ULNRC-06114, License Renewal Application NFPA 805 Gap Analysis

From kanterella
Jump to navigation Jump to search
License Renewal Application NFPA 805 Gap Analysis
ML14105A476
Person / Time
Site: Callaway Ameren icon.png
Issue date: 04/15/2014
From:
Ameren Missouri
To:
Office of Nuclear Reactor Regulation
Shared Package
ML14105A474 List:
References
ULNRC-06114
Download: ML14105A476 (42)


Text

ULNRC-06114 April 15, 2014 Page 1 of 30 CALLAWAY PLANT UNIT 1 LICENSE RENEWAL APPLICATION NFPA 805 GAP ANALYSIS

ULNRC-06114 April 15, 2014 Page 2 of 30 CALLAWAY LICENSE RENEWAL/NFPA 805 GAP ANALYSIS Callaway's original fire protection program was based on 10 CFR 50.48 and associated commitments to Branch Technical Position (BTP) APCSB 9.5-1, Appendix A, and 10 CFR 50, Appendix R. FSAR Appendix 9.5A currently lists the requirements of APCSB 9.5-1, Appendix A, along with a discussion of how Callaway met each of those requirements.

FSAR Appendix 9.5E currently provides a design comparison to 10 CFR 50, Appendix R.

Callaway is in the process of transitioning to a fire protection program based on 10 CFR 50.48(c), which incorporates, by reference, NFPA 805, with exceptions. This program supersedes commitments to BTP APCSB 9.5-1, Appendix A, and 10 CFR 50, Appendix R.

FSAR Appendix 9.5A and Appendix 9.5E will be deleted. This program was approved by the NRC on January 13, 2014, as License Amendment No. 206, to be implemented by eight months from the approval date, i.e. September 13, 2014. Scope differences between the approved NFPA 805 License Amendment and the License Renewal Application currently under review were assessed using the License Renewal Application through Amendment 32 (ULNRC-06090 dated March 13, 2014) and the NFPA 805 License Amendment Request through ULNRC-06031 dated September 24, 2013. The NFPA 805 and License Renewal programs are dynamic programs that will be maintained current to reflect changes to the plant and incorporation of site and industry operating experience.

The following is a gap analysis of the two programs as they relate to License Renewal. The purpose of this gap analysis is to:

1) identify systems, structures, and components (SSCs) required by the NFPA 805 program which are not currently within the scope of License Renewal; and
2) identify SSCs previously within the scope of License Renewal for fire protection, but which are no longer required by the NFPA 805 program.

This gap analysis compares License Renewal scope differences and does not address areas outside the scope of License Renewal, such as personnel requirements, administrative controls, analysis methodology, or procedure requirements.

This Gap Analysis focused on:

1) Nuclear Safety Capability Assessment (safe shutdown equipment list), and
2) Other fire protection systems and components required to meet the NFPA 805 Nuclear Safety Capability Assessment for each fire area.

ULNRC-06114 April 15, 2014 Page 3 of 30 OVERALL RESULTS The following LRA scoping and screening results have been revised to include or delete components to be consistent with the NFPA 805 program. Specific License Renewal changes are included in the NFPA 805 fire area summaries later in this gap analysis.

Condensate Storage and Transfer System (LRA Section 2.3.4.6 and LRA Table 2.3.4-6)

Added a generic tubing component for the Condensate Storage Tank level transmitter (APLT0004) sensing line to LRA Table 2.3.4-6.

Added a pump component and related flow orifice for the non-safety auxiliary feedwater pump (PAP01) to LRA Table 2.3.4-6.

Service Water System (LRA Section 2.3.3.5 and LRA Table 2.3.3-5)

Added a flow orifice for the piping associated with valves EAHV0005 and EAHV0006 to LRA Table 2.3.3-5.

Circulating Water System (LRA Section 2.3.3.29 and LRA Table 2.3.3-29)

Added steel piping, concrete piping, expansion joints, valves, and closure bolting which are used to return service water to the cooling tower basin.

Compressed Air System (LRA Section 2.3.3.8 and LRA Table 2.3.3-8)

Noted that portions of the compressed air system are also within the scope of license renewal to support fire protection requirements based on the criteria of 10CFR54.4(a)(3). Specifically a backup supply of nitrogen gas from the outdoor nitrogen storage tanks (service gas subsystem) is also provided for the auxiliary feedwater control valves and main steam atmospheric relief valves.

In-Scope Tank Foundations and Structures (LRA Section 2.4.7)

Added the nitrogen storage tank foundation and pipe trench to provide support, shelter, and protection for the compressed air system additions.

Radwaste Building HVAC System (LRA Section 2.3.3.17 and LRA Table 2.3.3-17)

Deleted this LRA system from the scope of License Renewal due to the removal of the fire barrier function from the dampers and removal of a charcoal filter spray line. These components had no other License Renewal intended functions.

Fire Protection System (LRA Section 2.3.3.20 and Table 2.3.3-20)

Removal of the fire protection (pressure boundary) function from fire protection components in NFPA 805 fire areas with safety related components required the addition of leakage boundary (spatial) as a function for the component.

The following systems and components were added to or removed from the scope of License Renewal for each fire area. Specific License Renewal changes are included in the NFPA 805 fire area summaries later in this gap analysis.

ULNRC-06114 April 15, 2014 Page 4 of 30 All Stand Pipe & Hose Stations added to the Scope of License Renewal in:

Turbine Building Fire Suppression System Changes to the Scope of License Renewal:

Diesel Generator Building: The fire protection function for two fire suppression systems removed Auxiliary Building: The fire protection function for two fire suppression systems removed Laundry Decontamination Facility: One fire suppression system removed Radioactive Material (RAM) Storage Building: One fire suppression system removed Fuel Building: The fire protection function for one fire suppression system removed Radwaste Building: One fire suppression system removed Turbine Building: Four fire suppression systems removed Auxiliary Boiler Room: One fire suppression system removed Yard: Three fire suppression systems removed Structures / Rated Fire Barriers Changes to the Scope of License Renewal:

Fuel Building is one fire area: Rated fire barriers associated with interior areas removed Radwaste Building is one fire area: Rated fire barriers associated with interior areas removed Gaseous Suppression Changes to the Scope of License Renewal:

Control Building: One gaseous suppression system removed Nuclear Safety Capability Assessment Equipment The nuclear safety goals, objectives, and performance criteria of NFPA 805 are different from the deterministic regulations and guidance of BTP APCSB 9.5-1, Appendix A, and 10 CFR 50 Appendix R. NFPA 805 requires the reactor fuel be maintained in a safe and stable condition rather than achieving and maintaining cold shutdown. In addition, it is necessary to maintain the nuclear fuel safe and stable if a fire occurs while the plant is shut down (Modes 4, 5, 6, and defueled). If the performance goals cannot be met by using deterministic analysis, NFPA 805 allows the use of a risk informed performance-based approach. Due to the difference in methodology, some equipment was required to meet the NFPA 805 performance goals which were not previously credited.

Callaway maintains the NFPA 805 list of required equipment to meet the Nuclear Safety Capability Assessment in a database. This list of equipment was compared to the list of equipment in scope for License Renewal. Electrical equipment in the NFPA 805 list, such as switchgear, transmitters, indicators, and solenoid valves, is within the scope of License Renewal and screened out as active. This includes components associated with communication and detection. All the mechanical equipment in the Nuclear Safety Capability Assessment equipment list is within the scope of License Renewal with the exception of the following, which are being added to the scope of License Renewal since

ULNRC-06114 April 15, 2014 Page 5 of 30 the NRC Safety Evaluation Report for the NFPA 805 license amendment request has been issued.

Nuclear Safety Capability Assessment Components Added to Scope of License Renewal ID Description Comments NA A level transmitter (APLT0004) sensing line for the Condensate Storage Tank Added a generic component representing this line EAHV0005 Service Water Return to Circulating Water System Valve.

Included associated piping and piping components (including the circulating water system, which returns the service water to the cooling tower basin)

EAHV0006 Service Water Return to Circulating Water System Valve.

Included associated piping and piping components (including the circulating water system, which returns the service water to the cooling tower basin)

PAP01 Non-safety Aux Feedwater Pump Included associated piping and piping components TKH2102A/B/C and PSEKH2101A/B/C Nitrogen Storage Tanks and associated Rupture Discs Included associated piping and piping components to connect the nitrogen storage tanks (service gas subsystem) to the compressed air system as a backup air supply.

N/A Nitrogen Storage Tank Foundation and Pipe Trench Included the nitrogen storage tank foundation and pipe trench to provide support, shelter, and protection for the compressed air system additions.

Comparison of BTP APCSB 9.5-1, Appendix A to NFPA 805 In addition to the Nuclear Safety Capability Assessment equipment, structures and components were put into the scope of License Renewal for fire protection based on the requirements of Branch Technical Position APCSB 9.5-1, Appendix A, and Callaway's commitments to them. NFPA 805 has similar requirements for this type of equipment. The table below provides a summary.

ULNRC-06114 April 15, 2014 Page 6 of 30 Comparison of BTP APCSB 9.5-1, Appendix A to NFPA 805 Equipment APCSB 9.5-1, App. A, Section NFPA 805 Section Lighting D.5 Not Applicable1 Communication D.5 3.4.6 Detection E.1 3.8 Suppression E.2, E.3, E.4, E.5, E.6 3.5, 3.6, 3.7, 3.9, 3.10 Drains to remove fire fighting water D.1(i) 4.3 Ventilation to remove smoke, etc.

D.1(i) 3.11.3(2)

Fire Barrier Floors, Walls, and Ceilings D.1(j) 3.11.2 Fire Doors D.1(j) 3.11.3(1)

Fire Dampers D.1(j) 3.11.3(2)

Penetration Seals D.1(j) 3.11.4 Coatings/Wraps D.1, D.3 3.11.5 1 NFPA 805 includes lighting in section 1.5.3 however, 10 CFR 50.48(c)(2)(i) excluded the Life Safety Goal, Objectives, and Criteria of NFPA 805 Chapter 1.5.3. Note, however, that emergency lighting in the control room is included in the scope of NFPA 805.

ULNRC-06114 April 15, 2014 Page 7 of 30 DETAILED RESULTS In the original fire protection program, construction features, detection, suppression, and ventilation are discussed for each fire area in the Fire Hazards Analysis (FSAR Appendix 9.5B). In the NFPA 805 program, these are addressed in the Fire Safety Analysis for each fire area, which are documented in calculations rather than the FSAR. The following fire area descriptions identify changes to LRA tables based on NFPA 805 Fire Safety Analysis changes to the structural barriers (concrete elements or masonry walls), structural barrier features (fire rated doors, fire barrier penetration seals, etc.) and mechanical barrier features (dampers). A generic NFPA 805 barrier changes table has been provided in to this gap analysis to demonstrate how different configurations of barriers and associated barrier features in fire areas were considered. Attachment 1 identifies and compares NFPA 805 functions and inspection/monitoring considerations with License Renewal functions and inspection/monitoring considerations.

Some License Renewal fire protection components are represented by generic components. These include fire barrier floors, walls, and ceilings, which are listed as concrete elements; fire barrier penetration seals; electrical raceways (wraps); and cementitious coatings. These were defined for all structures within the scope of License Renewal, and will be implemented at the Aging Management Program (AMP) level.

1. Reactor Building The Reactor Building is a single fire area in both programs. There were no differences in the fire areas between the original fire protection program and the NFPA 805 program. No components were identified which must be added to or removed from the scope of License Renewal for the NFPA 805 program in the Reactor Building. The only fire barrier door, which is between the tendon access gallery and the Auxiliary Building, was reassigned from the Reactor Building to the Auxiliary Building.

Reactor Building Fire Barrier LRA Changes Table 2.4-1 and Table 3.5.2-1 Reactor Building - Fire Barrier Doors Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 1

LRA Table 3.5.2-1 Reactor Building - Concrete Elements Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 2

Notes:

1. The License Renewal fire barrier intended function was removed from the emergency airlock hatch because it no longer has an NFPA 805 rated fire barrier

ULNRC-06114 April 15, 2014 Page 8 of 30 function. It remains within the scope of License Renewal based on other License Renewal intended functions. In addition, one Reactor Building door (the tendon gallery fire barrier door) was shown deleted in LRA Table 2.4-1 and Table 3.5.2-1.

This door retained its fire barrier function, but was reassigned to the Auxiliary Building.

2. All Reactor Building exterior concrete elements in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. These components remain within the scope of License Renewal based on other License Renewal intended functions.
2. Control Building There are no differences in the fire areas between the original fire protection program and the NFPA 805 program. The Halon suppression subsystem for the control room cable trenches, SKC07, is not required by the NFPA 805 program. The components comprising SKC07 were removed from the scope of License Renewal. One damper was identified which was added to the scope of License Renewal. Several dampers and doors were identified which are not credited in the NFPA 805 program, and were removed from the scope of License Renewal or remained in scope but have their fire barrier function removed. The dampers and doors that were removed are associated with several small rooms housing DC batteries and chargers. In the original fire protection program, each room was treated as a separate fire area. In the NFPA 805 program, these rooms were analyzed as a single area, so the internal barriers were not credited. The following tables summarize the changes to components in the Control Building.

Control Building Halon System Changes ID Description Comments SKC07 Control Room Cable Trenches and Trays Halon System Remove Halon cylinders TKC11, TKC12, TKC17, and TKC18, and all valves and piping associated with these cylinders from the scope of License Renewal Control Building Damper and Fire Barrier Door License Renewal Scope Changes ID Description Notes GKD0245 Control Bldg Supply Air Unit to Switchgear Room 1 Upstream Fire Damper 1

GKD0042 Control Bldg Switchgear Room 3/Elec Equip Room Supply Air Fire Damper 2

GKD0043 Control Bldg Switchgear Room 4/Elec Equip Room Supply Air Fire Damper 2

GKD0044 Control Bldg Switchgear Room 1/Switchgear Room 3 Supply Air Fire Damper 2

GKD0045 Control Bldg Switchgear Room 1/Elec Equip Room Supply Air Fire Damper 2

ULNRC-06114 April 15, 2014 Page 9 of 30 GKD0046 Control Bldg Battery Room 4/Elec Equip Room Exhaust Air Fire Damper 2

GKD0048 Control Bldg Battery Room 1/Elec Equip Room Exhaust Air Fire Damper 2

GKD0050 Control Bldg Switchgear Room 4/Battery Room 4 Air Xfr Fire Damper 2

GKD0051 Control Bldg Switchgear Room 2/Battery Room 2 Air Xfr Fire Damper 2

GKD0052 Control Bldg Switchgear Room 1/Battery Room 1 Air Xfr Fire Damper 2

GKD0053 Control Bldg Switchgear Room 3/Battery Room 3 Air Xfr Fire Damper 2

GKD0055 Control Bldg Battery Room 1/Room 3 Elec Equipment A/C A Return Fire Damper 3

GKD0056 Control Bldg Battery Room 3/Cor Air Return Fire Damper 3

GKD0058 Control Bldg Switchgear Room 3/Elec Equipment Room A/C Unit Return Fire Damper 3

GKD0062 Elec Equipment Room/Battery Room 3 A/C Unit A Supply Air Fire Damper 3

GKD0063 Elec Equipment Room/Battery Room 1 A/C Unit A Supply Air Fire Damper 3

GKD0064 Elec Equipment Room & Switchgear Room 3 Supply Air Fire Damper 3

GKD0069 Control Bldg Switchgear Room 2/Elec Equipment Room A/C Return Fire Damper 3

GKD0070 Control Bldg Battery Room 4/Room 2 Elec Equipment A/C Unit B Return Fire Damper 3

GKD0071 Control Bldg Battery Room 2/Cor Air Return Fire Damper 3

GKD0075 Elec Equipment Room & Switchgear Room 2 Supply Air Fire Damper 3

GKD0077 Elec Equipment Room/Battery Room 2 A/C Unit B Supply Air Fire Damper 3

GKD0078 Elec Equipment Room/Battery Room 4 A/C Unit B Supply Air Fire Damper 3

GKD0240 Control Room Press Fan B Discharge Fire Damper 3

GKD0242 Control Room Press Fan A Discharge Fire Damper 3

GKD0247 Control Bldg Supply Air to Switchgear Room Fire Damper 2

GKD0289 HP Audio/Video Storage Room Fire Damper 2

GKD0290 Control Bldg Cor/Decon Sink Area Wall Fire Damper 2

GKD0291 Control Bldg Cor/Laundry & Respro Decon Area Wall Fire Damper 2

GKD0302 Count Room/Control Bldg Cor Air in Damper 2

DSK31032 Door from Corridor #2 to Stair CC-1 4

DSK31033 Door from Corridor to Stair CC-1 4

DSK31034 Door from Corridor to Stair CC-1 4

DSK31035 Door from Corridor #3 to Stair CC-1 4

DSK31036 Door from Com Corridor Lobby to Stair CC-1 4

ULNRC-06114 April 15, 2014 Page 10 of 30 DSK31037 Door from Corridor #2 to Stair CC-1 4

DSK31038 Door from Stair CC-1 to Stair CC-2 4

DSK31039 Door from Stair CC-1 to Corridor 4

DSK32011 Door from ALARA Briefing Room to Stairs C-1 4

DSK33041 Door from Com Corridor General Floor Area to Corridor 4

DSK33071 Fire Door to Combustible Liquid Storage Room 4

DSK34032 Door from S. Non Vital AC SWGR to SWBD Room 4 4

DSK34033 Door from Non Vital AC SWGR to SWBD Room 2 4

DSK34042 Door from SWBD Room 2 to SWBD Room 4 4

DSK34051 Door from Battery Room 4 to SWBD Room 4 4

DSK34072 Door from Battery Room 1 to SWBD Room 1 4

DSK34082 Door from SWBD Room 1 to SWBD Room 3 4

DSK34092 Door from N. Non Vital SWGR to SWBD Room 1 4

DSK34093 Door from N. Non Vital AC SWGR to SWBD Room 3 4

DSK34101 Door from SWBD Room 2 to Battery Room 2 4

DSK34141 Door from Battery Room 3 to SWBD Room 3 4

DSK36141 Door from Corridor #3 to Com Corridor General Floor Area 4

Notes:

1. Dampers added to the scope of License Renewal
2. Dampers removed from the scope of License Renewal
3. Dampers with the License Renewal fire barrier function removed
4. Doors with the License Renewal fire barrier function removed Control Building Fire Barrier LRA Changes LRA Table 3.3.2-11 Control Building HVAC System - Dampers Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes 1

Table 3.5.2-2 Control Building - Fire Barrier Doors Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes 2

LRA Table 3.5.2-2 Control Building - Concrete Elements Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 3

ULNRC-06114 April 15, 2014 Page 11 of 30 LRA Table 3.5.2-2 Control Building - Fire Barrier Penetration Seals Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes Yes 4

Notes:

1. The License Renewal fire barrier intended function was removed from several dampers because they no longer have an NFPA 805 rated fire barrier function.

This resulted in some dampers being removed from the scope of License Renewal and some remaining in the scope of License Renewal. Therefore, no LRA changes were required for the Control Building HVAC system.

2. The License Renewal fire barrier intended function was removed from several doors because they no longer have an NFPA 805 rated fire barrier function. This resulted in some doors being removed from the scope of License Renewal and some remaining in the scope of License Renewal for other intended functions.

Therefore, no LRA changes were required for the Control Building fire barrier doors.

3. All Control Building exterior concrete elements in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. These components remain within the scope of License Renewal based on other License Renewal intended functions.
4. All Control Building fire barrier penetration seals in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. These seals were removed from the scope of License Renewal.
3. Diesel Generator Building There are two fire areas in the Diesel Generator Building, one for each diesel generator.

There were no differences in the fire areas between the original fire protection program and the NFPA 805 program. No components were identified which must be added to the scope of License Renewal for the NFPA 805 program in the Diesel Generator Building.

However, the SKC26 suppression subsystem, East Diesel Generator Preaction Sprinkler System, and the SKC27 suppression subsystem, West Diesel Generator Preaction Sprinkler System, are not required by the NFPA 805 program. The fire protection (pressure boundary) function was removed from these components, but they remain in the scope of License Renewal for (a)(2). The following table summarizes the components currently in the scope of License Renewal but which are not required by the NFPA 805 program.

ULNRC-06114 April 15, 2014 Page 12 of 30 Diesel Generator Building Preaction Sprinkler System Changes ID Description Comments SKC26 East Diesel Generator Preaction Sprinkler System Remove fire protection (pressure boundary) function from all components downstream of valve KCXV0561; add (a)(2) function for spatial interaction SKC27 West Diesel Generator Preaction Sprinkler System Remove fire protection (pressure boundary) function from all components downstream of valve KCXV0562; add (a)(2) function for spatial interaction Diesel Generator Building Fire Barrier LRA Changes LRA Table 3.3.2-16 Diesel Generator Building HVAC System - Dampers Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes 1

LRA Table 3.5.2-5 Diesel Generator Building - Concrete Elements Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 2

LRA Table 3.5.2-5 Diesel Generator Building - Fire Barrier Penetration Seals Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 3

Notes:

1. There were no changes to the Diesel Generator Building HVAC system.
2. All Diesel Generator Building exterior concrete elements in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. These components remain within the scope of License Renewal based on other License Renewal intended functions.
3. All Diesel Generator Building exterior fire barrier penetration seals in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. The Diesel Generator Building exterior fire barrier penetration seals were removed from the scope of License Renewal. The Diesel Generator Building interior fire barrier penetration seals remain within the scope of License Renewal.

ULNRC-06114 April 15, 2014 Page 13 of 30

4. Auxiliary Building The only change to the Auxiliary Building fire areas is the Auxiliary Shutdown Panel room.

In the original program, this room comprises one fire area. In the NFPA 805 program, it is divided into two fire areas: one for train A equipment and one for train B equipment. In the current fire protection program, the two halves of the room are divided by a rated fire wall with fire doors, as is the case in the NFPA 805 program. Thus, this difference has no impact on components within the scope of License Renewal. No components were identified which must be added to the scope of License Renewal for the NFPA 805 program in the Auxiliary Building. Two suppression subsystems, SKC22, Auxiliary Feedwater Pump Manual Water Spray System, and SKC36, South Cable Chase Wet Pipe Sprinkler System, are not credited in the NFPA 805 program. The fire protection (pressure boundary) function was removed from these components, but remains in the scope of License Renewal for (a)(2). This change required the addition of leakage boundary (spatial) as a function of the Fire Protection System in LRA Section 2.3.3.20 and Table 2.3.3-20. One damper and several doors were identified which had a fire barrier function added. Several dampers which are not credited in the NFPA 805 program were removed from the scope of License Renewal. The following tables summarize the component changes in the Auxiliary Building.

Auxiliary Building Suppression System Changes ID Description Comments SKC22 Auxiliary Feedwater Pump Manual Water Spray System Remove fire protection (pressure boundary) function from all components downstream of valve KCV0730; add (a)(2) function for spatial interaction SKC36 South Cable Chase Wet Pipe Sprinkler System Remove fire protection (pressure boundary) function from all components downstream of valve KCV0437; add (a)(2) function for spatial interaction Auxiliary Building Damper and Fire Barrier Door License Renewal Scope Changes ID Description Notes GTD0014 Containment S/D Purge Exhaust Outer Containment Damper 1

GLD0016 Aux Bldg Pen Room A Exhaust to Filter Adsorber Unit Damper 2

GLD0017 MG Set Room Fan Coil Discharge Downstream Damper 2

GLD0018 MG Set Room Fan Coil Unit Suction Damper 2

GLD0019 Aux Bldg Pen Room A Air Supply Damper 2

GLD0028 Aux Bldg Pen Room B Exhaust to Filter 2

GLD0029 Aux Bldg Pen Room B Air Supply Damper 2

GLD0068 Aux Bldg El 1974 to Filter Adsorber Unit in Fire Damper 2

DSK11195 Door from Aux Bldg to Outside 3

DSK11231 Door from Passage to Letdown Heat Exchanger Room 3

ULNRC-06114 April 15, 2014 Page 14 of 30 DSK14132 Door from Aux Shutdown Panel Room to Back of ASP Room 4

DSK14133 Door from Aux Shutdown Panel Room 4

DSK31041 Door from AB Corridor to Stairs from Health Physics 4

DSK33044 Door from Com Corridor Gen Floor to AB 4

DSK36091 Door from Control Room to SAS Room 4

Notes:

1. Dampers with fire barrier function added
2. Dampers removed from the scope of License Renewal
3. Doors with fire barrier function removed
4. Doors with fire barrier function added Auxiliary Building Fire Barrier LRA Changes LRA Table 3.3.2-13 Auxiliary Building HVAC System - Dampers Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes Yes 1

LRA Table 2.3.2-4 and LRA Table 3.2.2-4 Containment Purge System - Dampers Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 1

LRA Table 2.4-3 and Table 3.5.2-3 Auxiliary Building - Fire Barrier Doors Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes Yes 2

LRA Table 3.5.2-3 Auxiliary Building - Concrete Elements, Hatches, and Hatches and Plugs Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 3

LRA Table 3.5.2-3 Auxiliary Building - Fire Barrier Penetration Seals Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 4

ULNRC-06114 April 15, 2014 Page 15 of 30 Notes:

1. The License Renewal fire barrier intended function was removed from several dampers because they no longer have an NFPA 805 rated fire barrier function.

This resulted in some dampers being removed from the scope of License Renewal.

The License Renewal fire barrier intended function was added to one damper in the Containment Purge system in the Auxiliary Building.

2. All Auxiliary Building exterior fire barrier doors in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. These Auxiliary Building components remain within the scope of License Renewal based on other License Renewal intended functions. The License Renewal fire barrier intended function was added to several other doors currently within the scope of License Renewal.
3. All Auxiliary Building exterior concrete elements, hatches, and hatches and plugs in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. These Auxiliary Building components remain within the scope of License Renewal based on other License Renewal intended functions.
4. All Auxiliary Building fire barrier penetration seals in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. The external fire barrier penetration seals were removed from the scope of License Renewal. The Auxiliary Building interior fire barrier penetration seals remain within the scope of license renewal.
5. Laundry Decontamination Facility The Laundry Decontamination Facility, which is treated as part of the Auxiliary Building in LRA Section 2.4.3, consists of only one fire area. The NFPA 805 program does not consider the Laundry Decontamination Facility to be a power block structure. There are no differences between the original fire protection program and the NFPA 805 program. No components were identified which must be added to the scope of License Renewal for the NFPA 805 program in the Laundry Decontamination Facility. The suppression components in the Laundry Decontamination Facility are not required by the NFPA 805 program. These components were removed from the scope of License Renewal. The following table summarizes the components currently in the scope of License Renewal but which are not required by the NFPA 805 program.

Laundry Decontamination Facility Suppression System Changes ID Description Comments NA Laundry Decontamination Facility Suppression System Remove all components downstream of valve KCV0580 from the scope of License Renewal.

ULNRC-06114 April 15, 2014 Page 16 of 30

6. RAM Storage Building The RAM Storage Building, which is treated as part of the Auxiliary Building in LRA Section 2.4.3, consists of one fire area. The NFPA 805 program does not consider the RAM Storage Building to be a power block structure. There are no differences in the fire areas between the original fire protection program and the NFPA 805 program. No components were identified which must be added to the scope of License Renewal for the NFPA 805 program in the RAM Storage Building. The fire suppression components in the RAM Storage Building are not required by the NFPA 805 program. These components were removed from the scope of License Renewal. The following table summarizes the components currently in the scope of License Renewal but which are not required by the NFPA 805 program.

RAM Storage Building Suppression System Changes ID Description Comments NA RAM Storage Building Suppression System Remove all components downstream of valve KCV0579 from the scope of License Renewal

7. Fuel Building In the NFPA 805 program, there is now only one fire area for the entire Fuel Building. The Nuclear Safety Capability Assessment assumed a whole-room burnup level; i.e., all components and cables were assumed to fail. Thus, the fire barrier function for all the interior fire doors, dampers, walls, and seals were removed. In an evaluation of the potential for radiological release due to firefighting activities, it was determined that radioactive release performance criterion was met. Dampers that had only a fire barrier function and were no longer credited in NFPA 805 were removed from the scope of License Renewal. Dampers which have a pressure boundary function in addition to the fire barrier function remain in the scope of License Renewal, but had the fire barrier function removed. All the interior doors were removed from the scope of License Renewal as they no longer have a fire barrier function or any other license renewal intended function. No components were identified which must be added to the scope of License Renewal for the NFPA 805 program in the Fuel Building. One suppression subsystem, SKC25, Fuel Building Railroad Bay Preaction Sprinkler System, is not required by the NFPA 805 program. The fire protection (pressure boundary) function was removed from these components, but they remain in the scope of License Renewal for (a)(2). The following tables summarize the changes in the Fuel Building.

Fuel Building Suppression System Changes ID Description Comments SKC25 Fuel Building Railroad Bay Preaction Sprinkler System Remove fire protection (pressure boundary) function from all components downstream of valve KCV0076; add (a)(2) function for spatial interaction

ULNRC-06114 April 15, 2014 Page 17 of 30 Fuel Building Damper and Fire Barrier Door License Renewal Scope Changes ID Description Notes GGD0007 FB Air Supply Header Electrical Equip Room Fire Damper 1

GGD0008 SFP Cooling Pump Rooms A&B Main Air Supply Fire Damper 1

GGD0009 SFP Cooling Pump Rooms A/B Main Air Supply Fire Damper 1

GGD0010 FB Air Supply Sys Supply Header SFP Area Fire Damper 1

GGD0011 Emergency Exhaust Filter Adsorber Room A Out Fire Damper 2

GGD0012 FB Elec Equip Room/Cask Shipping & Receiving Area Fire Damper 1

GGD0013 FB Elec Equip Room/HVAC Equipment Room Fire Damper 1

GGD0014 SFP Pump Room A/Cask Shipping & Receiving Area Fire Damper 1

GGD0016 SFP Pump Room B/Cask Shipping & Receiving Area Fire Damper 1

GGD0047 FB Air Sys Supply Header Emergency Exhaust Room B Fire Damper 1

GGD0048 FB Air Sys Suction Header SFP Area Fire Damper 1

GGD0049 FB Normal Exhaust Air Sys Suction Header Equip Drain Sump Fire Damper 1

GGD0050 FB Normal Exhaust Air Sys Suction Header Floor Drain Sump Fire Damper 1

GGD0051 FB Normal Exhaust Air Sys Suction Header Equip Drain Sump Fire Damper 1

GGD0052 FB Normal Exhaust Air Sys Suction Header Floor Drain Sump Fire Damper 1

GGD0053 FB Normal Exhaust Air Sys Suction Header Equip Drain Sump Fire Damper 1

GGD0054 FB Normal Exhaust Air Sys Suction Header Floor Drain Sump Fire Damper 1

GGD0055 FB Normal Exhaust Air Sys Suction Header Equip Drain Sump Fire Damper 1

GGD0056 FB Emergency Filter ADS Units A&B Cross Connect Fire Damper 2

GGD0057 FB Emergency Filter ADS Units A&B Cross Connect Fire Damper 2

GGD0058 FB Air Sys Supply Header Emergency Exhaust Room A Fire Damper 1

GGD0061 Emergency Exhaust Filter Adsorber Room B Out Fire Damper 2

GGD0062 FB Air Sys Return Header SFP Area Fire Damper 1

GGD0063 FB Air Sys Supply Header SFP Area Fire Damper 1

GGD0064 FB Air Sys Supply Header SFP Area Fire Damper 1

GGD0065 FB Air Sys Supply Header SFP Area Fire Damper 1

GGD0066 FB Air Sys Supply Header SFP Area Fire Damper 1

GGD0067 Emergency Exhaust Air Sys B Suction Header Aux/FB Fire Damper 2

GGD0068 Emergency Exhaust Air Sys Suction Header Aux/FB Fire Damper 2

DSK6104 FB Door From West Fuel Pool Heat Exchanger Room to 3

ULNRC-06114 April 15, 2014 Page 18 of 30 1

Laydown DSK6105 1

FB Door From East Fuel Pool Heat Exchanger Room to Laydown 3

DSK6202 1

FB Door From Electric Equip Room to Passage 3

DSK6202 2

FB Door From Electric Equip Room to FB Supply Air 3

DSK6303 1

Door From Emergency Exhaust Filter Absorber B to Gen Floor 3

DSK6304 1

Door From Emergency Exhaust Filter Absorber A to Gen Floor 3

Notes:

1. Dampers removed from the scope of License Renewal
2. Dampers which had the fire barrier function removed
3. Doors removed from the scope of License Renewal Fuel Building Fire Barrier LRA Changes LRA Table 3.3.2-14 Fuel Building HVAC System - Dampers Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes 1

LRA Table 2.4-10 and Table 3.5.2-10 Fuel Building - Fire Barrier Doors Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes Yes 2, 3 LRA Table 3.5.2-10 Fuel Building - Concrete Elements Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 4

Notes:

1. The License Renewal fire barrier intended function was removed from several dampers because they no longer have an NFPA 805 rated fire barrier function.

This resulted in some dampers being removed from the scope of License Renewal and some remaining in the scope of License Renewal. No LRA changes were required for the Fuel Building HVAC system.

2. All Fuel Building fire barrier doors were removed from the scope of License Renewal because they no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. Some doors remain in the scope of License Renewal with other intended functions.

ULNRC-06114 April 15, 2014 Page 19 of 30

3. All fire barrier doors between the Fuel Building and the Auxiliary Building with a fire barrier License Renewal intended function are assigned to the Auxiliary Building.
4. All Fuel Building exterior concrete elements in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. These Fuel Building exterior concrete elements remain within the scope of License Renewal based on other License Renewal intended functions.
8. Radwaste Building The Radwaste Building consists of only one fire area. In the original fire protection program, only the Radwaste Tunnel is included in this fire area. In the NFPA 805 program, this fire area includes the tunnel and the entire Radwaste Building. The Radwaste Building contains no equipment required to meet the Nuclear Safety Capability Assessment. The fire suppression system and internal fire barriers are not required in the NFPA 805 program. In an evaluation of the potential for radiological release due to firefighting activities, it was determined that radioactive release performance criterion was met.

Therefore, the fire barrier function for all the interior fire barrier doors, dampers, walls, and fire barrier penetration seals was removed. The six dampers which have only a fire barrier function were no longer required for NFPA 805 and therefore removed from the scope of License Renewal. In addition, generic components such as pipe caps and fire hose fittings associated with the filter adsorber units in the Radwaste Building were removed from the scope of License Renewal. No components were identified which must be added to the scope of License Renewal for the NFPA 805 program in the Radwaste Building. The SKC33 suppression subsystem in the Radwaste Building is not required by the NFPA 805 program. These components were removed from the scope of License Renewal. The following tables summarize the changes in the Radwaste Building.

Radwaste Building Components Removed From the Scope of License Renewal.

ID Description Comments SKC33 Radwaste Building Suppression System Remove all components downstream of valve KCV0347 from the scope of License Renewal.

NA Generic components associated with the Radwaste Building Exhaust Filter Adsorber Unit Components include a fire hose fitting, pipe cap, piping, and a reducer.

Radwaste Building (RWB) Damper and Fire Barrier Door License Renewal Scope Changes ID Description Notes GHD0002 RWB EL 2000 Air Supply Fire Damper 1

GHD0003 RWB EL 1976 Air Supply Fire Damper 1

GHD0009 RWB EL 2000 Air Return Fire Damper 1

GHD0010 RWB EL 1976 Air Return Fire Damper 1

GHD0011 RWB Access Tunnel XFR Fan Out Fire Damper 1

ULNRC-06114 April 15, 2014 Page 20 of 30 GHD0012 Rad Pipe Tunnel Air Return Fire Damper 1

DSK71131 Door from Tunnel to General Area 2

DSK71141 RWB Door From Gen. Area to Central Stairs 2

DSK71142 RWB Door From Central Stairs to Gen. Floor Area 2

DSK71144 RWB Door From Central Stair to Vestibule 2

DSK71321 RWB Door From East Stairs to Corridor 2

DSK71322 RWB Door From East Stairs to Corridor 2

DSK71324 RWB Door From East Stair to Gen. Floor Area 2

DSK72281 RWB Door From Drywaste Compactor to Corridor 2

DSK72311 RWB Door From Subcoolers Condenser Room to Stairs 2

Notes:

1. Dampers removed from the scope of License Renewal
2. Fire Barrier Doors removed from the scope of License Renewal Radwaste Building Fire Barrier LRA Changes LRA Table 2.3.3-17 and Table 3.3.2-17 Radwaste Building HVAC System - Dampers and Piping Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes Yes 1

LRA Table 2.4-9 and Table 3.5.2-9 Radwaste Building - Fire Barrier Doors Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes Yes 2

LRA Table 2.4-9 and Table 3.5.2-9 Radwaste Building - Coatings/Wraps Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes Yes 2

LRA Table 2.4-9 and Table 3.5.2-9 Radwaste Building - Fire Barrier Penetration Seals Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes Yes 2

ULNRC-06114 April 15, 2014 Page 21 of 30 LRA Table 2.4-9 and Table 3.5.2-9 Radwaste Building - Concrete Elements Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 3

Notes:

1. The Radwaste Building HVAC system was removed from the scope of License Renewal.
2. All Radwaste Building fire barrier doors, coatings/wraps, and fire barrier penetration seals were removed from the scope of License Renewal because they no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. Some doors remain in the scope of License Renewal with other intended functions.
3. All Radwaste Building concrete elements no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. These Radwaste Building concrete elements remain within the scope of License Renewal based on other License Renewal intended functions.
9. Turbine Building and Communications Corridor Two fire areas are defined for the Turbine Building in the original fire protection program.

The first is a stairwell adjacent to the Auxiliary Building, and the second encompasses the area from the Auxiliary Building wall to 50 feet north of the Auxiliary Building wall. The remaining area in the Turbine Building is not included in the original FSAR fire hazards analysis. The Communications Corridor consists of one fire area, separate from the Turbine Building.

Under the NFPA 805 program, the entire Turbine Building is a single fire area, and includes the Communications Corridor.

The only components identified for the NFPA 805 program in the Turbine Building and Communications Corridor which were added to the scope of License Renewal are the standpipe and hose stations in the Turbine Building. This change resulted from the addition of the Turbine Building and Communications Corridor as a power block structure.

Some fire suppression components in the Turbine Building which were originally in the scope of License Renewal are not required by the NFPA 805 program. These include SKC47, BOP Computer Room Sprinkler System; SKC08, Lube Oil Storage Tank Wet Pipe Sprinkler System; SKC10, Lube Oil Reservoir Room Wet Pipe Sprinkler System, and SKC11, the deluge system for the Hydrogen Seal Oil Unit. These were removed from the scope of License Renewal.

Only three dampers in the Turbine Building which were originally in the scope of License Renewal are required by the NFPA 805 program. The rest were removed from the scope of License Renewal. Five dampers in the Turbine Building HVAC system are located in the Auxiliary Building and are safety-related. These five dampers remain in scope, but do not have a fire barrier function.

ULNRC-06114 April 15, 2014 Page 22 of 30 Only one door in the Turbine Building remains in the scope of License Renewal as a fire barrier. The remaining doors are not required by the NFPA 805 program. These remaining doors, except for two generic doors with a Shelter, Protection function, were removed from the scope of License Renewal.

The following tables summarize the License Renewal changes to components in the Turbine Building due to adoption of the NFPA 805 program.

Turbine Building Components Added to the Scope of License Renewal ID Description Comments All standpipe and hose stations in the Turbine Building KCHR0070, KCHR0073, KCHR0074, KCHR0075, KCHR0076, KCHR0077, KCHR0080, KCHR0081, KCHR0082, KCHR0083, KCHR0084, KCHR0085, KCHR0086, KCHR0087, KCHR0088, KCHR0089, KCHR0090, KCHR0091, KCHR0092, KCHR0093, KCHR0096, KCHR0097, KCHR0098, and KCHR0099, and associated piping and valves - add to the scope of License Renewal Turbine Building Components Removed From the Scope of License Renewal ID Description Comments SKC08 Lube Oil Storage Tank Wet Pipe Sprinkler System Remove all components downstream of valve KCV0038 from the scope of License Renewal SKC10 Lube Oil Reservoir Room Wet Pipe Sprinkler System Remove all components downstream of valve KCV0029 from the scope of License Renewal SKC47 BOP Computer Room Sprinkler System Remove all components downstream of valve KCV0479 from the scope of License Renewal SKC11 Hydrogen Seal Oil Deluge System Remove all components downstream of valve KCV0063 from the scope of License Renewal

ULNRC-06114 April 15, 2014 Page 23 of 30 Turbine Building Damper and Fire Barrier Door License Renewal Scope Changes ID Description Notes GED0023 TB Computer Room Fan Coil Units Air Return Fire Damper 1

GED0024 TB Computer Rm Fan Coil Units To Computer Rm Fire Damper 1

GED0025 TB Communications Corridor / Conference Room Fire Damper 1

GED0026 TB Conference Room / Work Control Area Fire Damper 1

GED0031 TB PK Battery Room/Turbine Building Fire Damper 1

GED0032 TB PJ Battery Room Fire Damper 1

GED0053 TB Lube Oil Room Supply Fire Damper 1

GED0054 TB Lube Oil Room Roof Exhaust Fan Suction Fire Damper 1

GED0055 TB PJ Battery Rm Chilled Wtr Coil to Battery Rm Fire Damper 1

GED0056 TB PK Battery Rm Chilled Wtr Coil to Battery Rm Fire Damper 1

GED0058 Field Office/Communications Corridor Air Return Fire Damper 1

GED0059 Comp Rm/Communications Corridor Air Return Fire Damper 1

GED0060 TB Elevator Mach Room EL 2078 Air Supply Fire Damper 1

GED0061 TB Elevator Mach Room EL 2078 Air Return Fire Damper 1

GED0062 TB Elevator Mach Room Air Supply Fire Damper 1

GED0071 TB Lube Oil Room Supply Air Unit Discharge Fire Damper 1

GED0072 TB Lube Oil Room Exhaust Fan Suction Fire Damper 1

GED0073 Communications Corridor EL 2000 Air Supply Fire Damper 1

GED0074 TB Elevator Mach Room Exhaust Fan Suction Fire Damper 1

GED0076 Communications Corridor EL 2032 Air Supply Fire Damper 1

GED0077 Comm Cor Supply Unit To Comm Cor EL 2032 Fire Damper 1

GED0078 Comm Cor Supply Unit To Comm Cor EL 2032 Fire Damper 1

GED0126 TB Radio Room/Battery Room Air Supply Fire Damper 1

GED0129 TB Battery Room Duct Heater Discharge Fire Damper 1

GED0130 TB Radio Room Air Return Fire Damper 1

GED0133 TB Battery Room Exhaust Fan Suction Fire Damper 1

GED0138 Communications Corridor/Restroom Fire Damper 1

GED0142 TB Battery Room No 1 Exhaust Fan Suction Fire Damper 1

GED0143 TB Battery Room 1 Air Supply Fire Damper 1

GED0144 TB Battery Room 1 Air Return Fire Damper 1

GED0148 TB Battery Room 1 Air Supply Fire Damper 1

DSK41012 TB Door from Gen. Floor To Southwest Stairs 2

DSK41013 Door from Communications Corridor to Southwest stairs 2

DSK41014 TB Door to the T-1 Stairs (South) 2 DSK41016 TB Door from S. West Stairs to Gen Floor Area 2

DSK41018 TB Door from Northwest Stairs to CC Gen. Floor 2

DSK41019 TB Door from CC Gen Floor to S. West Stairs 2

DSK43081 TB Door from Truck Bay to Lube Oil Tanks 2

DSK43091 TB Door from Gen. Floor to West Stair 2

DSK43093 TB Door from West Stairs to Gen Floor Area 2

DSK43094 TB Door to Stairwell T-2 2

DSK43101 TB Door from Gen. Floor to Northwest Stair 2

DSK43103 TB Door from General Floor to North West Stairs 2

DSK43104 TB Door from Gen. Floor to West Stairs 2

ULNRC-06114 April 15, 2014 Page 24 of 30 DSK43121 TB Door from R/R Bay to NE Stairwell 2

DSK43123 TB Door from Gen. Floor to NE Stairs 2

DSK43124 TB Door from Gen Floor to East Stairs 2

DSK43131 TB Door from Gen. Floor to East Stairs 2

DSK43133 TB Door from Gen. Floor to SE Stairs 2

DSK43134 TB Door from Gen. Floor to East Stairs 2

DSK43141 TB Door from Truck Bay to Southeast Stairs 2

DSD43143 TB Door from Southeast Stairs to Gen Floor 2

DSK43144 TB Door from Gen. Floor to South Stairs 2

DSK43145 TB Door from Gen. Floor to SE Stairs 2

DSK43171 TB Door from Process Sample Lab to Gen Floor 2

DSK44021 TB Door from East Battery Room to Gen. Floor 2

DSK44022 TB Door from East Battery Room to Gen Floor 2

DSK44031 TB Door from Lube Oil Res. Room to Gen. Floor 2

DSK44041 TB Door from West Battery Room to Gen Floor Area 2

DSK45041 Door from EHC Control Cabinet Room to General Floor A 2

DSK45042 TB Door from EHC Control Cab Room to Gen Floor 2

Notes:

1. Dampers removed from the scope of License Renewal
2. Doors removed from the scope of License Renewal Turbine Building Fire Barrier LRA Changes LRA Table 3.3.2-18 Turbine Building HVAC System - Dampers Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 1

LRA Table 3.5.2-4 Turbine Building - Fire Barrier Doors Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes 2

LRA Table 2.4-4 and Table 3.5.2-4 Turbine Building - Coatings/Wraps Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes Yes 3

ULNRC-06114 April 15, 2014 Page 25 of 30 LRA Table 2.4-4 and 3.5.2-4 Turbine Building - Concrete Elements Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 4

LRA Table 2.4-4 and Table 3.5.2-4 Turbine Building - Hatches and Plugs Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 5

LRA Table 2.4-4 and Table 3.5.2-4 Turbine Building - Metal Siding Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 5

Notes:

1. The License Renewal fire barrier intended function was removed from several dampers because they no longer have an NFPA 805 rated fire barrier function.

This resulted in some dampers being removed from the scope of License Renewal and some remaining in the scope of License Renewal for other license renewal intended functions.

2. All but one Turbine Building fire barrier doors were removed from the scope of License Renewal because they no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. The one remaining fire barrier door is the door between the Turbine Building and the Auxiliary Boiler Room.
3. All Turbine Building fire barrier coatings/wraps were removed from the scope of License Renewal because they no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function.
4. All turbine building exterior concrete elements in environment of atmosphere/weather no longer have a rated fire barrier intended function. The one remaining rated fire barrier is the masonry block wall between the Turbine Building and the Auxiliary Boiler Room.
5. All Turbine Building hatches and plugs and metal siding no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. These hatches and plugs and metal siding remain within the scope of License Renewal based on other License Renewal intended functions.
10. Auxiliary Boiler Room The Auxiliary Boiler Room, which is treated as part of the Turbine Building in LRA Section 2.4.4, consists of one fire area. There were no differences in the fire areas between the original fire protection program and the NFPA 805 program. This room contains no

ULNRC-06114 April 15, 2014 Page 26 of 30 equipment required for the Nuclear Capability Safety Assessment. The SKC09 fire suppression subsystem is not required by the NFPA 805 program. The suppression system was removed from the scope of License Renewal as a result of the NFPA 805 program.

Auxiliary Boiler Room Suppression System Changes ID Description Comments SKC09 Auxiliary Boiler Room Suppression Systems Remove all components downstream of valve KCV0028 from the scope of License Renewal.

11. ESW Pump House In the original fire protection program, the ESW Pump House is a single fire area with two fire zones. For License Renewal, the ESW Pump House is treated as part of ESW Structures. In the NFPA 805 program, it is divided into two areas, one for each room (train), which correspond to the original fire zones. The two rooms are divided by a fire wall. This difference has no impact on License Renewal because the wall was already in scope as a fire barrier. All ESW Pump House exterior fire barrier doors, exterior concrete elements, and exterior fire barrier penetration seals in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. No components were identified which must be added to or removed from the scope of License Renewal for the NFPA 805 program in the ESW Pump House.

ESW Structures Fire Barrier Door License Renewal Scope Changes ID Description Notes Generic Exterior ESW Structure Fire Barrier Doors 1

Notes:

1. Doors with fire barrier function removed.

ESW Structures Fire Barrier LRA Changes LRA Table 2.4-11 and Table 3.5.2-11 ESW Structures - Fire Barrier Doors Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 1

LRA Table 3.5.2-11 ESW Structures - Concrete Elements Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 2

ULNRC-06114 April 15, 2014 Page 27 of 30 LRA Table 3.5.2-11 ESW Structures - Fire Barrier Penetration Seals Removed From License Renewal Added to License Renewal Fire Barrier Function Removed Fire Barrier Function Added Notes Yes 3

Notes:

1. All ESW Pump House exterior fire barrier doors in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. These ESW Pump House exterior doors remain within the scope of License Renewal based on other License Renewal intended functions. The ESW Pump House interior fire barrier doors remain within the scope of license renewal.
2. All ESW Pump House exterior concrete elements in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. These ESW Pump House exterior concrete elements remain within the scope of License Renewal based on other License Renewal intended functions.
3. All ESW Pump House exterior fire barrier penetration seals in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. The ESW Pump House exterior fire barrier penetration seals were removed from the scope of license renewal. The ESW Pump House interior fire barrier penetration seals remain within the scope of license renewal.
12. Ultimate Heat Sink Cooling Tower The Ultimate Heat Sink Cooling Tower, which is treated as part of ESW Structures, is a single fire area with two fire zones. In the NFPA 805 program, it is divided into two areas which correspond to the original fire zones, one for the north side of the cooling tower and the attached electrical equipment rooms, and one for the south side of the cooling tower and attached electrical equipment rooms. This difference has no impact on License Renewal because the wall between the rooms was already in scope as a fire barrier. All Ultimate Heat Sink Cooling Tower exterior fire barrier doors, exterior concrete elements, and exterior fire barrier penetration seals in an environment of atmosphere/weather no longer have an NFPA 805 rated fire barrier function and therefore no longer have a License Renewal fire barrier intended function. No components were identified which must be added to or removed from the scope of License Renewal for the NFPA 805 program in the Ultimate Heat Sink Cooling Tower.
13. Yard The only Yard areas included in the original fire protection program are the areas around the Refueling Water Storage Tank, the Condensate Storage Tank, and the Emergency Diesel Fuel Oil Storage Tanks. In addition to these areas, the NFPA 805 program Yard fire area includes the Fire Water Pump House and the areas around the Circulating and Service Water Pump House, the ESF Transformer, the Main Transformers, the Main Switchyard, the Station Service Transformers, the Ultimate Heat Sink, and, generally, the

ULNRC-06114 April 15, 2014 Page 28 of 30 entire yard area. The fire barriers (such as the walls and doors in the Fire Water Pump House and the wall separating transformers) are already in scope. No components in the Yard were identified which must be added to the scope of License Renewal due to the transition to NFPA 805. The safety-related cable duct banks and access hatches had a fire barrier function added. The suppression components for XMR01, Startup Transformer; XNB01, ESF Transformer A; and XNB02, ESF Transformer B, are not required by the NFPA 805 program. These suppression subsystems are SKC16, SKC19, and SKC20, and were removed from the scope of License Renewal. The following tables summarize the changes in components in the Yard. The sump pumps in the Fire Water Pump House and for the Fire Water Storage Tanks are not required by the NFPA 805 program and were removed from the scope of License Renewal.

Yard Components which had a Fire Barrier Function Added ID Description Comments Safety-Related Cable Duct Banks and Access Hatches Added Fire Barrier function. The concrete element already had a fire barrier function, therefore no LRA change was required.

Yard Suppression System Components Changes ID Description Comments SKC16 Startup XFMR (XMR01) Water Spray System Remove all components downstream of valve KCV0464 from the scope of License Renewal SKC19 ESF XFMR A (XNB01) Water Spray System Remove all components downstream of valve KCV0463 from the scope of License Renewal SKC20 ESF XFMR B (XNB02) Water Spray System Remove all components downstream of valve KCV0463 from the scope of License Renewal Yard Components Removed from the Scope of License Renewal ID Description Comments PKC1006 Fire Water Storage Tank Sump Pump Related components removed from scope as appropriate.

PKC1008A, PKC1008B Fire Water Pump House Sump Pumps Related components removed from scope as appropriate.

ULNRC-06114 April 15, 2014 Page 29 of 30 ATTACHMENT 1 NFPA-805 Barrier Changes for License Renewal Structural Barriers (Concrete Elements or Masonry Walls)

Configuration NFPA-805 Functions License Renewal Function (Note 1)

NFPA 805 Inspection/Monitoring License Renewal Inspection/Monitoring Notes Barrier Between Fire Areas Rated Fire Barrier Fire Barrier (Rated)

Existing Fire Protection Program M26 Fire Protection and S6 Structures Monitoring Fire Area Exterior Barrier or Fire Modeling Credited Barrier Non-Rated Fire Barrier Shelter, Protection, Structural Support Design Control /

Periodic Inspection /

Monitoring of Barrier S6 Structures Monitoring (or S5 Masonry Walls) 6 Interior Barrier in Single Fire Area None None None None 2

Structural Barrier Features (Note 4)

Configuration NFPA-805 Functions License Renewal Function (Note 1)

NFPA 805 Inspection/Monitoring License Renewal Inspection/Monitoring Notes Feature Between Fire Areas Rated Fire Feature Fire Barrier (Rated)

Existing Fire Protection Program M26 Fire Protection Feature in Fire Area Exterior Barrier or Fire Modeling Credited Barrier No Specific Function (treated as part of the overall barrier)

Shelter, Protection, Structural Support Addressed by overall non-rated fire barrier program.

S6 Structures Monitoring 3

Door/Seal in Interior Wall in Single Fire Area None None None None 3

ULNRC-06114 April 15, 2014 Page 30 of 30 Mechanical Barrier Features (Dampers)

Configuration NFPA-805 Functions License Renewal Function (Note 1)

NFPA 805 Inspection/Monitoring License Renewal Inspection/Monitoring Notes Feature Between Fire Areas Rated Fire Feature Fire Barrier (Rated)

Existing Fire Protection Program M26 Fire Protection Feature in Fire Area Exterior Barrier or Fire Modeling Credited Barrier No Specific Function (treated as part of the overall barrier)

Pressure Boundary Addressed by overall non-rated fire barrier program.

M38 Inspection of Internal Surfaces in Miscellaneous Piping and Ducting 5

Damper/Seal in Interior Wall in Single Fire Area None None None None 5

Notes:

1. License renewal defines a fire barrier intended function as provides rated fire barrier to confine or retard a fire from spreading to or from adjacent areas in the plant
2. Interior barriers in single fire areas that do not have a fire rated function would require evaluation to determine if a license renewal intended function other than fire barrier (such as structural support or flood barrier) would apply.
3. Structural Fire Barrier Features that do not have a fire rated barrier function would require evaluation to determine if a license renewal intended function other than fire barrier (such as shelter/protection or structural support) would apply.
4. Structural barrier features include: fire barrier doors, fire barrier penetration seals and fire barrier coatings/wraps.
5. Mechanical Fire Barrier Features that do not have a fire rated barrier function would require evaluation to determine if a license renewal intended function other than fire barrier (such as pressure boundary) would apply.
6. Non-Rated Fire Barriers in a Fire Area Exterior Barrier or Fire Modeling Credited Barrier would require evaluation to determine if other license renewal intended functions would apply.

ULNRC-06114 April 15, 2014 Page 1 of 12 Amendment 33, LRA Changes Summary Table Affected LRA Section LRA As-Submitted Page Number(s)

Table 2.2-1 2.2-6 through 2.2-8 Section 2.3.3.8 2.3-40 and 2.3-41 Table 2.3.3-8 2.3-42 Section 2.4.7 2.4-18 and 2.4-19 Section 3.3.2.1.8 3.3-11 and 3.3-12 Table 3.3.2-8 3.3-113 through 3.3-115

ULNRC-06114 April 15, 2014 Page 2 of 12 Callaway Plant License Renewal Application Amendment 33 Changes made to add nitrogen storage tanks foundation and pipe trenches to the scope of license renewal to support compressed air system component additions required for NFPA 805.

Table 2.2-1 (Pages 2.2-6 through 2.2-8) is revised as follows (new text shown underlined and deleted text shown in strikethrough):

Table 2.2-1 Callaway Plant Scoping Results System/Structure In-Scope Section 2 Scoping and Screening Results In-Scope Tank Foundations and Structures includes:

Fire Water Storage Tanks Concrete Foundations Refueling Water Storage Tank Foundation and Valve House Condensate Storage Tank Foundation and Building Closure Nitrogen Storage Tank Foundation and Pipe Trench Yes 2.4.7 Miscellaneous Out-of-Scope Structures includes:

Auxiliary Oil Transfer Callaway Multipurpose Building Carbon Dioxide CO2 Storage Central Processing Facility Circulating Water Cooling Tower Cooling Water Chemical Control Demineralized Potable Water Building Demineralized Water Storage Tank Foundation Emergency Operations Facility Equalization Basin Fire Brigade Training Station Fitness for Duty Building Fuel Oil Storage Tank Foundation and Dike Gas Cylinder Storage Health Physics Calibration Facility Hydrogen Storage Intake Structure LCD Radwaste Storage Tank Foundation Lube Oil Storage Building Main Entrance Maintenance Shop Annex (Fab Shop)

Maintenance Storage Facility Maintenance Training Annex Nitrogen Storage No N/A

ULNRC-06114 April 15, 2014 Page 3 of 12 Table 2.2-1 Callaway Plant Scoping Results (Continued)

System/Structure In-Scope Section 2 Scoping and Screening Results OCA Access Facility OCA Access Booth Oily Waste Treatment Area Outage Maintenance Facility Oxygen Storage Parking for Training Center Plant Support Facility Quality Control Building Reactor Makeup Water Storage Tank Foundation Remote Multiplex Unit A.B.C Secondary Access Facility Service Building Sewage Lift Station Site Cathodic Protection Anode Bed Site Switchgear Building Sludge Pump Station Solvent Storage Spare Main Transformer Steam Generator Storage Facility Stores I Building Stores II Building Switchyard Concrete Foundations Technical Training Facility/Callaway Learning Center Technical Support Center Training Center Vendor Liaison Building Vendor Offices Watchman Gatehouse Water Treatment Control Building Water Treatment Plant Water Treatment Plant Clearwell Well number 1 Well number 3 XMB01 Excitation Transformer

ULNRC-06114 April 15, 2014 Page 4 of 12 Callaway Plant License Renewal Application Amendment 33 NFPA 805 changes made to identify that portions of the compressed air system are also within the scope of license renewal to support fire protection requirements based on the criteria of 10CFR54.4(a)(3). Specifically the backup supply of nitrogen gas for the auxiliary feedwater control valves and main steam atmospheric relief valves are also credited for fire protection.

Section 2.3.3.8 and Table 2.3.3-8 (Pages 2.3-40 through 2.3-42) are revised as follows (new text shown underlined):

2.3.3.8 Compressed Air System

System Description

The purpose of the compressed air system is to provide compressed air to the instrument air, service air, breathing air, and containment systems.

The compressed air system consists of the compressed air system, service gas system, and breathing air system.

Compressed air system The purpose of the compressed air system is to provide a continuous supply of filtered, dry, and oil-free air for instrument and control operations. The system also provides station air at service outlets throughout the plant for operation of pneumatic tools and other service requirements.

The compressed air system provides a reliable backup supply of nitrogen gas for the main feedwater control valves. The compressed air system also provides a safety-related backup supply of nitrogen gas for the auxiliary feedwater control valves and the main steam atmospheric relief valves.

The portion of the compressed air system within the scope of license renewal consists of accumulators for the main feedwater control valves, auxiliary feedwater control valves, and the main steam atmospheric relief valves to store nitrogen gas for use in the event there is a loss of operation of instrument air. The in-scope portion of the compressed air system also consists of instrument air and service gas containment penetration piping and associated isolation valves, components associated with air seals for the containment personnel airlock, and nonsafety piping and valves attached to safety-related components.

Service gas system The purpose of the service gas system is to provide nitrogen, hydrogen, carbon dioxide, oxygen, and laboratory gases to plant systems, as required.

The portion of the service gas system within the scope of license renewal consists of nonsafety-related piping and valves attached to safety-related components and a backup supply of

ULNRC-06114 April 15, 2014 Page 5 of 12 nitrogen gas from the outdoor nitrogen storage tanks is provided for the auxiliary feedwater control valves and main steam atmospheric relief valves.

Breathing air system The purpose of the breathing air system is to provide a dedicated source of respiratory air for use during maintenance operations within, and during abnormal entry into, areas having high or potentially high concentrations of airborne radioactive contaminants.

The portion of the breathing air system within the scope of license renewal consists of piping, containment isolation valves and the attached nonsafety-related piping and valves located in the reactor building and the auxiliary building.

The safety-related portions of the compressed air systems include the containment penetrations and their isolation valves, components associated with air seals for the containment personnel airlock, and components associated with the backup nitrogen gas supply for the auxiliary feedwater control valves and the main steam atmospheric relief valves.

System Intended Functions Portions of the compressed air systems provide containment isolation for instrument air, service air, and breathing air penetrations. Portions of the compressed air systems provide air for the seals for the containment personnel airlock doors to support containment integrity. Portions of the compressed air system provide a backup supply of nitrogen gas for operation of the auxiliary feedwater control valves and the main steam atmospheric relief valves to provide capability to shutdown the reactor and maintain it in a safe shutdown condition. Therefore, the compressed air systems are within the scope of license renewal based on the criteria of 10 CFR 54.4(a)(1).

Portions of the compressed air systems are within the scope of license renewal as nonsafety-related affecting safety-related components based on the criterion of 10 CFR 54.4(a)(2) for spatial interaction and structural integrity.

Portions of the compressed air systems are within the scope of license renewal to support environmental qualification, fire protection, and station blackout requirements based upon the criteria of 10 CFR 54.4 (a)(3).

Callaway FSAR References Additional details of the compressed air system are included in FSAR Sections 9.3.1 SP, 9.3.5 SP, and 9.5.10 SP.

License Renewal Boundary Drawings The license renewal boundary drawings for the compressed air system are listed below:

LR-CW-KA-M-22KA01 LR-CW-KA-M-22KA02 LR-CW-KA-M-22KA04 LR-CW-KA-M-22KA05 LR-CW-KA-M-22KB02 LR-CW-KB-M-22KB01

ULNRC-06114 April 15, 2014 Page 6 of 12 LR-CW-KH-M-22KH01 LR-CW-KH-X-89645 Component-Function Relationship Table The component types subject to aging management review are indicated in Table 2.3.3 Compressed Air System.

Table 2.3.3-8 Compressed Air System Component Type Intended Function Closure Bolting Pressure Boundary Structural Integrity (attached)

Flow Orifice Structural Integrity (attached)

Heat Exchanger (Breathing Air Compressor)

Structural Integrity (attached)

Piping Leakage Boundary (spatial)

Pressure Boundary Structural Integrity (attached)

Rupture Disc Pressure Boundary Strainer Structural Integrity (attached)

Tank Pressure Boundary Tubing Pressure Boundary Valve Pressure Boundary Structural Integrity (attached)

The AMR results for these component types are provided in Table 3.3.2-8, Auxiliary Systems -

Summary of Aging Management Evaluation - Compressed Air System.

ULNRC-06114 April 15, 2014 Page 7 of 12 Callaway Plant License Renewal Application Amendment 33 Changes made to add nitrogen storage tanks foundation and pipe trenches to the scope of license renewal to support compressed air system component additions required for NFPA 805.

Section 2.4.7 (Pages 2.4-18 and 2.4-19) is revised as follows (new text shown underlined):

2.4.7 In-Scope Tank Foundations and Structures Structure Description The purpose of the in-scope tank foundations is to provide support and shelter and protection to the seismic Category I safety-related refueling water storage tank (RWST) and valvehouse.

The nonsafety-related condensate storage tank (CST), the CST trench, the nitrogen storage tank foundation and pipe trench, and the fire water storage tanks are also included.

The foundation for refueling water storage tank is a concrete mat founded on compacted fill and some lean concrete backfill under the interface of tank foundation and valvehouse. The RWST foundation scope includes the RWST slab foundation, and the RWST valvehouse. The ductbanks associated with the RWST valvehouse are evaluated separately with electrical foundations and structures in Section 2.4.8, Electrical Foundations and Structures. The condensate storage tank foundation is also concrete slab founded on compacted backfill. The CST foundation scope includes the CST slab foundation, the CST pipehouse, CST trench, and all associated structural components. The nitrogen storage tank foundation is a grade-level concrete slab, and the pipe trench is covered with grade-level precast concrete covers and steel access hatches. The fire water storage tanks are supported on reinforced concrete ring beams founded on compacted backfill. The tanks themselves are evaluated under their respective mechanical systems in Section 2.3, Scoping and Screening Results: Mechanical Systems.

The emergency diesel fuel oil storage tanks are evaluated under emergency diesel engine fuel oil storage and transfer system in Section 2.3.3.21, Emergency Diesel Engine Fuel Oil Storage and Transfer System. The access vaults to the emergency diesel fuel oil storage tanks are evaluated with the diesel generator building in Section 2.4.5, Diesel Generator Building.

Structure Intended Function The in-scope tank foundations and structures provide structural support and shelter and protection for safety-related SSCs providing the capability to shutdown the reactor and maintain it in a safe shutdown condition. Therefore, the in-scope tank foundations and structures are within the scope of license renewal based on the criteria of 10 CFR 54.4(a)(1).

Portions of the in-scope tank foundations and structures provide structural support and shelter and protection for nonsafety-related SSCs whose failure could prevent performance of a safety-related function. Therefore, the in-scope tank foundations and structures are within the scope of license renewal based on the criterion of 10 CFR 54.4(a)(2).

ULNRC-06114 April 15, 2014 Page 8 of 12 Portions of the in-scope tank foundations and structures provide structural support and shelter and protection for SSCs that are within the scope of license renewal to support fire protection and station blackout requirements based upon criteria of 10 CFR 54.4(a)(3).

Callaway FSAR References Additional details of the in-scope tank foundations and structures are included in FSAR Sections 1.2.2 SP, 2.2.1.2.3.2 SA, 3.8.4.1.5 SP, 3.8.5.1.5 SP, 8.3A.5.1 SP, and 10.4.9.1.2 SP.

ULNRC-06114 April 15, 2014 Page 9 of 12 Callaway Plant License Renewal Application Amendment 33 Materials, Environment, and Aging Management Program additions for NFPA 805 made to portions of the service gas subsystem that are credited by fire protection with providing the backup supply of nitrogen gas for the auxiliary feedwater control valves and main steam atmospheric relief valves.

Section 3.3.2.1.8 (Pages 3.3-11 and 3.3-12) is revised as follows (new text shown underlined):

3.3.2.1.8 Compressed Air System Materials The materials of construction for the compressed air system component types are:

Carbon Steel Cast Iron (Gray Cast Iron)

Copper Alloy Copper Alloy (>15% Zinc)

Copper Alloy (Aluminum >8%)

Stainless Steel Environment The compressed air system component types are exposed to the following environments:

Atmosphere/Weather Borated Water Leakage Buried Condensation Dry Gas Plant Indoor Air Raw Water Aging Effects Requiring Management The following compressed air system aging effects require management:

Loss of material Loss of material and cracking

ULNRC-06114 April 15, 2014 Page 10 of 12 Loss of preload Aging Management Programs The following aging management programs manage the aging effects for the compressed air system component types:

Bolting Integrity (B2.1.8)

Boric Acid Corrosion (B2.1.4)

Buried and Underground Piping and Tanks (B2.1.25)

External Surfaces Monitoring of Mechanical Components (B2.1.21)

Inspection of Internal Surfaces in Miscellaneous Piping and Ducting Components (B2.1.23)

Selective Leaching (B2.1.19)

ULNRC-06114 April 15, 2014 Page 11 of 12 Callaway Plant License Renewal Application Amendment 33 NFPA 805 changes made to portions of the service gas subsystem that are credited by fire protection with providing the backup supply of nitrogen gas for the auxiliary feedwater control valves and main steam atmospheric relief valves.

Table 3.3.2-8 (Pages 3.3-113 through 3.3-115) is revised as follows (new text shown underlined):

Table 3.3.2-8 Auxiliary Systems - Summary of Aging Management Evaluation - Compressed Air System Component Type Intended Function Material Environment Aging Effect Requiring Management Aging Management Program NUREG-1801 Item Table 1 Item Notes Closure Bolting PB Carbon Steel Atmosphere/

Weather (Ext)

Loss of material Bolting Integrity (B2.1.8) VII.I.AP-126 3.3.1.012 A

Closure Bolting PB Carbon Steel Atmosphere/

Weather (Ext)

Loss of preload Bolting Integrity (B2.1.8) VII.I.AP-263 3.3.1.015 A

Piping PB Carbon Steel Atmosphere/

Weather (Ext)

Loss of material External Surfaces Monitoring of Mechanical Components (B2.1.21)

VII.I.A-78 3.3.1.078 A

Piping PB Carbon Steel Buried (Ext)

Loss of material Buried and Underground Piping and Tanks (B2.1.25)

VII.G.AP-198 3.3.1.106 A

Piping PB Copper Alloy

(> 15% Zinc)

Atmosphere/

Weather (Ext)

Loss of material External Surfaces Monitoring of Mechanical Components (B2.1.21)

VII.I.AP-159 3.3.1.081 A

Piping PB Copper Alloy

(> 15% Zinc)

Dry Gas (Int)

None None VII.J.AP-9 3.3.1.114 A

Rupture Disc PB Copper Alloy

(> 15% Zinc)

Atmosphere/

Weather (Ext)

Loss of material External Surfaces Monitoring of Mechanical Components (B2.1.21)

VII.I.AP-159 3.3.1.081 A

Rupture Disc PB Copper Alloy

(> 15% Zinc)

Dry Gas (Int)

None None VII.J.AP-9 3.3.1.114 A

ULNRC-06114 April 15, 2014 Page 12 of 12 Table 3.3.2-8 Auxiliary Systems - Summary of Aging Management Evaluation - Compressed Air System (continued)

Component Type Intended Function Material Environment Aging Effect Requiring Management Aging Management Program NUREG-1801 Item Table 1 Item Notes Tank PB Carbon Steel Atmosphere/

Weather (Ext)

Loss of material and cracking External Surfaces Monitoring of Mechanical Components (B2.1.21)

VII.D.A-405 3.3.1.132 C

Valve PB Carbon Steel Atmosphere/

Weather (Ext)

Loss of material External Surfaces Monitoring of Mechanical Components (B2.1.21)

VII.I.A-78 3.3.1.078 A

Valve PB Copper Alloy

(> 15% Zinc)

Atmosphere/

Weather (Ext)

Loss of material External Surfaces Monitoring of Mechanical Components (B2.1.21)

VII.I.AP-159 3.3.1.081 A

Valve PB Copper Alloy

(> 15% Zinc)

Dry Gas (Int)

None None VII.J.AP-9 3.3.1.114 A

Valve PB Copper Alloy (Aluminum >

8%)

Atmosphere/

Weather (Ext)

Loss of material External Surfaces Monitoring of Mechanical Components (B2.1.21)

VII.I.AP-159 3.3.1.081 A

Valve PB Copper Alloy (Aluminum >

8%)

Dry Gas (Int)

None None VII.J.AP-9 3.3.1.114 A