Pages that link to "05000287/LER-1982-014, Forwards LER 82-014/01T-0.Detailed Event Analysis Encl"
Jump to navigation
Jump to search
The following pages link to 05000287/LER-1982-014, Forwards LER 82-014/01T-0.Detailed Event Analysis Encl:
Displayed 45 items.
- 05000287/LER-1982-008, Forwards LER 82-008/01T-0.Detailed Event Analysis Encl (← links)
- 05000269/LER-1982-007, Forwards LER 82-007/01T-0.Detailed Event Analysis Encl (← links)
- 05000269/LER-1982-005, Forwards LER 82-005/03L-0.Detailed Event Analysis Encl (← links)
- 05000287/LER-1982-010, Forwards LER 82-010/01T-0.Detailed Event Analysis Encl (← links)
- 05000269/LER-1982-015, Forwards LER 82-015/03L-0.Detailed Event Analysis Encl (← links)
- ML20064J206 (redirect page) (← links)
- 05000287/LER-1982-014 (redirect page) (← links)
- 05000287/LER-1982-015, Forwards LER 82-015/01T-0.Detailed Event Analysis Encl (← links)
- 05000269/LER-1982-017, Forwards LER 82-017/01T-0.Detailed Event Analysis Encl (← links)
- 05000269/LER-1982-011, Forwards LER 82-011/03L-0.Detailed Event Analysis Encl (← links)
- 05000270/LER-1982-010, Forwards LER 82-010/01T-0.Detailed Event Analysis Encl (← links)
- 05000270/LER-1982-009, Forwards LER 82-009/03L-0.Detailed Event Analysis Encl (← links)
- 05000287/LER-1982-007, Forwards LER 82-007/01T-0.Detailed Event Analysis Encl (← links)
- 05000287/LER-1982-012, Forwards LER 82-012/01T-0.Detailed Event Analysis Encl (← links)
- 05000270/LER-1982-013, Forwards LER 82-013/03L-0.Detailed Event Analysis Encl (← links)
- 05000287/LER-1982-014-01, /01T-0:on 821211,steam Generator Tube Leak Indicated by Condensate Steam Air Ejector Offgas Radiation Monitor.Caused by Crack in Tube 77-9.Tube 77-9 & Tube 78-2 Removed from Svc (← links)
- 05000287/LER-1982-015-01, /01T-0:on 821212,manual Containment Isolation Valves 3IA 90 & 91 Found Open,Violating Containment Integrity.Caused by Personnel & Procedure Error.Personnel Counseled & Procedure Revised (← links)
- 05000269/LER-1982-017-01, /01T-0:on 820820,station I&C Batteries 1CA,1CB & 3CA Declared Inoperable Due to Failure to Take Corrective Actions on Deficiencies Identified During Monthly Surveillance.Caused by Personnel Error (← links)
- 05000270/LER-1982-010-01, /01T-0:on 820722,while Investigating Erroneous Instrument Readings,Upper Surge Tank Water Level Found to Be Less than 5 Ft.Caused by Stuck Suction Relief Valve on Main Feedwater Pump 2B.Valve Reseated.Instrumentation Repaire (← links)
- 05000270/LER-1982-009-03, /03L-0:on 820616,valve 2FDW-316 Would Not Open Fully.Valve Declared Inoperable,Making Emergency Feedwater Flowpath 2B Inoperable.Apparently Caused by Valve Manual Handwheel Being Partially Shut.Handwheels to Be Locked Open (← links)
- 05000269/LER-1982-013-01, /01T-0:on 820706,emergency Feedwater Initiation Logic Pressure Switches Determined Not Surveillance Tested from 820523-0708,rendering Pumps Inoperable.Caused by Inadequate Review of Tech Spec Change.Tests Performed (← links)
- 05000287/LER-1982-007-01, /01T-0:on 820521,during Video Insp of Fuel Assemblies,Broken Holddown Springs Found on Fuel Assemblies NJ001MH & NJ001M9.Caused by Fatigue Induced Cracking at Existing Surface Flaw.Springs Will Be Replaced (← links)
- 05000287/LER-1982-006-01, /01T-0:on 820430,visual Insp of Internal Auxiliary Feedwater Header in Both Steam Generators Revealed Header Deformation.Caused by Inadequate Design to Withstand Thermal & Pressure Forces.External Header to Be Installed (← links)
- 05000287/LER-1982-006, Forwards LER 82-006/01T-0.Detailed Event Analysis Encl (← links)
- 05000270/LER-1982-007-01, /01T-0:on 820428,during Final Reactor Bldg Insp, One Vertical Tendon in Secondary Shield Wall Was Found Broken.Caused by Stress Corrosion of post-tensioning Wires Near Stressing Washers Due to Water (← links)
- 05000270/LER-1982-007, Forwards LER 82-007/01T-0.Detailed Event Analysis Encl (← links)
- 05000269/LER-1982-010-03, /03L-0:on 820407,reactor Bldg Isolation Valve 1LWD-1 Failed to Close After Pumping Reactor Bldg Normal Sump.Apparently Caused by Dirty Contact in Valve Operating Motor Starting Compartment.Contact Cleaned (← links)
- 05000269/LER-1982-010, Forwards LER 82-010/03L-0.Detailed Event Analysis Encl (← links)
- 05000270/LER-1982-005-01, /01T-0:on 820312,insp of Fuel Assembly W/Experimental Zircaloy Spacer Grids Revealed That Grids Had Moved from Normal Position.Caused by Loss of Contact W/Mark B4 Grids Due to Weak Springs & Too Much Gap Growth (← links)
- 05000270/LER-1982-005, Forwards LER 82-005/01T-0.Detailed Event Analysis Encl (← links)
- 05000287/LER-1982-005-01, /01T-0:on 820330,spent Fuel Pool Fans Found to Have Been Inoperable During 820323-29 Move of 10 Fuel Assemblies.Caused by Personnel Error in That White Tags for Fans Not Placed or Removed During Leak Rate Test Procedure (← links)
- 05000270/LER-1982-006-01, /01T-0:on 820402,spent Fuel Assembly Moved from Spent Fuel Pool Racks to Sipping Can While Spent Fuel Pit Ventilation Sys Out of Svc.Caused by Personnel Error.Fuel Handling Suspended (← links)
- 05000287/LER-1982-005, Forwards LER 82-005/01T-0.Detailed Event Analysis Encl (← links)
- 05000270/LER-1982-006, Forwards LER 82-006/01T-0.Detailed Event Analysis Encl (← links)
- 05000270/LER-1982-004-01, /01T:on 820302,testing of HPI Nozzle Areas Revealed Loose 2A2 Thermal Sleeves & Cracks in Id of Safe End & Piping.Caused by Thermal Fatigue.Cracked Piping,Safe End & Thermal Sleeves Replaced (← links)
- 05000269/LER-1982-009-01, /01T-0:on 820329,five Differential Pressure Regulators for Oxygen Supply on Channel B Hydrogen Analyzer Found Defective.Caused by Mfg Deficiency (← links)
- 05000270/LER-1982-004, Forwards LER 82-004/01T-0.Detailed Event Analysis Encl (← links)
- 05000287/LER-1982-004-01, /01T-0:on 820226,nondestructive Testing of HPI Nozzles Revealed 3A2 Thermal Sleeve Displaced & Cracks in Inside Diameter of Piping & Safe End.Caused by Thermal Fatigue Due to Loose Thermal Sleeve.Piping Replaced (← links)
- 05000287/LER-1982-004, Forwards LER 82-004/01T-0.Detailed Event Analysis Encl (← links)
- 05000269/LER-1982-006-01, /01T-0:on 820306,steam Generator Tube Leak of Approx 0.08 Gpm Indicated by Condensate Steam Air Ejector Offgas Radiation Monitor.Caused by Crack in Tube 78-2.Unit Shut Down,Leaking Tube Stabilized & Plugged (← links)
- 05000269/LER-1982-006, Forwards LER 82-006/01T-0.Detailed Event Analysis Encl (← links)
- 05000287/LER-1982-002-03, /03L-0:on 820210,reactor Protection Sys Channel B Hot Leg Temp Readings Were Lower than Those of Channels A,C & D.Caused by Failure of Liner Bridge in Input Circuitry for Channel B Indication.Bridge Replaced (← links)
- 05000287/LER-1982-002, Forwards LER 82-002/03L-0.Detailed Event Analysis Encl (← links)
- 05000287/LER-1982-003-01, /01T-0:on 820211,steam Generator Tube Leak of Approx 0.01 Gpm Indicated by Condensate Steam Air Ejector Offgas Monitor.Caused by Erosion of Tube at Point 31 Inches Above Fifteenth Tube Support Plate.Tube Explosively Plugged (← links)
- 05000287/LER-1982-003, Forwards LER 82-003/01T-0.Detailed Event Analysis Encl (← links)