Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000315/LER-1979-003-03, /03L-0 on 790120:during Review of Completed Surveillance Tests,Discovered That Test on Solid State Protection Sys Train a Exceed 1-h Limit Imposed by Tech Specs.Caused by Technician Overlooking 1-h Limit + (22:01:31, 7 January 2025)
- 05000315/LER-1978-069-03, /03L-0 on 781010:axial Flux Difference Monitoring Alarm Point Discovered Set Above Tech Spec Max.Caused by Raising of Alarm Trip Point During Preoperational Test Failure to Return to Required Value at End + (22:01:33, 7 January 2025)
- ML17317A957 + (22:01:34, 7 January 2025)
- ML17317A956 + (22:01:35, 7 January 2025)
- ML17317A955 + (22:01:38, 7 January 2025)
- ML17317A954 + (22:01:39, 7 January 2025)
- ML17317A952 + (22:01:40, 7 January 2025)
- IR 05000315/1978035 + (22:01:41, 7 January 2025)
- ML17317A949 + (22:01:47, 7 January 2025)
- 05000315/LER-1979-002, Forwards LER 79-002/03L-0 + (22:01:54, 7 January 2025)
- 05000316/LER-1979-006-03, /03L-0 on 790123:svc Water Supply Check Valve to AB diesel,ESW-143,failed to Seat.Caused by Normal Wear of Split Center Disc of Carbon Steel Check Valve,Centerline Part D-10495-26 + (22:01:56, 7 January 2025)
- 05000316/LER-1979-005-03, /03L-0 on 790117:solid State Protection Sys Tested Unsatisfactorily.Caused by Failure of Universal Logic Card A-214 + (22:01:57, 7 January 2025)
- 05000316/LER-1979-004-01, /01T-0 on 780802:turbine Low Fluid Oil Pressure Switches Set at non-conservative Value.Initially Calibr at Vendors Recommended Setpoints;Were Not Recalibr Per Tech Specs + (22:01:59, 7 January 2025)
- 05000316/LER-1979-004, Forwards LER 79-004/01T-0,79-005/03L-0 & 79-006/03L-0 + (22:02:00, 7 January 2025)
- ML17317A940 + (22:02:01, 7 January 2025)
- ML17317A938 + (22:02:02, 7 January 2025)
- ML17317A934 + (22:02:03, 7 January 2025)
- ML17317A936 + (22:02:03, 7 January 2025)
- ML17317A933 + (22:02:04, 7 January 2025)
- IR 05000315/1978011 + (22:02:07, 7 January 2025)
- ML17317A931 + (22:02:08, 7 January 2025)
- 05000315/LER-1979-001-03, /03L-0 on 790122:during Mode 1,position of Rod F-6 Showed Deviation of Greater than 12 Steps from Demand Position.Caused by Drift in Signal Conditioning Module + (22:02:12, 7 January 2025)
- ML17317A929 + (22:02:14, 7 January 2025)
- 05000315/LER-1979-001, Forwards LER 79-001/03L-0 + (22:02:15, 7 January 2025)
- 05000316/LER-1979-003-03, /03L-0 on 790106:reactor Trip/Safety Injection Occurred.Caused by Freezing of Steam Generator/Main Steam Pressure Sensing Lines.Freezing Due to Failure to Close Off Steam Vent Openings in West Steam Encl + (22:02:17, 7 January 2025)
- 05000316/LER-1979-002-03, /03L-0 on 790106:during Startup,Auxiliary Feedwater Motor Operated Valve Would Not Close Due to Broken Wire in SMB-0-25 Operator.Caused by Vibration & Use of Solid Conductor + (22:02:19, 7 January 2025)
- ML17317A923 + (22:02:20, 7 January 2025)
- ML17317A922 + (22:02:21, 7 January 2025)
- ML17317A920 + (22:02:22, 7 January 2025)
- ML17317A918 + (22:02:22, 7 January 2025)
- ML17317A917 + (22:02:23, 7 January 2025)
- ML17317A915 + (22:02:24, 7 January 2025)
- ML17317A914 + (22:02:25, 7 January 2025)
- 05000316/LER-1979-001-03, /03L-0 on 790111:at 100% Power,Quadrant Power Tilt Ratio Alarm Per Tech Spec 4.2.4 Was in Error.Calculation of Tilt Ratio Is Required Every 12-h;first Survey Was Missed Because Alarm Instruments Were Being Calibr + (22:02:26, 7 January 2025)
- 05000316/LER-1979-001, Forwards LER 79-001/03L-0 + (22:02:28, 7 January 2025)
- ML17317A910 + (22:02:29, 7 January 2025)
- ML17317A909 + (22:02:30, 7 January 2025)
- ML17317A907 + (22:02:32, 7 January 2025)
- ML17317A906 + (22:02:32, 7 January 2025)
- 05000315/LER-1978-068-03, /03L-0 on 781221:during Rapid Power Reduction from 100% to 74% Axial Flux Difference Was Forced Outside Target Band Specified by Tech Specs.Inadvertent Feed Pump Turbine Trip Necessitated Load Reduction to Prevent Trip + (22:02:34, 7 January 2025)
- 05000315/LER-1978-067-03, /03L-0 on 781223:during Routine Surveillance Test on Solid State Protection Sys,Several Logic Functions in Train B Tested Unsatisfactorily.Test Card(Model 6056033G01) Had Failed & Was Replaced + (22:02:38, 7 January 2025)
- 05000315/LER-1978-067, Forwards LER 78-067/03L-0 & LER 78-068/03L-0 + (22:02:43, 7 January 2025)
- 05000316/LER-1978-031-03, /03X-1 on 780507:during Normal Operation Between 780507 & 780519 RPI Did Not Meet +/- 12 Step Limit of Tech Specs 22 Times.Caused by Recessed Pins in Connector + (22:02:47, 7 January 2025)
- ML17317A900 + (22:02:48, 7 January 2025)
- 05000316/LER-1978-022-03, /03X-1 on 780407:during Normal Operation,Position Indication for Rods D-12 & H-8 Exceeded +/- 12 Step Limit of Tech Specs.Outputs of Amplifiers That Feed Control Board Indicators Found to Be Incorrect + (22:02:50, 7 January 2025)
- 05000316/LER-1978-022, Forwards LER 78-022/03X-1, 78-031/03X-1 & 78-076/03X-1 + (22:02:52, 7 January 2025)
- ML17317A896 + (22:02:53, 7 January 2025)
- ML17317A891 + (22:02:55, 7 January 2025)
- ML17317A890 + (22:02:56, 7 January 2025)
- 05000315/LER-1978-066-03, /03L-0 on 781229:during Routine Startup,Rod Position Indication for Rods F-4,D-6 & K-6 Exceeded 12 Step Limit of Tech Specs.Caused by Drift of Signal Conditioning Modules + (22:02:58, 7 January 2025)
- 05000315/LER-1978-065-03, /03L-0 on 781229:indication for Pressurizer Level Channel 2 Deviated Approx 5% from Other 2 Channels.Caused by Gas Pocket in Sensing Line + (22:02:59, 7 January 2025)