Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20003B818 + (19:42:20, 23 December 2024)
- ML20003B816 + (19:42:21, 23 December 2024)
- ML20003B817 + (19:42:21, 23 December 2024)
- ML20003B815 + (19:42:23, 23 December 2024)
- ML20003B814 + (19:42:24, 23 December 2024)
- ML20003B813 + (19:42:24, 23 December 2024)
- ML20003B811 + (19:42:25, 23 December 2024)
- ML20003B810 + (19:42:26, 23 December 2024)
- ML20003B809 + (19:42:27, 23 December 2024)
- ML20003B808 + (19:42:28, 23 December 2024)
- ML20003B806 + (19:42:29, 23 December 2024)
- ML20003B805 + (19:42:29, 23 December 2024)
- ML20003B804 + (19:42:30, 23 December 2024)
- ML20003B802 + (19:42:31, 23 December 2024)
- ML20003B801 + (19:42:32, 23 December 2024)
- ML20003B800 + (19:42:34, 23 December 2024)
- DD-80-36, Informs That Time within Which Commission May Act to Review Directors Decision DD-80-36 Has Expired.Commission Declined Review.Decision Became Final Agency Action on 810220 + (19:42:35, 23 December 2024)
- ML20003B798 + (19:42:36, 23 December 2024)
- 05000237/LER-1981-007-03, /03L-0:on 810122,temp Switch TS 2-261-18D Failed to Trip.Caused by Fill Matl Leakage Due to Broken Capillary Tube Close to Sensing Bulb.Broken Switch Replaced W/New Calibr Switch + (19:42:38, 23 December 2024)
- AECM-80-313, Final Deficiency Rept Re Removal of Cable Insulation, Initially Reported 800403.Caused by Rodents.Damaged Cable Replaced & Maint Insp Program Expanded to Include Visual Insp for Rodent Infestation.Rodent Control Subcontracted + (19:42:39, 23 December 2024)
- 05000305/LER-1981-003, Forwards LER 81-003/03L-0 + (19:42:41, 23 December 2024)
- ML20003B794 + (19:42:44, 23 December 2024)
- NUREG-0760, Forwards Notice of Violation & NUREG-0760 Detailing Investigation Conducted Mar 1980-Jan 1981 Into Info Flow During 790328 Accident + (19:42:45, 23 December 2024)
- ML20003B791 + (19:42:53, 23 December 2024)
- ML20003B790 + (19:42:54, 23 December 2024)
- 05000278/LER-1981-005-03, /03L-0:on 810127,setpoint of Temp Switch TS 5943 B (HPCI Steam Line Area High Temp Isolation) Found to Be Above Tech Spec Limit.Caused by Setpoint Drift.Instrument Recalibr to within Tech Spec Limits,Tested & Returned to Svc + (19:42:55, 23 December 2024)
- ML20003B788 + (19:42:57, 23 December 2024)
- ML20003B787 + (19:42:57, 23 December 2024)
- 05000317/LER-1981-006-03, /03L-0:on 810113,steam Generator 11,level Channel D Placed Out of Svc Per Tech Specs to Correct Problem W/Ref Leg.Caused by Indication Deviation Among Redundant Safety Channels Due to Level Transmitter Valve leak-through + (19:42:58, 23 December 2024)
- 05000317/LER-1981-006, Forwards LER 81-006/03L-0 + (19:43:00, 23 December 2024)
- 05000249/LER-1981-003-03, /03L-0:on 810120,Model 288 Differential Pressure Indicating switch,3-1349B,tripped Above Tech Spec Limit. Caused by Instrument Drift.Switch Readjusted & Repeatability Verified + (19:43:02, 23 December 2024)
- ML20003B781 + (19:43:03, 23 December 2024)
- ML20003B782 + (19:43:03, 23 December 2024)
- 05000302/LER-1981-006-03, /03L-0:on 810123,breaker for Control Complex Emergency Ventilation Fan AHF-18A Found Open.Caused by Inadvertent Bumping of Breaker.Breaker Shut,Operability Checks Performed & Personnel Advised to Exercise Caution + (19:43:04, 23 December 2024)
- ML20003B779 + (19:43:05, 23 December 2024)
- ML20003B778 + (19:43:06, 23 December 2024)
- 05000302/LER-1981-006, Forwards LER 81-006/03L-0 + (19:43:07, 23 December 2024)
- ML20003B775 + (19:43:08, 23 December 2024)
- 05000346/LER-1981-007-03, /03L-0:on 810122,door 306 Found Partially Open,So That Spent Fuel Pool Emergency Ventilation Sys Could Not Have Maintained Area at Correct Pressure.Caused by Maladjusted Door Closure.Maint Work Order Issued + (19:43:09, 23 December 2024)
- 05000255/LER-1981-008-03, /03L-0:on 810124,component Cooling Water Pump P-52C Motor Caught on Fire.Caused by Motor Bearing Failure Due to Oil Loss.Motor Replaced + (19:43:11, 23 December 2024)
- ML20003B772 + (19:43:13, 23 December 2024)
- 05000346/LER-1981-007, Forwards LER 81-007/03L-0 + (19:43:14, 23 December 2024)
- 05000324/LER-1981-010-03, /03L-0:on 810120,RHR Svc Water Subsys a Suction valve,2-SW-V101,would Not Open Fully.Caused by Two Hex Nuts on Input Shaft of Valve Motor Operator,Model H3BC-SMB-00, Freezing to Shaft.Nuts & Shaft Reworked & Lubricated + (19:43:16, 23 December 2024)
- 05000324/LER-1981-010, Forwards LER 81-010/03L-0 + (19:43:19, 23 December 2024)
- 05000318/LER-1981-006-03, /03L-0:on 810113 Diesel Generator 12 Switchgear Would Not Close in on 21 4-kV Bus Per Tech Spec.Caused by High Resistance at Secondary Disconnect.Continuity of Closing Circuit Interlocks Verified & Switchgear Tested + (19:43:25, 23 December 2024)
- 05000318/LER-1981-007, Forwards LER 81-007/03L-0 + (19:43:27, 23 December 2024)
- 05000029/LER-1981-001-03, /03L-0:on 810122,low Main Coolant Flow Sys B Under Current Relays 2A & 4C Failed to Drop Out When de-energized. Caused by Residue Buildup on Relay Activation Plunger.Relay Plungers in Sys a & B Inspected & Cleaned as Require + (19:43:29, 23 December 2024)
- 05000029/LER-1981-001, Forwards LER 81-001/03L-0 + (19:43:30, 23 December 2024)
- 05000317/LER-1981-005-03, /03L-0:on 810119,during Surveillance Testing, Containment Cooler 14 Would Not Start in Slow Speed.Caused by Contacts Not Closing on Slow Speed Motor Starter Interlock Contact Assembly Due to Cracked Case + (19:43:32, 23 December 2024)
- 05000318/LER-1981-006, Forwards LER 81-006/03L-0 + (19:43:34, 23 December 2024)
- 05000317/LER-1981-005, Forwards LER 81-005/03L-0 + (19:43:35, 23 December 2024)