163A319 (2)


Text

From: Hickman, John Sent: Monday, June 10, 2013 4:48 PM To: Donald A. Beckman

Subject:

Another Heavy Loads Amendment Question Attachments: Question on page 24 of 53.pdf Don, Please see the attached page markup. Dan needs you to explain:

(1) the relationship in between shear wall column P7, P4, etc. to the SFP column 17 to 23 and P to W? (Yellow Highlight),

(2) missing Value (Green Highlight), and

(3) below Table, foot note *SSE Max. Moment (IR = 1.111). This interaction ratio (IR) is unacceptable (need to see a conservative reanalysis [method] that has an IR below unity.

Thanks, John