Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000368/LER-1982-029, Forwards LER 82-029/03L-0 + (15:36:53, 16 December 2024)
- ML20069K241 + (15:36:54, 16 December 2024)
- 05000361/LER-1982-176-01, /01T-0:on 820710,independent Verification Not Performed on Reactor Trip Circuit Breakers 4,6 & 7 Undervoltage Trip Mechanism Operability After Maint.Caused by Personnel Oversight.Maint Program Revised + (15:36:56, 16 December 2024)
- ML20069K237 + (15:36:57, 16 December 2024)
- 05000302/LER-1983-014, Forwards LER 83-014/03L-0 + (15:36:58, 16 December 2024)
- 05000373/LER-1982-114-01, /01T-0:on 821005,installed Configuration of HVAC Duct Hanger 1382 Did Not Match Design Drawing M-1538.Caused by Misinterpretation of Fcr by Draftsman.Sargent & Lundy Drawing M-1538 Will Be Revised Prior to 821008 + (15:37:00, 16 December 2024)
- ML20069K232 + (15:37:02, 16 December 2024)
- 05000250/LER-1982-013, Forwards LER 82-013/03L-0 + (15:37:05, 16 December 2024)
- ML20069K222 + (15:37:06, 16 December 2024)
- 05000373/LER-1982-114, Forwards LER 82-114/01T-0 + (15:37:07, 16 December 2024)
- 05000361/LER-1982-176, Forwards LER 82-176/01T-0 + (15:37:08, 16 December 2024)
- ML20069K211 + (15:37:08, 16 December 2024)
- RC-94-0156, Monthly Operating Rept for May 1994 for VC Summer Nuclear Station,Unit 1 + (15:37:09, 16 December 2024)
- ML20069K207 + (15:37:10, 16 December 2024)
- ML20069K202 + (15:37:10, 16 December 2024)
- ML20069K198 + (15:37:11, 16 December 2024)
- ML20069K197 + (15:37:13, 16 December 2024)
- 05000311/LER-1982-108-03, /03L-0:on 820915 & 17,RPI 1C4 Discovered Reading Greater than 12 Steps Lower than Bank Demand Indication.Caused by Combination of RPI Module Calibr Drift & Change in Actual Rod Position Signal Output + (15:37:15, 16 December 2024)
- ML20069K193 + (15:37:16, 16 December 2024)
- ML20069K192 + (15:37:17, 16 December 2024)
- ML20069K190 + (15:37:19, 16 December 2024)
- 05000395/LER-1983-027-03, /03L-0:on 830318,main Control Board Temp Indication TE-413 for Reactor Coolant Outlet Temp Exhibited Erratic Indications.Caused by Varying Resistance Between Compensated Lead & Low Side Resistance Leg of TE-413 + (15:37:21, 16 December 2024)
- ML20069K188 + (15:37:22, 16 December 2024)
- 05000331/LER-1982-061-03, /03L-0:on 820914,RHR Svc Water Pumps 1P-22A & 1P-22D Failed to Meet Tech Spec Requirements.Caused by Excessive Clearances Between Pump Impellers & Casing Wear Rings Due to Pump Wear.Impellers Adjusted & Pumps Tested + (15:37:24, 16 December 2024)
- ML20069K186 + (15:37:25, 16 December 2024)
- 3F0694-10, Monthly Operating Rept for May 1994 for Crystal River Unit 3 + (15:37:26, 16 December 2024)
- ML20069K182 + (15:37:27, 16 December 2024)
- 05000387/LER-1982-023-03, /03L-0:on 820915,during Startup Testing of Steam Relief Valve Acoustic Monitoring Sys,Three Monitors Failed to Operate Correctly.Event Was Initial Calibr of Monitors Using Steam.Monitors Adjusted,Tested & Placed in Svc + (15:37:33, 16 December 2024)
- 05000324/LER-1983-043-01, /01T-0:on 830405,discovered Continuous Fire Watches for Inoperable Fire Detectors in Augmented Offgas Bldg Not Established on 830213.Caused by Personnel Error. Continuous Fire Watches Established + (15:37:36, 16 December 2024)
- ML20069K175 + (15:37:39, 16 December 2024)
- 05000331/LER-1982-061, Forwards LER 82-061/03L-0 + (15:37:40, 16 December 2024)
- ML20069K171 + (15:37:41, 16 December 2024)
- ML20069K168 + (15:37:41, 16 December 2024)
- 05000311/LER-1982-108, Forwards LER 82-108/03L-0.Detailed Event Analysis Encl + (15:37:42, 16 December 2024)
- ML20069K165 + (15:37:43, 16 December 2024)
- 05000387/LER-1982-023, Forwards LER 82-023/03L-0 + (15:37:44, 16 December 2024)
- ML20069K161 + (15:37:46, 16 December 2024)
- 05000395/LER-1983-027, Forwards LER 83-027/03L-0.Detailed Event Analysis Encl + (15:37:47, 16 December 2024)
- 3F0694-11, Requests non-withholding of Info from Public Disclosure Re Re Refuel 9 Insp Plan for OTSG + (15:37:47, 16 December 2024)
- ML20069K153 + (15:37:48, 16 December 2024)
- ML20069K151 + (15:37:49, 16 December 2024)
- ML20069K150 + (15:37:54, 16 December 2024)
- 05000387/LER-1982-022-03, /03L-0:on 820916,while Cleaning Control Rod Drive (CRD) Suction Strainers,Crd Pumps Tripped.Caused by Low Suction Pressure Due to Pressure Fluctuations from Cycling Condensate Reject Valve.Suction Trip Logic Modified + (15:37:56, 16 December 2024)
- 05000324/LER-1983-043, Forwards LER 83-043/01T-0 + (15:37:57, 16 December 2024)
- ML20069K145 + (15:37:58, 16 December 2024)
- ML20069K144 + (15:37:58, 16 December 2024)
- 05000282/LER-1982-018-03, /03L-0:on 820915,discovered That Two Ventilation Flow Tests Not Performed as Scheduled.Caused by Personnel Error.Tests Rescheduled + (15:38:00, 16 December 2024)
- 05000281/LER-1983-013-03, /03L-0:on 830323,ampere Readings for Heat Tracing Panel 8,circuit 2B Was Below Acceptance Criteria.Caused by Butt Splice Failure.Defective Butt Splice Replaced & Circuit Tested Satisfactorily + (15:38:03, 16 December 2024)
- ML20069K130 + (15:38:04, 16 December 2024)
- 05000335/LER-1983-020-03, /03L-0:on 830322,closing Latch Pin Broken on LPSI Pump 1B Breaker While Being Slow Closed for Alignment Check. Westinghouse porcel-line Air Circuit Breaker Model 50DHP250 Involved.Pins from Two Breakers on Bus Removed & Test + (15:38:06, 16 December 2024)
- ML20069K121 + (15:38:07, 16 December 2024)